Home›MTU›MTU DG12V2000A3N

MTU DG12V2000A3N Generator Set

The MTU DG12V2000A3N is a 800 kW (1000 kVA) Diesel standby generator set powered by a MTU 12V2000G85TB engine. It is available at 208 V, 240 V, 380 V, 480 V, 600 V and 4160 V, 3-phase, 60 Hz and rated 1204 A. It holds about 77 L (20.3 gal) of oil and 316 L (83.5 gal) of coolant, with a maximum ambient rating of 50 °C. Starting uses battery rated 2800 CCA at 24 V. The set measures 4375×1905×2623 mm (172.2×75.0×103.3 in), weighs about 5737 kg (12648 lb) and produces 88.9 dBA at 7 m. An integrated tank holds 5262 L (1390.1 gal), roughly 24 hours of runtime.

800 kW
Standby
23.9 L
Displacement
77.0 L
Oil capacity
1
Document types

How to read your MTU serial & model number →

Typical fuel consumption for 800–805 kW Diesel generators →

Compare with other 800–805 kW Diesel generators →

Specifications

FuelDiesel
Frequency60.0 Hz
Standby power800 kW
Standby kVA1000
Prime power725 kW
EmissionsEPA Tier 2
ControllerMGC-2020
Oil capacity77.0 L
AlternatorMarathon 574RSL4038 (4-pole, Class H insulation)
Voltage options208 V, 240 V, 380 V, 480 V, 600 V, 4160 V
Phase3
Rated current1204 A
Power factor0.8
Circuit breaker1200 A
Battery cranking2800 CCA
Battery voltage24 V
Coolant capacity316 L
Max ambient50 °C
Dimensions (L×W×H)4375×1905×2623 mm
Dry weight5737 kg
Sound level88.9 dBA @ 7 m
Fuel tank5262.0 L
Tank runtime24 hr

Engine

MTU 12V2000G85TB
Oil capacity77.0 L
Coolant capacity110.0 L
Displacement23.9 L
AspirationTurbocharged
Rated speed1800 rpm

Filters for the MTU 12V2000G85TB

2

Engine-mounted filters the filter manufacturers list for this engine family. These come from the engine, not from this generator set’s own parts list, so confirm against your serial number before ordering.

Listed for this engine in only one kind of machine, so they may depend on how the engine was installed:

SystemFilterDescriptionCross-references
Fuel / water separatorP502404Fuel Filter, Water Separator Spin-OnMTU 0020920601, MTU 20920601, BALDWIN BF7987, SDMO 330510032 KuduParts $18.00 FridayParts $20.68
Fuel / water separatorP552216Fuel Filter, Water Separator Spin-On Twist&DrainNAPA 3613, BALDWIN BF1216, FURUKAWA 1257972H1, CATERPILLAR 1510240 buy

Common questions

What is the power rating of the MTU DG12V2000A3N?

The MTU DG12V2000A3N is rated 800 kW standby (1000.0 kVA).

What engine is in the MTU DG12V2000A3N?

The MTU DG12V2000A3N is powered by the MTU 12V2000G85TB engine.

Is the MTU DG12V2000A3N diesel or gas?

The MTU DG12V2000A3N runs on Diesel.

What is the oil capacity of the MTU DG12V2000A3N?

The MTU 12V2000G85TB engine in the MTU DG12V2000A3N has an oil capacity of 77.0 liters.

How much coolant does the MTU DG12V2000A3N hold?

The MTU DG12V2000A3N cooling system holds 316 liters (83.5 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.

What is the prime power rating of the MTU DG12V2000A3N?

The MTU DG12V2000A3N is rated 725 kW prime, against 800 kW standby.

What is the sound level of the MTU DG12V2000A3N?

The MTU DG12V2000A3N is rated at 88.9 dBA at 7 m, per the manufacturer specification sheet.

How much does the MTU DG12V2000A3N weigh?

The MTU DG12V2000A3N has a dry weight of 5737 kg (12647 lb).

What size fuel tank does the MTU DG12V2000A3N have?

The MTU DG12V2000A3N has a 5262 liter (1390 US gallon) fuel tank, giving about 24 hours of runtime.

What voltages is the MTU DG12V2000A3N available in?

The MTU DG12V2000A3N is offered in 208 V, 240 V, 380 V, 480 V, 600 V, 4160 V, 3-phase.

What size battery does the MTU DG12V2000A3N need?

The MTU DG12V2000A3N uses 24 V each, 2800 CCA, per the manufacturer specification sheet.

Which alternator is fitted to the MTU DG12V2000A3N?

The MTU DG12V2000A3N uses a Marathon 574RSL4038 alternator. It has 4 poles. Insulation class H.

Fuel consumption

RatingLoadL/hgal/h
Standby50%111.329.4
Standby75%164.643.5
Standby100%218.857.8