Specifications
| Fuel | Diesel |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 2000 kW |
| Standby kVA | 2500 |
| Prime power | 1825 kW |
| Emissions | EPA Tier 2 |
| Controller | DGC-2020 |
| Oil capacity | 280.0 L |
| Alternator | Marathon 744RSL4056 |
| Voltage options | 277/480 V |
| Phase | 3 |
| Rated current | 3010 A |
| Power factor | 0.8 |
| Circuit breaker | 3010 A |
| Battery group | 24 |
| Battery cranking | 1800 CCA |
| Battery voltage | 24 V |
| Battery quantity | 1 |
| Coolant capacity | 159 L |
| Max ambient | 77 °C |
| Dimensions (L×W×H) | 2340×1372×414 mm |
| Dry weight | 34700 kg |
| Fuel tank | 1500.0 L |
| Tank runtime | 12.5 hr |
Engine
| Oil capacity | 61.0 L |
|---|---|
| Coolant capacity | 42.0 L |
| Displacement | 60.2 L |
| Aspiration | Turbocharged and Low Temp Aftercooled (2P/2L) |
| Rated speed | 1800 rpm |
Maintenance & consumables
for the Cummins/Onan QSK60-G6| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Battery | Cold Soak @ -18 °C to 0 °C (0 °C to 32°F) | — |
Common questions
What is the power rating of the MQ Power EGC2000C?
The MQ Power EGC2000C is rated 2000 kW standby (2500.0 kVA).
What engine is in the MQ Power EGC2000C?
The MQ Power EGC2000C is powered by the Cummins/Onan QSK60-G6 engine.
Is the MQ Power EGC2000C diesel or gas?
The MQ Power EGC2000C runs on Diesel.
How much oil does the MQ Power EGC2000C take?
The Cummins/Onan QSK60-G6 engine in the MQ Power EGC2000C has an oil capacity of 61.0 liters.
What alternator does the MQ Power EGC2000C use?
The MQ Power EGC2000C uses a Marathon 744RSL4056 alternator.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 25% | 153.0 | 40.0 |
| Prime | 50% | 269.0 | 71.0 |
| Prime | 75% | 370.0 | 98.0 |
| Prime | 100% | 469.0 | 124.0 |
| Standby | 100% | 469.0 | 124.0 |