Specifications
| Fuel | Diesel |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 800 kW |
| Standby kVA | 1000 |
| Prime power | 725 kW |
| Emissions | EPA Tier 2 |
| Controller | MGC-2020 |
| Oil capacity | 77.0 L |
| Alternator | Marathon 574RSL4038 (4-pole, Class H insulation) |
| Voltage options | 208 V, 240 V, 380 V, 480 V, 600 V, 4160 V |
| Phase | 3 |
| Rated current | 1204 A |
| Power factor | 0.8 |
| Circuit breaker | 1200 A |
| Battery cranking | 2800 CCA |
| Battery voltage | 24 V |
| Coolant capacity | 316 L |
| Max ambient | 50 °C |
| Dimensions (L×W×H) | 4375×1905×2623 mm |
| Dry weight | 5737 kg |
| Sound level | 88.9 dBA @ 7 m |
| Fuel tank | 5262.0 L |
| Tank runtime | 24 hr |
Engine
| Oil capacity | 77.0 L |
|---|---|
| Coolant capacity | 110.0 L |
| Displacement | 23.9 L |
| Aspiration | Turbocharged |
| Rated speed | 1800 rpm |
Common questions
What is the power rating of the MTU DG12V2000A3N?
The MTU DG12V2000A3N is rated 800 kW standby (1000.0 kVA).
What engine is in the MTU DG12V2000A3N?
The MTU DG12V2000A3N is powered by the MTU 12V2000G85TB engine.
Is the MTU DG12V2000A3N diesel or gas?
The MTU DG12V2000A3N runs on Diesel.
What is the oil capacity of the MTU DG12V2000A3N?
The MTU 12V2000G85TB engine in the MTU DG12V2000A3N has an oil capacity of 77.0 liters.
Which alternator is fitted to the MTU DG12V2000A3N?
The MTU DG12V2000A3N uses a Marathon 574RSL4038 alternator. It has 4 poles. Insulation class H.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Standby | 50% | 111.3 | 29.4 |
| Standby | 75% | 164.6 | 43.5 |
| Standby | 100% | 218.8 | 57.8 |