HomeMTUMTU 12V2000 DS800

MTU 12V2000 DS800 Generator Set

The MTU 12V2000 DS800 is a 800 kW (1000 kVA) Diesel #2 standby generator set powered by a MTU 12V2000G85TB engine. It is available at 208 V, 240 V, 380 V, 480 V, 600 V and 4160 V, 3-phase, 60 Hz and rated 2515 A. It holds about 77 L (20.3 gal) of oil and 372 L (98.3 gal) of coolant, with a maximum ambient rating of 50 °C. Starting uses 4 group-8 batteries rated 2800 CCA at 24 V. The set measures 4674.75×2292×2341.3 mm (184.0×90.2×92.2 in), weighs about 7883 kg (17379 lb) and produces 92 dBA at 7 m. An integrated tank holds 5262 L (1390.1 gal), roughly 24 hours of runtime.

800 kW
Standby
23.9 L
Displacement
77.0 L
Oil capacity
2
Document types

How to read your MTU serial & model number →

Specifications

FuelDiesel #2
Frequency60.0 Hz
Standby power800 kW
Standby kVA1000
Prime power725 kW
EmissionsEPA Tier 2
ControllerMGC-2020
Oil capacity77.0 L
AlternatorLSA 49.1 L11
Voltage options208 V, 240 V, 380 V, 480 V, 600 V, 4160 V
Phase3
Rated current[2515, 2180, 1377, 1090, 872, 126] A
Power factor0.8
Circuit breaker1200 A
Battery group8D
Battery cranking2800 CCA
Battery voltage24 V
Battery quantity4
Coolant capacity372 L
Max ambient50 °C
Dimensions (L×W×H)4674×2292×2341 mm
Dry weight7883 kg
Sound level92.0 dBA @ 7 m
Fuel tank5262.0 L
Tank runtime24 hr

Engine

MTU 12V2000G85TB
Oil capacity77.0 L
Coolant capacity110.0 L
Displacement23.9 L
Aspiration4-Cycle
Rated speed1800 rpm

Maintenance & consumables

for the MTU 12V2000G85TB
ItemSpecCapacityPart #Interval
Air filterDry find
Fuel filter8690920031 PartsGeek
Oil filter find
Belt find
Coolant
Oil

Common questions

What is the power rating of the MTU 12V2000 DS800?

The MTU 12V2000 DS800 is rated 800 kW standby (1000.0 kVA).

What engine does the MTU 12V2000 DS800 use?

The MTU 12V2000 DS800 is powered by the MTU 12V2000G85TB engine.

What fuel does the MTU 12V2000 DS800 use?

The MTU 12V2000 DS800 runs on Diesel #2.

What is the oil capacity of the MTU 12V2000 DS800?

The MTU 12V2000G85TB engine in the MTU 12V2000 DS800 has an oil capacity of 77.0 liters.

What alternator does the MTU 12V2000 DS800 use?

The MTU 12V2000 DS800 uses a LSA 49.1 L11 alternator.

Parts

3
Part #DescriptionQtySystem
X00038929HOSE ASM FUEL 12V S2000 ADEC1Hose PartsGeek
23524563KIT, CLOSED LOOP BREATHER SYSTEM 12V20001Service part / kit PartsGeek
23524780KIT, ENGINE BLOCK HEATER 120V (12V 2000)1Service part / kit PartsGeek

Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.

Fuel consumption

RatingLoadL/hgal/h
Prime
Prime50%104.0
Prime75%153.0
Prime100%204.0
Standby
Standby50%114.030.0
Standby75%168.045.0
Standby100%224.059.0

Available documents

Brochure — 16120643 PowerGeneration Solutionguide 1 2020 (MTU)Spec sheet — 231082 PG Spec 12V2000DS800 725kW 3B T2 SCAQMD 60Hz (MTU)Spec sheet — 231083 PG Spec 12V2000DS800 800kW 3D T2 60Hz (MTU)Spec sheet — 231083 PG Spec 12V2000DS800 800kW 3D T2 SCAQMD 60Hz (MTU)Spec sheet — EngineersGuidebook (MTU)Spec sheet — EngineersGuidebookUpdate102017 (MTU)Spec sheet — MTU-Engineers-Guidebook-2014 (MTU)Spec sheet — MTU 12V2000 DS800 725kW Prime (MTU)Spec sheet — MTU 12V2000 DS800 800kW Standby (MTU)Spec sheet — PSC 2ND POD - 28 - ssuggs@weilerengineering.org - KWRU FIlter CCC Replacement Replacement Generator Scope (MTU)