Home›Generac›Generac MMG75

Generac MMG75 Generator Set

The Generac MMG75 is a 86 kW (107 kVA) standby generator set powered by a John Deere PE4045HFG92 engine. It is available at 120 V, 139 V, 208 V, 220 V, 240 V and 277 V, 3Ø, 60 Hz and rated 297 A. It holds about 15.5 L (4.1 gal) of oil and 4.5 L (1.2 gal) of coolant, with a maximum ambient rating of 120 °C. Starting uses 1 group-24 battery rated 720 CCA at 12 V. The set measures 3020×1020×1570 mm (118.9×40.2×61.8 in), weighs about 1600 kg (3527 lb) and produces 68 dBA at 23 m. An integrated tank holds 625 L (165.1 gal), roughly 31 hours of runtime. The same PE4045HFG92 engine also powers generator sets from Magnum.

86 kW
Standby
4.5 L
Displacement
15.5 L
Oil capacity
4
Document types

How to read your Generac serial & model number →

Specifications

Frequency60.0 Hz
Standby power86 kW
Standby kVA107
Prime power77 kW
Emissions4i
ControllerPower Zone
Oil capacity15.5 L
AlternatorMarathon 361PSL1602
Voltage options120 V, 139 V, 208 V, 220 V, 240 V, 277 V
Phase3Ø
Rated current297 A
Power factor1 (1Ø), 0.8 (3Ø)
Circuit breaker300 A
Battery group24
Battery cranking720 CCA
Battery voltage12 V
Battery quantity1
Max ambient120 °C
Dimensions (L×W×H)3020×1020×1570 mm
Dry weight1600 kg
Sound level68.0 dBA @ 23 m
Fuel tank625.0 L
Tank runtime31 hr

Engine

John Deere PE4045HFG92
Oil capacity14.7 L
Coolant capacity4.5 L
Displacement4.5 L
Aspirationturbocharged
Rated speed1800 rpm

Same engine, other brands

1 brand

The John Deere PE4045HFG92 in this set also powers 1 generator set sold under 1 other brand. Service parts and maintenance intervals for the engine are shared; enclosure, alternator, controller and ratings are not.

BrandModels
MagnumMMG75

Maintenance & consumables

for the John Deere PE4045HFG92
ItemSpecCapacityPart #Interval
Air filter—300 hr
Fuel filter—1000 hr
Oil filter—300 hr
Battery—250 hr
Belt—500 hr
Coolant20.8—1000 hr
Coolant filter—
Oil15.5—300 hr
Spark plug—1000 hr

Common questions

What size generator is the Generac MMG75?

The Generac MMG75 is rated 86 kW standby (107.0 kVA).

What engine does the Generac MMG75 use?

The Generac MMG75 is powered by the John Deere PE4045HFG92 engine.

How much oil does the Generac MMG75 take?

The John Deere PE4045HFG92 engine in the Generac MMG75 has an oil capacity of 14.7 liters.

What is the coolant capacity of the Generac MMG75?

The Generac MMG75 cooling system holds 4.5 liters (1.2 US gallons) for the engine, per the manufacturer specification sheet.

What is the prime power rating of the Generac MMG75?

The Generac MMG75 is rated 77 kW prime (97 kVA), against 86 kW standby.

How loud is the Generac MMG75?

The Generac MMG75 is rated at 68.0 dBA at 23 m, per the manufacturer specification sheet.

What is the dry weight of the Generac MMG75?

The Generac MMG75 has a dry weight of 1600 kg (3527 lb).

What size fuel tank does the Generac MMG75 have?

The Generac MMG75 has a 625 liter (165 US gallon) fuel tank, giving about 31 hours of runtime.

What voltages is the Generac MMG75 available in?

The Generac MMG75 is offered in 120 V, 139 V, 208 V, 220 V, 240 V, 277 V, 3Ø-phase.

How many cold cranking amps does the Generac MMG75 require?

The Generac MMG75 uses 1 battery, 12 V each, 720 CCA, group 24, per the manufacturer specification sheet.

What alternator does the Generac MMG75 use?

The Generac MMG75 uses a Marathon 361PSL1602 alternator.

Troubleshooting

3

Symptoms & remedies

SymptomCauseRemedy
Low Fuel LevelShutdown, Low fuel level, Unit not level, Fuel tank leaking, Damaged fuel sender or wiringCheck fuel level in LCD window of controller. Confirm that unit is sitting level to ensure an accurate reading. Check tank for leaks. Check for continuity between sender and engine controller.
Low Oil PressureShutdown, Low oil level, Oil leaking from engine, Oil pressure senderCheck oil level on dipstick. Add oil, if needed. Visually inspect the engine for leaks. Restart unit and verify loss of pressure. Shut down immediately if pressure does not reach 5 psi (34 kPa) within five seconds. See engine operator’s manual to identify corrective action.
Low Coolant LevelShutdown, Low coolant level, Coolant hoses leaking, Engine block or water pump leakingAllow engine to cool, then check coolant level in radiator. Add coolant, if needed.

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.

Parts

11
Part #DescriptionQtySystem
100-025Air Filter1Air filter Amazon eBay
100-030Oil Filter1Oil filter Amazon eBay
100-045Fuel Filter1Fuel filter Amazon eBay FridayParts $20.19
100-060Coolant Filter1Coolant filter Amazon eBay
100-085Belt2Belt Amazon eBay
100-100Spark Plug1Spark plug Amazon eBay
25-1476Air Filter Minders1Air filter Amazon eBay
25-1483Primary Air Cleaners1Air filter Amazon eBay
25-1639Fuel Filters1Fuel filter Amazon eBay
25-1648Oil Filters1Oil filter Amazon eBay
AN500T0106STARTER SWITCHStarter Amazon eBay

Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.

Fuel consumption

RatingLoadL/hgal/h
Prime50%2.69.8
Prime75%3.7414.2
Prime100%6.41.6
Standby25%3.80.97

Available documents

Operator's manual — Generac Towable Diesel Generator - MMG75D-MMG100D Owners Manual (Generac)Owner's manual — 33701 (Generac)Parts manual — Generac Mobile Diesel Generator Brochure (Generac)Service manual — 26635 (Generac)

This page was generated from the 4 manufacturer documents above by automated extraction; every figure shown is copied from one of them. How the data is compiled.

Other sets with this engine