Specifications
| Fuel | Diesel |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 800 kW |
| Standby kVA | 1000 |
| Prime power | 725 kW |
| Emissions | EPA Tier 2 |
| Controller | MGC-2020 |
| Oil capacity | 77.0 L |
| Alternator | Marathon 574RSL4038 (4-pole, Class H insulation) |
| Voltage options | 208 V, 240 V, 380 V, 480 V, 600 V, 4160 V |
| Phase | 3 |
| Rated current | 1204 A |
| Power factor | 0.8 |
| Circuit breaker | 1200 A |
| Battery cranking | 2800 CCA |
| Battery voltage | 24 V |
| Coolant capacity | 316 L |
| Max ambient | 50 °C |
| Dimensions (L×W×H) | 4375×1905×2623 mm |
| Dry weight | 5737 kg |
| Sound level | 88.9 dBA @ 7 m |
| Fuel tank | 5262.0 L |
| Tank runtime | 24 hr |
Engine
| Oil capacity | 77.0 L |
|---|---|
| Coolant capacity | 110.0 L |
| Displacement | 23.9 L |
| Aspiration | Turbocharged |
| Rated speed | 1800 rpm |
Filters for the MTU 12V2000G85TB
2Engine-mounted filters the filter manufacturers list for this engine family. These come from the engine, not from this generator set’s own parts list, so confirm against your serial number before ordering.
Listed for this engine in only one kind of machine, so they may depend on how the engine was installed:
| System | Filter | Description | Cross-references | |
|---|---|---|---|---|
| Fuel / water separator | P502404 | Fuel Filter, Water Separator Spin-On | MTU 0020920601, MTU 20920601, BALDWIN BF7987, SDMO 330510032 | KuduParts $18.00 FridayParts $20.68 |
| Fuel / water separator | P552216 | Fuel Filter, Water Separator Spin-On Twist&Drain | NAPA 3613, BALDWIN BF1216, FURUKAWA 1257972H1, CATERPILLAR 1510240 | buy |
Common questions
What is the power rating of the MTU DG12V2000A3N?
The MTU DG12V2000A3N is rated 800 kW standby (1000.0 kVA).
What engine is in the MTU DG12V2000A3N?
The MTU DG12V2000A3N is powered by the MTU 12V2000G85TB engine.
Is the MTU DG12V2000A3N diesel or gas?
The MTU DG12V2000A3N runs on Diesel.
What is the oil capacity of the MTU DG12V2000A3N?
The MTU 12V2000G85TB engine in the MTU DG12V2000A3N has an oil capacity of 77.0 liters.
How much coolant does the MTU DG12V2000A3N hold?
The MTU DG12V2000A3N cooling system holds 316 liters (83.5 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.
What is the prime power rating of the MTU DG12V2000A3N?
The MTU DG12V2000A3N is rated 725 kW prime, against 800 kW standby.
What is the sound level of the MTU DG12V2000A3N?
The MTU DG12V2000A3N is rated at 88.9 dBA at 7 m, per the manufacturer specification sheet.
How much does the MTU DG12V2000A3N weigh?
The MTU DG12V2000A3N has a dry weight of 5737 kg (12647 lb).
What size fuel tank does the MTU DG12V2000A3N have?
The MTU DG12V2000A3N has a 5262 liter (1390 US gallon) fuel tank, giving about 24 hours of runtime.
What voltages is the MTU DG12V2000A3N available in?
The MTU DG12V2000A3N is offered in 208 V, 240 V, 380 V, 480 V, 600 V, 4160 V, 3-phase.
What size battery does the MTU DG12V2000A3N need?
The MTU DG12V2000A3N uses 24 V each, 2800 CCA, per the manufacturer specification sheet.
Which alternator is fitted to the MTU DG12V2000A3N?
The MTU DG12V2000A3N uses a Marathon 574RSL4038 alternator. It has 4 poles. Insulation class H.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Standby | 50% | 111.3 | 29.4 |
| Standby | 75% | 164.6 | 43.5 |
| Standby | 100% | 218.8 | 57.8 |
Available documents
This page was generated from the 2 manufacturer documents above by automated extraction; every figure shown is copied from one of them. How the data is compiled.