HomeEnginesJohn Deere PE4045HFG92

John Deere PE4045HFG92 Engine

The John Deere PE4045HFG92 is a 4.5 L 4-cylinder turbocharged engine rated at 1800 rpm, producing up to 72 kW. It powers generator sets from Generac, John Deere and Magnum, including the MMG100D, MMG75, MMG100D and MMG100D. It holds 14.7 L (3.9 gal) of oil and 4.5 L (1.2 gal) of coolant.

Also known as: John Deere PE4045HFG92

4.5 L
Displacement
4
Cylinders
1800 rpm
Rated speed
72 kW
Gross power

Engine specifications

Oil capacity14.7 L
Coolant capacity4.5 L
Displacement4.5 L
Cylinders4
Aspirationturbocharged
Rated speed1800 rpm
Gross power72 kW

Common problems

8
  • LOW OIL PRESSURE SHUTDOWN
    Cause: Oil pressure is less than 20 psi (138 kPa), engine has oil leaks, or oil pressure sender is faulty.
    Fix: Check the level of the engine oil with the dipstick. Visually inspect the engine for oil leaks. If the oil level is good, restart the unit and verify the loss of oil pressure. Check the oil pressure sender.
  • LOW FUEL LEVEL SHUTDOWN
    Cause: Fuel level is low, fuel tank has leaks, or fuel level sender and wiring are damaged.
    Fix: Check the fuel level on the Home screen. Confirm that the generator is sitting level to ensure an accurate reading. Check for leaks in the fuel tank. If the fuel level is good and no leaks are found, check the fuel level sender and the connecting wiring for damage.
  • LOW COOLANT LEVEL SHUTDOWN
    Cause: Coolant level in the radiator is low.
    Fix: Allow the engine to cool. Check the coolant level in the radiator.
  • Engine shutdown
    Cause: Fuel tank running dry, oil pressure less than 20 psi, coolant level low, high coolant temperature
    Fix: Check fuel level and add if necessary; check for leaks; inspect engine for damage; check oil level and add if necessary; visually inspect engine for leaks; check coolant level and add if necessary; check radiator hoses, engine block, water pump for leaks; check oil to ensure no coolant mixed in; allow engine to cool before checking
  • Low Oil Pressure
    Cause: Shutdown, Low oil level, Oil leaking from engine, Oil pressure sender
    Fix: Check oil level on dipstick. Add oil, if needed. Visually inspect the engine for leaks. Restart unit and verify loss of pressure. Shut down immediately if pressure does not reach 5 psi (34 kPa) within five seconds. See engine operator’s manual to identify corrective action.
  • Low Fuel Level
    Cause: Shutdown, Low fuel level, Unit not level, Fuel tank leaking, Damaged fuel sender or wiring
    Fix: Check fuel level in LCD window of controller. Confirm that unit is sitting level to ensure an accurate reading. Check tank for leaks. Check for continuity between sender and engine controller.
  • Low Coolant Level
    Cause: Shutdown, Low coolant level, Coolant hoses leaking, Engine block or water pump leaking
    Fix: Allow engine to cool, then check coolant level in radiator. Add coolant, if needed.
  • HIGH COOLANT TEMPERATURE SHUTDOWN
    Cause: Coolant temperature is 230°F (110°C) or more
    Fix: Check coolant level in overflow jug, restart engine and read coolant temperature, add coolant if low

Compiled from service & troubleshooting documentation across every generator set that uses the John Deere PE4045HFG92.

Maintenance schedule

ItemSpecCapacityPart #Interval
Air filterAir Filter Replacement300 hr
Fuel filter1000 hr
Oil filterOil Filter Replacement300 hr
Battery250 hr
BeltInspect pulleys and bearings. Rotate and feel for hard turning or unusual sounds. If pulleys or bearings need replacement, contact John Deere.500 hr
Coolant20.8 L1000 hr
Coolant filter
OilOil Change15.5 L300 hr
Spark plug1000 hr

Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.

Service specifications

6
TypeItemValueUnitCondition
PressureOil pressure20psishutdown threshold
PressureOil pressure25psiwarning threshold
TemperatureCoolant temperature220°Fwarning threshold
TemperatureCoolant temperature230°Fshutdown threshold
VoltageBattery voltage11VDCunder warning
VoltageBattery voltage15VDCover warning

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

What is the oil capacity of the John Deere PE4045HFG92?

The John Deere PE4045HFG92 engine has an oil capacity of 14.7 liters.

What is the displacement of the John Deere PE4045HFG92?

The John Deere PE4045HFG92 has a displacement of 4.5 liters with 4 cylinders.

Which generators use the John Deere PE4045HFG92 engine?

The John Deere PE4045HFG92 powers 7 generator set(s), including Generac MMG100D, Generac MMG75, John Deere MMG100D, Magnum MMG100D, Magnum MMG100D Super Start.

How often should you change the oil in the John Deere PE4045HFG92?

The John Deere PE4045HFG92 oil change interval is every 300 hours.

What is a common problem with the John Deere PE4045HFG92 engine?

A commonly reported issue on generators using the John Deere PE4045HFG92 is: LOW OIL PRESSURE SHUTDOWN. Cause: Oil pressure is less than 20 psi (138 kPa), engine has oil leaks, or oil pressure sender is faulty.. Fix: Check the level of the engine oil with the dipstick. Visually inspect the engine for oil leaks. If the oil level is good, restart the unit and verify the loss of oil pressure. Check the oil pressure sender..