Service parts for the 20 kW 3-Phase
Grouped by system, with how many of each the parts manual calls for.
Air intake
1 requiredOil system
1 requiredElectrical
1 requiredIgnition
1 requiredPrices captured from merchant listings; some links are affiliate links. Confirm against your serial number before ordering.
Specifications
| Fuel | Natural Gas / LP Gas |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 20 kW |
| Controller | Evolution 2 HSB |
| Oil capacity | 1.8 L |
| Voltage options | 208 V |
| Phase | 3 |
| Rated current | 69.4 A |
| Power factor | 0.8 |
| Circuit breaker | 80 A |
| Battery group | 26R-540CCA or 35AGM-650CCA |
| Battery cranking | 540 CCA (26R) or 650 CCA (35AGM) CCA |
| Battery voltage | 12 V |
| Battery quantity | 1 |
| Dry weight | 211 kg |
Engine
| Oil capacity | 1.8 L |
|---|---|
| Displacement | 0.999 L |
| Aspiration | naturally aspirated |
| Rated speed | 3600 rpm |
Maintenance & consumables
for the Generac G-Force 1000 Series| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Air filter | 0J8478 | 1000 hr | Amazon $28.99 eBay $20.00 KuduParts $15.00 | ||
| Fuel filter | — | 200 hr | |||
| Oil filter | 070185E | 500 hr | Amazon $35.19 eBay $30.00 FridayParts $45.99 | ||
| Battery | 12 Volts, Group 26R 540 CCA minimum or Group 35AGM 650 CCA minimum | 0H3421S | Amazon eBay $283.32 | ||
| Belt | — | 200 hr | |||
| Coolant | — | ||||
| Oil | 3.75 | — | 500 hr | ||
| Spark plug | Gap 0.040 in. (1.02 mm); torque to 18.4 ft-lbs (25 Nm) | RC12YC | 1000 hr | Amazon $19.99 eBay $12.90 FridayParts $19.99 |
Service intervals
6| Item | Action | Hours | Months | Notes |
|---|---|---|---|---|
| Engine oil and oil filter | Replace | 100 hr | 12 mo | First service — After first 25 hours of operation. In cold weather (below 40°F) or continuous hot operation (above 85°F), change every year or 100 hours. |
| Engine air filter | Replace | 200 hr | 12 mo | Schedule A: Every year or 200 hours. |
| Spark plugs | Replace | 200 hr | 12 mo | Schedule A: Clean, check gap, replace every year or 200 hours. |
| Sediment trap | Clean | 400 hr | 48 mo | Schedule B: Every 4 years or 400 hours. Inspect and clean. |
| Valve clearance | Adjust | 400 hr | First service — After first 25 hours of operation, then every 400 hours. | |
| Battery condition, electrolyte level, and state of charge | Check | 12 mo | Every year, every 2 years, and every 4 years. |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Service specifications
5| Type | Item | Value | Unit | Condition |
|---|---|---|---|---|
| Gap | Spark plug gap | 0.040 | in | |
| Torque | Rocker arm jam nut | 174 | in-lbs | |
| Torque | Spark plug | 18.4 | ft-lbs | |
| Torque | Valve cover fasteners | 60 | in-lbs | Cross pattern |
| Valve clearance | Valve clearance | 0.002–0.004 | in | Engine cool |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Recommended fluids
| Fluid | Grade | Standard | Ambient | Capacity | Notes |
|---|---|---|---|---|---|
| Engine oil | Synthetic SAE 5W-30 | API Service Class SJ, SL, or better | -29°C to 50°C | 1.9 qt | All Generac oil kits meet minimum API Service Class. Do not use special additives. |
| Fuel | Natural Gas or LP Gas (vapor) | Natural Gas: minimum 1000 BTUs per cubic foot. LP Gas: minimum 2500 BTUs per cubic foot. Minimum LP tank size of 250 gal recommended. |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Fault codes
20| Code | Name | Meaning | Severity | Action |
|---|---|---|---|---|
| BATTERY PROBLEM | Battery Problem | Yellow LED illuminated in any state | Warning | Contact an IASD. |
| CHARGER WARNING | Charger Warning | Yellow LED illuminated in any state | Warning | Contact an IASD. |
| FUSE PROBLEM | Fuse Problem | Unit will not start in AUTO with utility loss | Shutdown | Check the 7.5 amp fuse. If blown, replace with ATO 7.5 amp fuse. If intact, contact an IASD. |
| HIGH TEMPERATURE | High Temperature | Unit shuts down during operation due to high temperature | Shutdown | Check ventilation around the generator, intake, exhaust, and rear of generator. If no obstructions present, contact an IASD. |
| INSPECT BATTERY | Inspect Battery | Yellow LED illuminated indicating battery inspection due | Warning | Inspect battery. Press ENTER to clear. |
| LOW BATTERY | Low Battery | Yellow LED illuminated in any state | Warning | Clear alarm. Check the battery. If condition displays GOOD, contact an IASD. If CHECK BATTERY, replace the battery. |
| LOW OIL PRESSURE | Low Oil Pressure | Unit will not start in AUTO with utility loss | Shutdown | Check oil level and add oil as needed. If oil level is correct, contact an IASD. |
| LOW VOLTS | Low Volts / Remove Load | Unit will not start in AUTO with utility loss | Shutdown | Clear alarm and remove household loads from the generator. Put in AUTO and restart. |
| MISWIRE | Miswire | Unit will not start in AUTO with utility loss | Shutdown | Contact an IASD. |
| NOT ACTIVATED | Not Activated | Unit will not start in AUTO with utility loss | Warning | Refer to Activation in installation manual. |
| OVERCRANK | Overcrank | Unit will not start in AUTO with utility loss | Shutdown | Check fuel line shutoff valve is ON. Clear alarm. Start the unit in MANUAL. If it does not start, contact an IASD. |
| OVERLOAD | Overload / Remove Load | Unit shuts down during operation due to overload | Shutdown | Clear alarm and remove household loads from the generator. Put in AUTO and restart. |
| OVERSPEED | Overspeed | Unit will not start in AUTO with utility loss | Shutdown | Contact an IASD. |
| OVERVOLTAGE | Overvoltage | Unit will not start in AUTO with utility loss | Shutdown | Contact an IASD. |
| RPM SENSE LOSS | RPM Sensor Loss | Unit was running and shut down, attempts to restart | Shutdown | Clear alarm and remove household loads from the generator. Put into AUTO and restart. If generator does not start, contact an IASD. |
| SERVICE A | Service A | Yellow LED illuminated indicating Schedule A maintenance due | Warning | Perform SERVICE A maintenance. Press ENTER to clear. |
| SERVICE B | Service B | Yellow LED illuminated indicating Schedule B maintenance due | Warning | Perform SERVICE B maintenance. Press ENTER to clear. |
| STEPPER OVERCURRENT | Stepper Overcurrent | Unit will not start in AUTO with utility loss | Shutdown | Contact an IASD. |
| UNDERSPEED | Underspeed | Unit will not start in AUTO with utility loss | Shutdown | Contact an IASD. |
| UNDERVOLTAGE | Undervoltage | Unit will not start in AUTO with utility loss | Shutdown | Contact an IASD. |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Procedures
7Valve Clearance Adjustment adjustment
⚠ Allow engine to cool before adjusting valve clearance
Tools: 13 mm wrench, 10 mm Allen wrench, Feeler gauge, Torque wrench
- Remove spark plug wire(s) and position away from plugs.
- Remove spark plug(s).
- Remove the four screws attaching the valve cover.
- Remove and discard the valve cover gasket.
- Make sure the piston is at top dead center (TDC) of its compression stroke.
- Remove the intake screen at the front of the engine to access the flywheel nut.
- Use a large socket and wrench to rotate the flywheel nut clockwise to position the piston at TDC.
- Loosen the rocker jam nut using a 13 mm wrench.
- Turn the pivot ball stud using a 10 mm Allen wrench while checking clearance.
- Adjust clearance to 0.002–0.004 in using a feeler gauge.
- Hold the pivot ball stud in place with a wrench and tighten the rocker arm jam nut to 174 in-lbs (19.68 Nm).
- Recheck valve clearance to verify it did not change.
- Install new valve cover gasket.
- Install the valve cover and tighten fasteners in a cross pattern to 60 in-lbs (6.8 Nm).
- Install spark plugs and torque to 18 ft-lbs (25 Nm).
Battery Maintenance maintenance
⚠ Disconnect negative battery cable first
⚠ Do not use tap water for battery
⚠ Remove jewelry and use insulated tools
Tools: Wrench for battery terminals
- Lift the lid and press the OFF button to shut down the generator.
- Remove the front panel.
- Remove the 7.5 amp fuse from the control panel.
- Remove the intake side panel.
- Disconnect the white battery charger cable.
- Inspect the battery posts and cables for tightness and corrosion.
- Tighten and clean as necessary.
- For unsealed batteries only: Disconnect the battery completely.
- Check the battery fluid level and fill with distilled water only if necessary.
- Have an IASD or qualified service technician check the state of charge and condition.
- Reconnect the battery cables and battery charger cable.
- Reinstall the intake side panel.
- Reinstall the 7.5 amp fuse.
- Place the controller in AUTO mode.
- Complete the Installation Wizard Menu.
Changing the Oil and Oil Filter maintenance
⚠ Allow engine to cool before draining oil
Tools: Oil drain hose, Oil filter wrench, Oil collection container, Clean cloth
- Press the MANUAL button on the control panel to start the engine.
- Run the engine until it is thoroughly warmed up.
- Press the OFF button to shut down the engine.
- Allow the engine to cool slightly.
- Lift the lid and remove the front panel.
- Pull the oil drain hose free of its retaining clip.
- Remove the cap from the hose and drain the oil into a suitable container.
- Replace the cap after draining and secure the hose with the retaining clip.
- Remove the old oil filter by turning it counterclockwise.
- Apply a light coating of clean engine oil to the gasket of the new filter.
- Screw the new filter on by hand until its gasket lightly contacts, then tighten an additional 3/4 to one full turn.
- Refill the engine with the proper recommended oil.
- Press the MANUAL button to start the engine and run for one minute.
- Check for leaks and press the OFF button to stop the engine.
- Wait five minutes and recheck the oil level.
Checking Engine Oil Level maintenance
Tools: Oil dipstick, Clean cloth
- Run the generator for approximately one minute cool-down period.
- Turn the main utility disconnect off.
- Turn the main line circuit breaker (MLCB) on the generator to OFF (OPEN).
- Turn the generator off and press the OFF button.
- Wait five minutes.
- Remove the oil dipstick and wipe it dry with a clean cloth.
- Completely insert the oil dipstick into the oil dipstick tube and remove it.
- Observe the oil level; should be at the FULL mark.
- If necessary, remove the oil fill cap and add oil until reaching the FULL mark.
- Insert the oil dipstick and fill cap back in place.
Cleaning the Sediment Trap maintenance
⚠ Fuel and vapors are extremely flammable and explosive
Tools: Clean-out tool, Pipe wrench, Gas leak detection fluid
- Lift the lid and press the OFF button to shut down the generator.
- Remove the front panel.
- Remove the intake side panel.
- Turn the generator fuel supply off.
- Remove the battery.
- Unscrew and remove the sediment trap cap.
- Use a clean-out tool to remove accumulated moisture and particles from the cap and body.
- Wipe the inside of each component with a clean, dry, lint-free cloth.
- Seal the threads of the cap with appropriate sealing compound.
- Install the cap and hand-tighten.
- Tighten the cap with an appropriately sized pipe wrench without overtightening.
- Turn the generator fuel supply on.
- Check for leaks by spraying all connection points with non-corrosive gas leak detection fluid.
- Install the battery.
- Install the intake side panel, put the generator into AUTO mode and close the lid.
Servicing the Air Cleaner maintenance
Tools: Screwdriver for cover clips
- Press the OFF button on the control panel to stop the generator.
- Lift the lid and remove the front panel.
- Remove the cover clips and air cleaner cover.
- Remove the old air filter element and discard it.
- Thoroughly clean the air cleaner enclosure of any dust or debris.
- Install a new air filter element.
- Install the air cleaner cover and fasten the cover clips.
- Verify that the air inlet duct is properly connected to the air cleaner cover.
- Press the AUTO button on the control panel to return to AUTO mode.
Spark Plug Service maintenance
Tools: Wire feeler gauge, Socket and torque wrench
- With the generator OFF and the engine cool, lift the lid and remove the front panel.
- Clean the area around the base of the spark plugs to keep dirt and debris out.
- Remove the spark plugs and check their condition.
- Install new plugs if the old plugs are worn or questionable.
- Clean the plugs by scraping or washing with a wire brush and commercial solvent.
- Do not blast the plugs to clean.
- Check the spark plug gap using a wire feeler gauge.
- Replace the spark plug if the gap is out of specification.
- Reinstall the spark plugs and torque to 18.4 ft-lbs (25 Nm).
- Press the control panel AUTO button to return to AUTO mode.
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Common questions
What is the power rating of the Generac 20 kW 3-Phase?
The Generac 20 kW 3-Phase is rated 20 kW standby.
What engine does the Generac 20 kW 3-Phase use?
The Generac 20 kW 3-Phase is powered by the Generac G-Force 1000 Series engine.
What kind of fuel does the Generac 20 kW 3-Phase run on?
The Generac 20 kW 3-Phase runs on Natural Gas / LP Gas.
How much oil does the Generac 20 kW 3-Phase take?
The Generac G-Force 1000 Series engine in the Generac 20 kW 3-Phase has an oil capacity of 1.8 liters.
Which oil filter part number does the Generac 20 kW 3-Phase take?
The Generac 20 kW 3-Phase uses oil filter part number 070185E.
What air filter fits the Generac 20 kW 3-Phase?
The Generac 20 kW 3-Phase uses air filter part number 0J8478.
Troubleshooting
6Symptoms & remedies
| Symptom | Cause | Remedy |
|---|---|---|
| Engine will not crank. | 1. Blown fuse. 2. Loose, corroded, or defective battery cables. 3. Defective starter contact. 4. Defective starter motor. 5. Discharged battery. | 1. Correct short circuit condition by replacing 7.5 amp fuse in generator control panel. Contact an Independent Authorized Service Dealer (IASD) if fuse continues to blow. 2. Tighten, clean, or replace as necessary.* 3. *See #2. 4. *See #2. 5. Charge or replace battery. |
| Engine cranks but will not start. | 1. No fuel. 2. Defective fuel solenoid (FS). 3. Open Wire 14 from controller. 4. Defective spark plug(s). 5. Valve clearance out of adjustment. | 1. Replenish fuel / turn on fuel valve. 2. * 3. * 4. Clean; check gap; replace plug(s) if necessary. 5. Reset valve clearance. |
| Engine starts hard and runs rough. | 1. Air cleaner plugged or damaged. 2. Defective spark plug(s). 3. Incorrect fuel pressure. 4. Fuel selector in wrong position. 5. Valve(s) out of adjustment. 6. Internal engine issue. | 1. Check and clean air cleaner. 2. Clean; check gap; replace plug(s) as needed. 3. Confirm fuel pressure to regulator is 10–12 in water column (19–22 mm Hg) for LP, and 3.5–7.0 in water column (9–13 mm Hg) for natural gas. 4. Turn fuel conversion valve to correct position. 5. Adjust valve clearance. 6. * |
| Generator is set to OFF, but the engine continues to run. | 1. Controller wired incorrectly. 2. Defective control board. | 1. * 2. * |
| No AC output from generator. | 1. Main line circuit breaker (MLCB) (generator disconnect) is OFF (OPEN). 2. Generator internal failure. 3. Engine may be warming up. Refer to Cold Smart Start. | 1. Reset generator disconnect to ON (CLOSED). 2. * 3. Check the controller screen to verify status. |
| No transfer to standby after utility source failure. | 1. MLCB (generator disconnect) is OFF (OPEN). 2. Defective transfer switch coil. 3. Defective transfer relay. 4. Transfer relay circuit open. 5. Defective control logic board. 6. Engine may be warming up. Refer to Cold Smart Start. | 1. Reset generator disconnect to ON (CLOSED). 2. * 3. * 4. * 5. * 6. Check the controller screen to verify status. |
Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing. Full Generac 20 kW 3-Phase troubleshooting guide (9 entries) →
Parts
62| Part # | Description | Qty | System | |
|---|---|---|---|---|
| 070185E | Oil Filter | 1 | Oil filter | Amazon $35.19 eBay $30.00 FridayParts $45.99 |
| 070185ES | Recommended oil filter (engine specifications table) | Oil filter | Amazon $16.99 eBay $30.00 FridayParts $22.99 | |
| 070185F | Oil filter | 1 | Oil filter | Amazon $31.99 eBay $18.50 |
| 0C2979 | GASKET, VALVE COVER | 2 | Gasket | Amazon eBay $4.89 |
| 0G0767A | Spark Plug (RC12YC or equivalent) | 2 | Spark plug | Amazon $17.29 eBay $18.00 |
| 0J8318 | Rotor Brushes | Brush | eBay | |
| 0J8478 | Air Filter | 1 | Air filter | Amazon $28.99 eBay $20.00 KuduParts $15.00 |
| 0J8478S | Recommended air filter (engine specifications table) | Air filter | Amazon $17.99 eBay $16.00 KuduParts $15.00 | |
| 0K3054 | AVR Air filter | 1 | Air filter | Amazon eBay |
| 0K3717 | EcoGen Oil System Drain Pump Kit | 1 | Pump | eBay |
| A0006487350 | AGM Group BTX20L Battery | Battery | Amazon eBay | |
| G005819-0 | 26R Wet Cell Battery | 1 | Battery | Amazon eBay |
| G006199-0 | PMM Starter Kit | Starter | Amazon eBay | |
| RC12YC | Spark Plug | 1 | Spark plug | Amazon $19.99 eBay $12.90 FridayParts $19.99 |
| 073590A | FUSE 5A X BUSS | 2 | Service part / kit | Amazon eBay $45.99 |
| 098290 | ASM MOTOR STEPPER | 1 | Service part / kit | Amazon eBay $65.00 |
| 098941A | Governor connector housing | 1 | Service part / kit | Amazon eBay |
| 098958A | CONNECTOR INTERFACE ASSEMBLY | 1 | Service part / kit | Amazon eBay $47.99 |
| 0A7568 | Door weldment 1.5EPS | 2 | Service part / kit | eBay $540.52 |
| 0D7178T | Control panel fuse | 1 | Service part / kit | Amazon $6.99 eBay $26.44 |
| 0D8656 | Mounting base 1.5L standard & acoustic | 1 | Service part / kit | Amazon eBay |
| 0D8657 | Radiator support 1.5L Mitsubishi | 1 | Service part / kit | eBay $339.95 |
| 0D8660 | Side brace 1.5L Mitsubishi | 2 | Service part / kit | eBay |
| 0D8664 | Duct acoustic & standard compartment 1.5L | 1 | Service part / kit | eBay |
| 0D8666 | Roof acoustic & standard compartment 1.5L | 1 | Service part / kit | eBay |
| 0G66240KEY | Service keys (pair) | 1 | Service part / kit | Amazon $6.99 eBay $5.95 |
| 0H34215 | 26R Exide Battery | 1 | Service part / kit | eBay |
| 0H3421S | 26R Exide Battery | 1 | Service part / kit | Amazon eBay $283.32 |
| 0L4836A | FUEL LINE FLEX 3/4 NO PVC (13,16-24KW) | 1 | Service part / kit | Amazon eBay $34.95 |
| 10000013645 | DECAL AUX SHUTDOWN (13,16-24KW) | 2 | Service part / kit | Amazon eBay |
| 10000029476 | BADGE ADHESITIVE GUARDIAN (24KW) | 1 | Service part / kit | Amazon eBay $5.99 |
| 10000044454 | EWAR SEGSI (ESE1) EN (13, 16-24KW) | 1 | Service part / kit | Amazon eBay |
| 929-0100 | 1 | Service part / kit | Amazon eBay | |
| G005621-0 | Auxiliary Transfer Switch Contact Kit | 1 | Service part / kit | Amazon Amazon eBay eBay |
| G005703-0 | Paint Kit | 1 | Service part / kit | Amazon Amazon eBay eBay |
| G005704-0 | Paint Kit | 1 | Service part / kit | Amazon eBay |
| G006186-0 | Power Management Module (50 Amps) | Service part / kit | Amazon eBay | |
| G006463-4 | Mobile Link | 1 | Service part / kit | Amazon eBay $99.99 |
| G006485-0 | Scheduled Maintenance Kit | 1 | Service part / kit | Amazon eBay $24.99 |
| G006829-0 | Scheduled Maintenance Kit | Service part / kit | Amazon eBay | |
| G007000-0 | Smart Management Module (50 amp) | 1 | Service part / kit | Amazon Amazon eBay $65.00 |
| G007000-1 | Generac Load Manager (50 amp) | Service part / kit | Amazon Amazon eBay $69.99 eBay $125.00 | |
| G007005-0 | Wi-Fi LP Fuel Level Monitor | 1 | Service part / kit | Amazon Amazon eBay |
| G007006-0 | Smart Management Module (100 amp) | 1 | Service part / kit | Amazon Amazon eBay $109.99 |
| G007006-1 | Generac Load Manager (100 amp) | Service part / kit | Amazon Amazon eBay $300.00 eBay | |
| G007009-0 | LTE LP Tank Fuel Level Monitor | 1 | Service part / kit | Amazon Amazon eBay $157.99 eBay $157.99 |
| G007027-0 | Fascia Base Wrap Kit | 1 | Service part / kit | Amazon eBay |
| G007101-0 | Battery Pad Warmer | 1 | Service part / kit | Amazon eBay $95.00 |
| G007102-0 | Oil Warmer | 1 | Service part / kit | Amazon eBay $119.95 |
| G007102-1 | Oil Heater | Service part / kit | Amazon eBay $79.99 | |
| G007103-1 | Breather Warmer | 1 | Service part / kit | Amazon eBay $105.99 |
| G007103-2 | Breather Heater | Service part / kit | Amazon eBay | |
| G007169-0 | Accessoire cellulaire Mobile Link ® 4G LTE | 1 | Service part / kit | Amazon Amazon eBay eBay |
| G007170-0 | Mobile Link® Cellular Accessories - Wi-Fi/Ethernet | 1 | Service part / kit | Amazon eBay |
| G007211-0 | Battery Heater | Service part / kit | Amazon eBay | |
| G007216-0 | Scheduled Maintenance Kit | Service part / kit | Amazon Amazon eBay $56.48 eBay $56.48 | |
| G007220-0 | Base Plug Kit - Bisque | 1 | Service part / kit | Amazon eBay |
| G007301-0 | High Altitude Kit | Service part / kit | Amazon eBay | |
| G007303-0 | High Altitude Kit (20 kW) | 1 | Service part / kit | Amazon eBay |
| G007305-0 | High Altitude Kit | Service part / kit | Amazon eBay | |
| G009918-0 | Touch-Up Paint Kit | Service part / kit | Amazon Amazon eBay eBay | |
| G050277 | DECAL OIL DRAIN (10,20-24KW) | 1 | Service part / kit | Amazon eBay |
Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.