Specifications
| Fuel | Diesel |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 300 kW |
| Standby kVA | 375 |
| Prime power | 270 kW |
| Emissions | Tier 3 |
| Controller | Decision-Maker 550 (also Decision-Maker 3+ |
| Oil capacity | 30.0 L |
| Alternator | 4UA13 (4-pole, Class Class H insulation) |
| Voltage options | 120/208 V, 120/240 V, 127/220 V, 139/240 V, 220/380 V, 240/416 V, 277/480 V, 347/600 V |
| Phase | 3 |
| Rated current | 1041 A |
| Power factor | 0.8 |
| Battery cranking | 950 CCA |
| Battery voltage | 12 V |
| Battery quantity | 2 |
| Coolant capacity | 45.4 L |
| Engine jacket water | 22.7 L |
| Max ambient | 50 °C |
| Dimensions (L×W×H) | 3500×1250×1941 mm |
| Wet weight | 2903 kg |
Engine
| Oil capacity | 30.0 L |
|---|---|
| Coolant capacity | 22.7 L |
| Displacement | 12.7 L |
| Aspiration | Turbocharged, Aftercooled |
| Rated speed | 1800 rpm |
Maintenance & consumables
for the Detroit Diesel S60| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Air filter | Clean/Replace | — | 500 hr | ||
| Fuel filter | Primary/Secondary | — | 250 hr | ||
| Oil filter | Cartridge | — | 250 hr | ||
| Battery | Replace | — | 250 hr | ||
| Belt | Replace | — | 250 hr | ||
| Coolant | Check/Clean | 45.4 | — | 250 hr | |
| Coolant filter | — | 50 hr | |||
| Oil | 36.0 L | — | 50 hr | ||
| Spark plug | Check/Replace | — | 250 hr |
Service specifications
31| Type | Item | Value | Unit | Condition |
|---|---|---|---|---|
| Other | 10 in. weld flange bolt circle diameter B | 361.95 | mm (14.25 in.) | |
| Other | 10 in. weld flange outside diameter C | 406.4 | mm (16.0 in.) | |
| Other | 10 in. weld flange quantity of bolts / bolt hole diameter D | 12, 25.40 | mm (1.00 in.) | |
| Other | 12 in. weld flange bolt circle diameter B | 431.80 | mm (17.00 in.) | |
| Other | 12 in. weld flange outside diameter C | 482.6 | mm (19.0 in.) | |
| Other | 12 in. weld flange quantity of bolts / bolt hole diameter D | 12, 25.40 | mm (1.00 in.) | |
| Other | 14 in. weld flange bolt circle diameter B | 476.25 | mm (18.75 in.) | |
| Other | 14 in. weld flange outside diameter C | 533.4 | mm (21.0 in.) | |
| Other | 14 in. weld flange quantity of bolts / bolt hole diameter D | 12, 28.58 | mm (1.13 in.) | |
| Other | 16 in. weld flange bolt circle diameter B | 539.75 | mm (21.25 in.) | |
| Other | 16 in. weld flange outside diameter C | 596.9 | mm (23.5 in.) | |
| Other | 16 in. weld flange quantity of bolts / bolt hole diameter D | 16, 28.58 | mm (1.13 in.) | |
| Other | 18 in. weld flange bolt circle diameter B | 577.85 | mm (22.75 in.) | |
| Other | 18 in. weld flange outside diameter C | 635.0 | mm (25.0 in.) | |
| Other | 18 in. weld flange quantity of bolts / bolt hole diameter D | 16, 31.75 | mm (1.25 in.) | |
| Other | 20 in. weld flange bolt circle diameter B | 635.00 | mm (25.00 in.) | |
| Other | 20 in. weld flange outside diameter C | 698.5 | mm (27.5 in.) | |
| Other | 20 in. weld flange quantity of bolts / bolt hole diameter D | 20, 31.75 | mm (1.25 in.) | |
| Other | 5 in. weld flange bolt circle diameter B | 215.90 | mm (8.50 in.) | |
| Other | 5 in. weld flange outside diameter C | 241.30 | mm (9.50 in.) | |
| Other | 5 in. weld flange quantity of bolts / bolt hole diameter D | 8, 22.23 | mm (0.88 in.) | |
| Other | 6 in. weld flange bolt circle diameter B | 254.0 | mm (10.0 in.) | |
| Other | 6 in. weld flange outside diameter C | 279.4 | mm (11.0 in.) | |
| Other | 6 in. weld flange quantity of bolts / bolt hole diameter D | 8, 22.23 | mm (0.88 in.) | |
| Other | 8 in. weld flange bolt circle diameter B | 298.45 | mm (11.75 in.) | |
| Other | 8 in. weld flange outside diameter C | 342.9 | mm (13.5 in.) | |
| Other | 8 in. weld flange quantity of bolts / bolt hole diameter D | 8, 22.23 | mm (0.88 in.) | |
| Other | Weld flange angle A (10, 12, 14 in. nominal pipe size) | 30 | deg. | |
| Other | Weld flange angle A (16, 18, 20 in. nominal pipe size) | 22.5 | deg. | |
| Other | Weld flange angle A (5, 6, 8 in. nominal pipe size) | 45 | deg. | |
| Pressure | Maximum allowable exhaust back pressure | 10.2 | kPa | at rated kW, dry exhaust |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Recommended fluids
| Fluid | Grade | Standard | Ambient | Capacity | Notes |
|---|---|---|---|---|---|
| Fuel | #2 Diesel | Recommended fuel #2 Diesel; max fuel flow 329 Lph (86.8 gph); supply line min ID 13 mm (0.50 in.), return line min ID 8 mm (0.31 in.); max lift 2.1 m (6.8 ft.) |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Voltage reconnection
| Voltage | Phase | Connection | Leads | Notes |
|---|---|---|---|---|
| 120/208 | 3 | 12, Reconnectable | 60 Hz, 3-phase, 0.8 PF; Standby 300 kW/375 kVA, 1041 A; Prime 270 kW/338 kVA, 937 A | |
| 120/240 | 3 | 12, Reconnectable | 60 Hz, 3-phase, 0.8 PF; Standby 300 kW/375 kVA, 902 A; Prime 270 kW/338 kVA, 812 A | |
| 127/220 | 3 | 12, Reconnectable | 60 Hz, 3-phase, 0.8 PF; Standby 300 kW/375 kVA, 984 A; Prime 270 kW/338 kVA, 886 A | |
| 139/240 | 3 | 12, Reconnectable | 60 Hz, 3-phase, 0.8 PF; Standby 300 kW/375 kVA, 902 A; Prime 270 kW/338 kVA, 812 A | |
| 220/380 | 3 | 12, Reconnectable | 60 Hz, 3-phase, 0.8 PF; Standby 280 kW/350 kVA, 532 A; Prime 255 kW/319 kVA, 484 A | |
| 240/416 | 3 | 12, Reconnectable | 60 Hz, 3-phase, 0.8 PF; Standby 300 kW/375 kVA, 520 A; Prime 270 kW/338 kVA, 468 A | |
| 277/480 | 3 | 12, Reconnectable | 60 Hz, 3-phase, 0.8 PF; Standby 300 kW/375 kVA, 451 A; Prime 270 kW/338 kVA, 406 A | |
| 347/600 | 3 | 12, Reconnectable | 60 Hz, 3-phase, 0.8 PF; Standby 300 kW/375 kVA, 361 A; Prime 270 kW/338 kVA, 325 A |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Common questions
What size generator is the Kohler 300REOZDD?
The Kohler 300REOZDD is rated 300 kW standby (375.0 kVA).
What engine is in the Kohler 300REOZDD?
The Kohler 300REOZDD is powered by the Detroit Diesel S60 engine.
What fuel does the Kohler 300REOZDD use?
The Kohler 300REOZDD runs on Diesel.
How much oil does the Kohler 300REOZDD take?
The Detroit Diesel S60 engine in the Kohler 300REOZDD has an oil capacity of 30.0 liters.
What is the coolant capacity of the Kohler 300REOZDD?
The Kohler 300REOZDD cooling system holds 45.4 liters (12.0 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.
What is the prime power rating of the Kohler 300REOZDD?
The Kohler 300REOZDD is rated 270 kW prime (338 kVA), against 300 kW standby.
What voltage does the Kohler 300REOZDD produce?
The Kohler 300REOZDD is offered in 120/208 V, 120/240 V, 127/220 V, 139/240 V, 220/380 V, 240/416 V, 3-phase.
What size battery does the Kohler 300REOZDD need?
The Kohler 300REOZDD uses 2 batteryies, 12 V each, 950 CCA, per the manufacturer specification sheet.
Which alternator is fitted to the Kohler 300REOZDD?
The Kohler 300REOZDD uses a 4UA13 alternator. It has 4 poles. Insulation class Class H.
Parts
9| Part # | Description | Qty | System | |
|---|---|---|---|---|
| 279261 | Filter, fuel | 1 | Fuel filter | Amazon $37.36 eBay $292.07 KuduParts $42.00 |
| 360A | Wire size | 1 | Wire | Amazon eBay FridayParts $193.96 |
| 440A | Wire size | 1 | Wire | Amazon eBay FridayParts $20.50 |
| F1-5 | Fuse 4A | 1 | Fuse | Amazon Amazon eBay eBay |
| GM13224 | Filter, oil | 1 | Oil filter | Amazon eBay $60.00 |
| GM30594 | Filter, fuel, secondary | 1 | Fuel filter | Amazon $109.99 eBay $60.00 KuduParts $59.00 |
| P1-3 | Amperemeter | 1 | Ammeter | Amazon eBay |
| Q1.1 | Main circuit breaker | 1 | Breaker | buy |
| T1-3 | Current transformer | 1 | Transformer | Amazon eBay KuduParts $43.00 |
Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 25% | 24.6 | 6.5 |
| Prime | 50% | 43.9 | 11.6 |
| Prime | 75% | 65.5 | 17.3 |
| Prime | 100% | 85.9 | 22.7 |
| Standby | 25% | 27.6 | 7.3 |
| Standby | 50% | 51.9 | 13.7 |
| Standby | 75% | 76.5 | 20.2 |
| Standby | 100% | 96.1 | 25.4 |
Available documents
This page was generated from the 3 manufacturer documents above by automated extraction; every figure shown is copied from one of them. How the data is compiled.