Cummins/Onan MDKBH Generator Set

The Cummins/Onan MDKBH is a generator set.

2
Document types

How to read your Cummins/Onan serial & model number →

Service parts for the MDKBH

Grouped by system, with how many of each the parts manual calls for.

Fuel system

1 required

Oil system

1 required
185-7444Oil filter$9.09NAPA

Belts

1 required

Prices captured from merchant listings; some links are affiliate links. Confirm against your serial number before ordering.

Specifications

Ratings spec sheet not in our library yet — see the documents below.

Maintenance & consumables

ItemSpecCapacityPart #Interval
Fuel filterFuel Filter149-2106 Amazon eBay $34.99 NAPA $61.61 KuduParts $68.00
Oil filterOil Filter185-7444 Amazon eBay $29.95 NAPA $9.09 KuduParts $11.00 FridayParts $13.23
BeltV-Belt511-0197 Amazon eBay

Service intervals

24
ItemActionHoursMonthsNotes
Coolant LevelCheck8 hrBefore first startup of each day.
Engine Oil LevelCheck8 hrEvery Day / 8 Hrs
Exhaust SystemInspect8 hrEvery startup and every 8 hours of operation; check for leaks and loose hose clamps.
General InspectionInspect8 hrIncludes inspection of oil level, coolant level, fuel system, exhaust system, batteries and battery connections; before first start of day and after every 8 hours
Generator SetInspect8 hrGeneral Inspection; includes oil level, coolant level, fuel system, exhaust system, batteries and sea water strainer.
Sea Water StrainerClean8 hrClean if necessary and make sure sea cock is open.
BatteryCheck100 hr1 moSee battery manufacturer's recommendations.
Battery and Battery ConnectionsInspect100 hr1 moSee battery manufacturer's recommendations
Fuel FiltersDrain100 hr1 moEvery Month / 100 Hrs
Siphon BreakCheck100 hr1 moEvery Month / 100 Hrs
Siphon BreakInspect100 hr1 mo
Water from Fuel FilterDrain100 hr1 moEvery Month/100 Hrs
Engine Oil and Oil FilterChange200 hr12 moFirst service — Every Year/200 Hrs
Engine Oil/Oil FilterChange200 hr12 moFirst service — Every year/200 hours.
Fuel FiltersReplace200 hr12 moEvery year/200 hours; change if engine lacks power.
Oil/Oil FilterChange200 hrFirst service — Every Year / 200 Hrs
Brushes/Slip RingsCheck500 hrMust be performed by a trained and experienced mechanic.
Raw Water ImpellerReplace500 hr12 moEvery Year/500 Hrs
V-Belt TensionCheck500 hr1 moMust be performed by a trained and experienced mechanic.
Engine Valve LashAdjust800 hrMust be performed by a trained and experienced mechanic.
Pump ImpellerReplace800 hrMust be performed by a trained and experienced mechanic.
Generator Bearings, Drive Belt, Belt Tensioner & Drive CouplingCheck2000 hr60 moEvery 5 years/2000 hours; must be performed by a trained and experienced mechanic.
Coolant, Pressure Cap & ThermostatReplace24 moEvery 2 years. There is no zinc anode to replace.
Generator SetOther1 moExercise at least 1 hour every month if use is infrequent; run at 1/4 to 3/4 load.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

60
TypeItemValueUnitCondition
GapV-belt deflection0.4inch (10 mm)20 pounds (10 kg) applied to middle of pulley span
Injection timingFuel Injection Timing18.25 − 19.75° BTDC
Injection timingFuel Injection Timing18° – 20°BTDC
Injection timingFuel injection timing18 - 20degrees BTDCtiming marks line up at 19 degrees BTDC
OtherBattery Charging OutputTrickle (3 amps)
OtherBattery cable gauge1AWGtotal cable length 22 ft (6.7 m); approx. diameter 9.43 mm
OtherBattery cable gauge1/0AWGtotal cable length 30 ft (9.1 m); approx. diameter 9.46 mm
OtherBattery cable gauge2AWGtotal cable length 18 ft (5.5 m); approx. diameter 7.42 mm
OtherBattery cable gauge3AWGtotal cable length 14 ft (4.3 m); approx. diameter 6.61 mm
OtherBattery cable gauge4AWGtotal cable length 10 ft (3 m); approx. diameter 5.88 mm
OtherCombustion Air18 CFM (30 M3/HR)
OtherCompression Ratio23.5:1
OtherCompression Ratio23:1
OtherCoolant Capacity2.2 quart (2.1 liter)
OtherCoolant Flow3.0 gpm (16 liter/min)50 Hz
OtherCoolant Flow3.5 gpm (13 liter/min)60 Hz
OtherEngine Oil Capacity2.2 quart (2.1 liter)
OtherFiring Order (Clockwise Rotation)1-2
OtherFuel Injection Order (Firing Order, clockwise rotation)1-2
OtherGenerator Cooling Air60-80 CFM (100-135 M3/HR)
OtherMaximum Fuel Pump Lift4 feet (1.2 m) with 3/8 inch ID fuel line
OtherMaximum Raw Water Pump Lift4 feet (1.2 m) with 5/8 inch ID hose
OtherMinimum CCA Rating360amps
OtherPublished Standard Repair Time (example: productive 3.48 hr + 5% personal + 10% supplementary)4.0hoursexample calculation in foreword
OtherRaw Water Flow4.0 gpm (15 liter/min)50 Hz
OtherRaw Water Flow5.0 gpm (19 liter/min)60 Hz
PressureCooling System Pressure10psi
PressureCooling system pressure (pressure cap)10psi
PressureFuel Injection Pressure1991 psi (13.73 MPa)
PressureFuel injection pressure1991psi (13.73 MPa)
PressureMaximum Exhaust Back Pressure3inch Hg (76 mm Hg)
PressureMaximum Exhaust Back Pressure3 INCH (76 MM) HG
PressureMinimum engine oil pressure (shutdown/service threshold)14psi (98 kPa)
ResistanceBattery charging winding B1-B20.114ohms@ 77 F (25 C) +/-10%
ResistanceCoolant temperature sender E2approximately 800ohmsroom temperature
ResistanceField winding F1-F232ohms@ 77 F (25 C) +/-10%
ResistanceGovernor actuator stator1.7-2.8ohms
ResistanceOil pressure sender E1227-257ohms0 psi, engine stopped
ResistanceQuadrature winding Q1-Q22.93ohms@ 77 F (25 C) +/-10%
ResistanceRotor/stator winding insulation to groundminimum 1megohm
ResistanceStator main winding T1-T2, T3-T40.353ohms@ 77 F (25 C) +/-10%
SpeedEngine/Generator Speed2400/3000rpm50 Hz
SpeedEngine/Generator Speed2900/3600rpm60 Hz
SpeedEngine/generator speed (50 Hz)2400/3000rpm50 Hz
SpeedEngine/generator speed (60 Hz)2900/3600rpm60 Hz
SpeedHigh-idle speed3300-3400rpm
SpeedMaximum cranking duration20-60secondsengine temperature dependent
SpeedPreheat duration prior to crankingmax 15secondsengine temperature dependent
SpeedRated RPM (50 Hz)2400rpm
SpeedRated RPM (60 Hz)2900rpm
SpeedStarter disconnect speed800rpm
TemperatureEngine room temperature (best performance)40°C (104 °F)maximum recommended
TemperatureGenerator set air inlet temperature50°C (122 °F)should not exceed under full load
TorqueDrive coupling nuts8lb-ft (12 N-m)
TorqueEngine-generator adapter mounting bolts (6)21lb-ft (29 N-m)
TorqueExhaust manifold nuts (4) and mixer bolts (3)8lb-ft (11 N-m)
TorqueFan hub bolt45lb-ft (61 N-m)
TorqueFlywheel mounting bolts (5)42lb-ft (56 N-m)
TorqueFront engine support bracket bolts (3)41lb-ft (55 N-m)
TorqueGenerator end bell support bracket bolts8lb-ft (11 N-m)

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
CoolantFleetguard ES Compleat and EG Premix (ethylene glycol based)
Coolant50/50 mixture of water and ethylene glycolabove -37°C2.1 literUse best quality ethylene glycol antifreeze with rust inhibitors and coolant stabilizers; distilled water best. Protection down to -34°F (-37°C).
CoolantEthylene glycol antifreeze, fully formulated with rust inhibitors and coolant stabilizers; 50/50 mixture of water and ethylene glycolabove -37°C2.1 literProtection from freezing down to -34°F (-37°C); use fresh water low in minerals, distilled best
Engine oilAPI Service Category CI-4 or better; SAE 15W-40 recommendedAPI CI-42.1 liter2.2 quart (2.1 liter). Multigrade oils such as SAE 15W-40 are recommended for year-round use.
Engine oilPremium Blue E 15W402.1 L (2.2 qt)Lubricant oil - Premium Blue E 15W40
Engine oilSAE 15W-40 (multigrade) recommended for year-round useAPI Service Category CI-4 or better2.1 literChoose viscosity grade appropriate for ambient temperatures expected until next scheduled oil change
Engine oilSAE 15W-40 multi-grade recommended for year-round useAPI Service Category CI-4 or better2.1 literChoose viscosity grade appropriate for ambient temperatures expected until the next scheduled oil change (Figure 3-1)
FuelGas Oil (red diesel, fuel oil, type A1 or A2)USCG TYPE A1 or ISO 7840-A1 fuel hoses
FuelGrade 2-D diesel fuel (Grade 1-D if tank exposed below 40 F (5 C))EN 590 or ASTM D975; Cetane number not less than 45; sulfur content not more than 0.5 percent by weightFuel lubricity: minimum load level 3100 grams per ASTM D6078 or maximum scar diameter 0.45 mm per ASTM D6079 or ISO 12156-1
FuelGrade 2-D diesel fuel; Grade 1-D if fuel tank exposed to temperatures below 40°F (5°C)EN 590 or ASTM D975Cetane number not less than 45; sulfur content not more than 0.5 percent by weight. Cloud point at least 10°F (6°C) below lowest expected fuel temperature. Fuel lubricity: minimum load level 3100 grams per ASTM D6078 or max scar diameter 0.45 mm per ASTM D6079 or ISO 12156-1.
FuelHigh quality Grade 2-D diesel fuel; use Grade 1-D if fuel tank exposed to temperatures below 40°F (5°C)EN 590 or ASTM D975Cetane number not less than 45; sulfur content not more than 0.5 percent by weight; fuel lubricity min 3100 grams per ASTM D6078 or max scar diameter 0.45 mm per ASTM D6079/ISO 12156-1

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Fault codes

33
CodeNameMeaningSeverityAction
1High Engine TemperatureEngine coolant temperature exceeded design limitShutdownOpen sea valve; clean sea water strainer; check coolant level and repair leaks; check/replace raw water hoses; readjust a loose pump belt (p. 4-9); replace worn raw water impeller (p. 4-10); clean heat exchanger (p. 4-12); check through-hull; drain/clean cooling system (p. 4-6); replace coolant thermostat (p. 4-8); tighten coolant sender E2 ring terminal; test/replace sender E2; check continuity Pin 9 to E2
2Low Oil PressureLow oil pressureShutdownCheck oil level; tighten sender E1 ring terminal; check sender E1 resistance and replace if necessary; check continuity Pin 10 to E1; replace sender with a gauge and service the engine lubrication system if oil pressure is less than 14 psi (98 kPa)
3Service CheckA fault with a 2-Digit Fault Code Number occurredShutdownPush and Release Stop to check the 2-Digit fault code (does not apply to e-Series Digital Display)
4OvercrankCranking time exceeded 20 to 60 seconds, depending on ambient temperatureShutdownPush line circuit breaker OFF; check fuel tank and fill; remove combustion air or exhaust blockages; open closed fuel valves; prime the fuel system at least 30 seconds; service the battery; check all fuel filters and fittings and reprime; replace fuel filters; change to proper oil viscosity; conduct fuel pump test; inspect glow plugs; service fuel injectors and worn engine
5Shutdown Due to Vessel CODangerous levels of Carbon Monoxide in VesselShutdownGet everyone out into fresh air immediately and seek medical attention
7Loss of Raw Water FlowInsufficient raw water flow through the heat exchanger to cool the engineShutdownOpen sea valve; clean sea water strainer; check/replace raw water hoses; readjust a loose pump belt; replace worn raw water impeller; check through-hull; check continuity Pin 8 to B- and raw water flow switch S6
12High AC VoltageAfter voltage regulation was enabled, output voltage jumped to more than 125% of rated for 75 milliseconds or more than 115% of rated for 3 secondsShutdownPush line circuit breaker OFF and start the genset; check all fuel filters and fittings for fuel and air leaks; check brushes and slip rings and rotor and stator windings; replace the genset controller
13Low AC VoltageAfter voltage regulation was enabled, output voltage fell to less than 90% of rated for 5 secondsShutdownReduce electrical loads; check fuel tank; remove air/exhaust blockages; prime fuel system; check fuel filters and fittings; replace fuel filters; check brushes/slip rings and windings; conduct fuel pump test; check governor actuator; readjust high idle speed; service injectors; check injection timing; check internal governor; service worn engine; replace controller
14High AC FrequencyAfter the starter was engaged, frequency jumped to more than 70 Hz for 40 milliseconds or to more than 2% over nominal for 6 secondsShutdownCheck for a tripped genset circuit breaker and run with fewer loads; check fuel filters and fittings for air leaks and reprime; check governor actuator operation; check internal governor mechanism; replace the genset controller
15Low AC FrequencyDuring normal operation, frequency fell to less than 90% of nominal for more than 8 secondsShutdownReduce loads with high motor starting loads; check fuel tank; remove air/exhaust blockages; prime fuel system; check fuel filters and reprime; replace fuel filters; conduct fuel pump test; check governor actuator; readjust high idle speed; service injectors; check injection timing; check internal governor; service worn engine; replace controller
17Overprime
22Governor OverloadMaximum allowable time at full-duty cycle was exceededShutdownReduce appliances running at the same time; check fuel tank; remove air/exhaust blockages; prime fuel system; check fuel filters and reprime; replace fuel filters; conduct fuel pump test; check governor actuator; readjust high idle speed; service injectors; check injection timing; check internal governor; service worn engine; replace controller
23Faulty Oil Pressure SenderController sensed grounded senderShutdownTighten the ring terminal on sender E1; check continuity between Pin 10 and ring terminal E1-1; test sender E1 and replace as necessary; replace the genset controller
24Faulty Temperature SenderController sensed open senderShutdownTighten the ring terminal on sender E2; check continuity between Pin 9 and ring terminal E2-1; test sender E2 and replace as necessary; replace the genset controller
27Loss of AC Voltage SenseController lost VAC sensing during normal voltage regulation when the field was functioning normally and frequency was at least 40 HzShutdownCheck continuity between Pin 11 (S1) and Pin 12 (S2); service or replace brush block, slip rings, rotor or stator; replace the genset controller
29High Battery VoltageDuring startup the controller sensed that battery system voltage was greater than 19.2 voltsShutdownCheck battery bank connections and reconnect for 12 volts; select a lower battery booster charge rate
32Starting FaultThe genset Controller could not detect cranking speed (quadrature zero crossings) for 3 secondsShutdownHave the propulsion engines running while trying to start the genset; service the battery; change to oil of proper viscosity for the ambient temperature.
35Control Card Failure-EEDuring startup the controller detected a EE memory errorShutdownReplace the genset controller
36Unknown ShutdownEngine speed fell below 1000 RPM for 0.5 seconds, though not by genset or engine control actionShutdownCheck for mechanical damage; reduce appliances running; check fuel level; remove air/exhaust blockages; prime fuel system; check fuel filters and reprime; replace fuel filters; conduct fuel pump test; check governor actuator; service brushes/slip rings and test rotor and quadrature windings; service injectors; check internal governor; service worn engine; replace controller
37Invalid Genset ConfigurationThe controller is not configured properly for the gensetShutdownMake sure CONFIG 1 and CONFIG 2 leads are not connected and are terminated with insulated connectors; reconfigure the genset controller (p. 2-7); replace the genset controller
38Field OverloadHigh field voltage induced by high rotor temperature or low power factor loadsShutdownRemove blockages to generator air flow; reduce appliances running; have air conditioners checked; check for a loose generator fan; service brushes and slip rings and test the field, stator and quadrature windings; replace a stator or rotor with faulty windings
41Generator Rotor FaultF+ groundedShutdownCheck for continuity between Pin P3-7 (F+) and B- (ground); repair or replace wiring, brushes and slip rings or rotor; replace the genset controller
42Control Card ROM
43Control Card Failure-RAMDuring startup the controller detected a RAM memory errorShutdownReplace the genset controller
45Speed Sense LostAfter start disconnect the controller lost speed sense (quadrature zero crossings) for 0.25 secondsShutdownCheck for open or shorted field (P3-6/P3-7) or quadrature (P3-4/P3-5) windings; service or replace brush block, slip rings, rotor or stator; replace the genset controller
46Genset OverloadThe genset Controller shutdown the genset because engine load exceeded 135 percent of genset rating for 10 secondsShutdownReduce the number of loads on the genset.
48Field Sense Lost-RAMController unable to sense field voltageShutdownReplace the genset controller
57OverprimeA local or remote control switch was held in the Prime position for more than 5 minutesShutdownRemove any object holding a control switch in the prime position; replace any control switch S4 that does not open across terminals 1 and 2 when Stop is released
58High Exhaust TemperatureExhaust temperature exceeded design limits due to lack of water delivered to the exhaust/water mixerShutdownOpen sea valve; clean sea water strainer; check/replace raw water hoses; inspect siphon break; readjust a loose pump belt; replace worn raw water impeller; clean heat exchanger; check continuity between Pin P1-11 and B- and exhaust temperature switch S5
59Low coolant levelProvides continuous monitoring of the coolant level in the engine block. If the level falls below a pre-set level for more than 10 seconds the genset control activates a shutdown and indicates fault code 59.ShutdownRepair any leak and add coolant as appropriate.
61External ShutdownGenset was shut down by a fire suppression system or other external controlShutdownMake all necessary repairs to the genset and connected equipment and reset the external control which shut down the genset
Code No. 5Warning - Shutdown due to Vessel COShutdown occurring due to the vessel CO detectorWarningAll status indicator lights in the control circuit will also blink the fault code. See Troubleshooting Chapter of the Operator Manual.
Code No. 61Emergency ShutdownShutdown occurring due to external emergency shutdown deviceShutdownAll status indicator lights in the control circuit will also blink the fault code. See Troubleshooting Chapter of the Operator Manual.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Adjusting High-Idle Speed adjustment

⚠ Keep your hands away from the engine belt and pulleys.

⚠ The actuator could overheat if the battery is left on more than 10 minutes.

⚠ Be prepared to clamp off supply and return fuel lines to stop the engine.

Tools: strobe or injector clamp-on tachometer, 12 volt battery, battery switch

  1. Adjust the speed control lever stop.
  2. Measure engine speed with a strobe or injector clamp-on type tachometer.
  3. Remove the front and top access doors and loosen the front/left side panel assembly for access to the speed adjusting screw.
  4. Disconnect the actuator leads and connect a 12 volt battery to the actuator terminals using a battery switch.
  5. Switch the battery on, start the genset, measure engine speed (rpm) and stop the engine by switching off the battery.
  6. Loosen the lock nuts on the two bottom screws and back out the clamping screw if speed is not between 3300 and 3400 rpm.
  7. To increase speed turn the speed adjusting screw in 1 turn clockwise; to decrease turn it out 1 turn counterclockwise.
  8. Repeat until high-idle speed is between 3300 and 3400 rpm and set the lock nut.
  9. Run the clamping screw in by hand until snug, back it out 1-1/2 turns and set the lock nut.
Adjusting Speed Control Lever Stop adjustment

⚠ Accidental or remote starting can cause severe personal injury; disconnect the negative battery cable.

  1. Remove the front and top access doors and loosen the front/left side panel assembly so it can swing left.
  2. Loosen the stop screw locknut and back the screw out a few turns.
  3. Turn the stop screw in until it just makes contact and set the locknut.
Adjusting V-Belt Tension adjustment

⚠ Disconnect the negative battery cable to prevent accidental starting.

Tools: open-end wrench, 3/8 inch drive socket

  1. Disconnect the negative battery cable to prevent the engine from starting.
  2. Remove the front and top access doors; remove the end panel if work space is limited.
  3. Loosen both bolts so that the pump can pivot.
  4. Pivot the pump out to tighten belt tension and hold by tightening the tension adjusting bolt.
  5. Check tension by applying 20 pounds (10 kg) to the middle of the pulley span; deflection should be 0.4 inch (10 mm).
  6. Tighten the bolts, reassemble the panels and doors and reconnect the battery cables (negative last).
Adjusting Valve Lash adjustment

⚠ Do not use the fuel injection timing marks when adjusting valve lash.

  1. Rotate the engine clockwise (looking from the front) until the intake valve push rod just stops moving down (valve closed).
  2. Turn the engine one half turn more.
  3. Adjust lash for both intake and exhaust valves of that cylinder.
  4. Repeat this procedure for the other cylinder.
Adjusting Voltage Using Control Switch adjustment

Tools: separate voltmeter

  1. Start the genset and let voltage and frequency stabilize for 5 to 10 seconds with all loads disconnected.
  2. Rapidly press START 6 times during the first minute after startup to enter voltage adjust mode.
  3. To adjust voltage up, press and quickly release START (about 0.6 volts per press).
  4. To adjust voltage down, press and hold START for about 2 seconds (about 0.6 volts each press).
  5. Wait about 20 seconds for the amber lamp to stop blinking, then press STOP to save the adjustment.
  6. Restart the genset and check voltage.
Adjusting Voltage Using Digital Display adjustment
  1. Start generator set and let voltage and frequency stabilize 5 to 10 seconds; disconnect all loads.
  2. Rapidly press START 6 times during the first minute after startup to enter voltage adjust mode.
  3. Press and quickly release START to increase voltage approximately 0.6 volts per press.
  4. Press and hold START about 1 second to adjust voltage down.
  5. Wait about 20 seconds for status to change from Volt Adj to Running, then press STOP to save.
  6. Restart the generator set and check voltage; recalibrate AC voltage on the digital display.
Adjusting Voltage Using Optional Digital Display adjustment

Tools: Separate voltmeter

  1. Start the genset and let voltage and frequency stabilize for 5 to 10 seconds; make sure all loads have been disconnected.
  2. Rapidly press START 6 times during the first minute after startup to put the genset controller into voltage adjust mode.
  3. To adjust voltage up, press and quickly release START; voltage increases approximately 0.6 volts each press and release.
  4. To adjust voltage down, press and hold START for about 1 second; voltage decreases approximately 0.6 volts each press and release.
  5. Wait about 20 seconds for the Display to indicate a Status change from Volt Adj to Running, then press STOP to stop the genset and save the adjustment.
  6. Restart the genset and check voltage.
  7. Recalibrate AC Voltage on the Digital Display as instructed in the Operator's Manual.
Changing Frequency adjustment
  1. Connect J5 to P6 for 60 HZ.
  2. Disconnect J5 from P7 for 50 HZ.
  3. Apply the appropriate reconfiguration label.
Changing Generator Set Frequency adjustment

⚠ When changing frequency, make sure the line circuit breakers are suitable for the new output.

  1. Remove the control box cover.
  2. Connect J5 to P6 for 60 Hz.
  3. Disconnect J5 from P7 for 50 Hz.
  4. Apply the appropriate reconfiguration label.
  5. Replace the control box cover.
  6. Check and adjust voltage as necessary after the frequency has been changed.
Configuring the Controller Using Control Switch adjustment

⚠ In configuration mode the control will not start, prime or display faults.

  1. Remove the insulating connectors from harness connectors CONFIG 1 and CONFIG 2 and connect them together.
  2. Press START to increase the code number or STOP to decrease it one unit each press.
  3. Set the configuration code number to 19 for this genset.
  4. Verify the status lamp blinks one blink, pause, then nine blinks.
  5. Disconnect CONFIG 1 from CONFIG 2 and re-install the insulating connectors.
Disabling Battery Charger adjustment
  1. Disconnect the leads marked B1, B2 and B+ from the quick-connect terminals on battery charging voltage regulator.
  2. Insulate the end of each lead with several wraps of listed electrical insulating tape and tie them neatly into the wiring harness.
  3. Secure the access cover when done.
Valves - Adjust adjustment
  1. Disconnect and connect battery cables, engine wiring harness, fuel lines, exhaust hose, coolant hoses
  2. Drain and refill engine fluids
  3. Remove and install soundshield, glowplugs, valve cover
  4. Adjust valve lash
  5. Test run unit

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
50 Hz: Disconnect J5 from P7J5, P6, P7Frequency selection jumper leads in the genset control box
60 Hz: Connect J5 to P6J5, P6, P7Frequency selection jumper leads in the genset control box
220/208312 Lead ReconnectableApplies to MDKDP (60 Hz), MDKDR (60 Hz), MDKDS
220/380312 Lead ReconnectableApplies to MDKDP, MDKDR, MDKDT, MDKDU
3-phase312 Lead ReconnectableApplies to MDDCW, MDDCU, MDDCY, MDDCS, MDDCT

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

Which oil filter part number does the Cummins/Onan MDKBH take?

The Cummins/Onan MDKBH uses oil filter part number 185-7444.

Which fuel filter part number does the Cummins/Onan MDKBH take?

The Cummins/Onan MDKBH uses fuel filter part number 149-2106.

Troubleshooting

29

Fault codes

CodeMeaningRemedy
1High engine temperature — Engine coolant temperature exceed design limitOpen the sea valve; Check for and clean a blocked sea water strainer. If above the water line, fill the strainer with water to assist priming; Check engine coolant level, add coolant as necessary and check for and repair leaks (p. 4-7); Check for and reconnect or replace any disconnected, kinked or leaking raw water hoses; Check the bottom of the hull for any blockage at the through-hull fitting; Drain and clean the cooling system to remove fouling (p. 4-7); Replace the coolant thermostat, which might not be opening fully (p. 4-10)
2Low oil pressure — Low oil pressureCheck engine oil level, add or drain oil as necessary and repair any leaks (p. 4-4)
3Service check — A fault with a 2-Digit Fault Code Number occurredCheck the 2-Digit fault code by Pushing and Releasing Stop. The 2-Digit fault will be one of the following in this table. (Does not apply to e-Series Digital Display.)
4Overcrank — Cranking time exceeded 20 to 60 seconds, depending on ambient temperaturePush the generator set line circuit breaker OFF; Check the fuel tank and fill as necessary. (Note: The arrangement of pickup tubes in the fuel supply tank probably is such that the generator set will run out of fuel before the propulsion engines.); Remove combustion air or exhaust system blockages; Open any closed fuel supply and return valves; Prime the engine fuel system for at least 30 seconds (p. 3-3); Service the battery as necessary by cleaning and tightening connections, recharging or replacing the battery or replacing damaged battery cables (p. 4-3); Check all fuel filters and fittings for fuel and air leaks, tighten as necessary and reprime; Replace the fuel filters and reprime (p. 4-6); Change the engine oil to oil of the proper viscosity for the ambient temperature. High oil viscosity can slow down cranking speed
7Loss of raw water flow — Insufficient raw water flow through the heat exchanger to cool the engineOpen the sea valve; Check for and clean a blocked sea water strainer. If above the water line, fill the strainer with water to assist priming; Check for and reconnect or replace any disconnected, kinked or leaking raw water hoses; Check the bottom of the hull for any blockage at the through-hull fitting
12High AC voltage — After voltage regulation was enabled Output Voltage jumped to more than 125percent of rated for 75 milliseconds or to more than 115percent of rated for 3 secondsPush the generator set line circuit breaker OFF, start the generator set. If output voltage is normal, the problem is in the circuits external to the generator set; Check all fuel filters and fittings for fuel and air leaks, tighten as necessary and reprime. (Air bubbles can disrupt frequency.)
13Low AC voltage — After voltage regulation was enabled Output Voltage fell to less than 90percent of rated for 5 secondsPush the generator set line circuit breaker OFF. If the generator set now runs and voltage and frequency are normal, reduce the number of electrical loads; Check the fuel tank and fill as necessary. (Note: The arrangement of pickup tubes in the fuel supply tank probably is such that the generator set will run out of fuel before the propulsion engines.); Remove combustion air or exhaust system blockages; Prime the engine fuel system for at least 30 seconds (p. 3-3); Check all fuel filters and fittings for fuel and air leaks, tighten as necessary and reprime. (Air bubbles can disrupt frequency.); Replace the fuel filters and reprime (p. 4-6)
14High AC frequency — After the starter was engaged Frequency jumped to more than 70 Hz for 40 milliseconds or to more than 2percent over nominal for 6 secondsCheck for a tripped generator set circuit breaker, reset it if necessary, and run with fewer connected loads. (A breaker tripping under load can cause generator set frequency to overshoot.); Check all fuel filters and fittings for fuel and air leaks, tighten as necessary and reprime. (Air bubbles can disrupt frequency.)
15Low AC frequency — During normal operation Frequency fell to less than 90percent of nominal for more than 8 secondsPush the generator set line circuit breaker OFF. If the generator set now runs, reduce the number of loads, especially those with high motor starting loads such as air conditioners; Check the fuel tank and fill as necessary. (Note: The arrangement of pickup tubes in the fuel supply tank probably is such that the generator set will run out of fuel before the propulsion engines.); Remove combustion air or exhaust system blockages; Prime the engine fuel system for at least 30 seconds (p. 3-3); Check all fuel filters and fittings for fuel and air leaks, tighten as necessary and reprime. (Air bubbles can disrupt frequency.); Replace the fuel filters and reprime (p. 4-6)
22Governor overload — Maximum allowable time at full-duty cycle was exceededReduce the number of appliances running at the same time, especially those with high motor starting loads such as air conditioners; Check the fuel tank and fill as necessary. (Note: The arrangement of pickup tubes in the fuel supply tank probably is such that the generator set will run out of fuel before the propulsion engines.); Remove combustion air or exhaust system blockages; Prime the engine fuel system for at least 30 seconds (p. 3-3); Check all fuel filters and fittings for fuel and air leaks, tighten as necessary and reprime; Replace the fuel filters and reprime (p. 4-6)
23Faulty oil pressure sender — Controller sensed grounded senderSee an authorized Onan service representative
24Faulty temperature sender — Controller sensed open senderSee an authorized Onan service representative
27Loss of AC voltage sense — The generator set Controller lost VAC sensing during normal voltage regulation when the field was functioning normally and frequency was at least 40 HzSee an authorized Onan service representative
29High battery voltage — During startup the generator set Controller sensed that battery system voltage was greater than 19.2 voltsCheck battery bank connections and reconnect if necessary for 12 volts; Select a lower battery booster charge rate
35Control card failure−EE — During startup the generator set Controller detected a EE memory errorSee an authorized Onan service representative
36Unknown shutdown — The generator set Controller declared this fault because engine speed fell below 1000 RPM for 0.5 seconds, though not by generator set or engine control actionCheck for mechanical damage and service as necessary; Reduce the number of appliances running at the same time, especially those with high motor starting loads such as air conditioners; Check fuel level and refill as necessary. (Note: The generator set fuel pickups are probably higher than the propulsion engine fuel pickups.); Remove combustion air or exhaust system blockages; Prime the engine fuel system for at least 30 seconds (p. 3-3); Check all fuel filters and fittings for fuel and air leaks, tighten as necessary and reprime; Replace the fuel filters and reprime (p. 4-6)
37Invalid genset configuration — The generator set Controller is not configured properly for the generator setSee an authorized Onan service representative
38Field overload — High field voltage induced by high rotor temperature or low power factor loadsRemove blockages to generator air flow at the front inlet grill and right side, if enclosed; Reduce the number of appliances running at the same time, especially those with high motor starting loads such as air conditioners; Have air conditioners and other appliances checked for proper operation. (A locked compressor rotor can cause very low power factor.)
41Generator rotor fault — F+ groundedSee an authorized Onan service representative
43Control card failure−RAM — During startup the generator set Controller detected a RAM memory errorSee an authorized Onan service representative
45Speed sense lost — After start disconnect the generator set Controller lost speed sense [quadrature zero crossings] for 0.25 secondsSee an authorized Onan service representative
48Field sense lost−RAM — Controller unable to sense field voltageSee an authorized Onan service representative
57Overprime — A local or remote control switch was held in the Prime position for more than 5 minutesCheck for and remove any object that may be holding either control switch (remote or local) in the prime position
58High exhaust temperature — Exhaust temperature exceeded design limits due to lack of water delivered to the exhaust/water mixerOpen the sea valve; Check for and clean a blocked sea water strainer. If above the water line, fill the strainer with water to assist priming; Check for and reconnect or replace any disconnected, kinked or leaking raw water hoses; Inspect the siphon break (if provided) for proper operation
61External shutdown — The generator set was shut down by a fire suppression system or other external controlMake all necessary repairs to the generator set and connected equipment and reset the external control which shut down the generator set

Symptoms & remedies

SymptomCauseRemedy
No response at operator panel or control switchFaulty switch, poor or missing connections, dead batteryPush the Emergency Stop Breaker ON if tripped; Try the Operator Panel or control switch on the generator set (local) if there is no response at a remote Operator Panel or control switch, and vice versa; If none of the Operator Panels or control switches works, service as necessary by cleaning and tightening battery connections, recharging or replacing the battery or replacing damaged battery cables (p. 4-3)
The starter engages and disengagesLow cranking voltagePush the generator set line circuit breaker OFF; Service the battery as necessary by cleaning and tightening connections, recharging or replacing the battery or replacing damaged battery cables (p. 4-3)
The starting batteries do not maintain a chargeMarginal battery, battery connections or charging systemService the battery as necessary by cleaning and tightening connections, recharging or replacing the battery or replacing damaged battery cables (p. 4-3); Check for and disconnect parasitic battery loads
No AC power when generator set is runningA Circuit Breaker is OFF, tripped or malfunctioning or the generator is not connected properlyReset or turn ON the generator set circuit breaker if OFF or tripped; Reset or turn ON any other circuit breaker in the AC power supply system if OFF or tripped

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.

Parts

20
Part #DescriptionQtySystem
0541-0876-02Siphon break assembly, eight hose clamps, two rubber grommets, two pre-formed rubber hoses, two 3/4 in hose unions and instruction sheetSiphon break Amazon eBay $229.91
149-2106Element1Fuel filter Amazon eBay $34.99 NAPA $61.61 KuduParts $68.00
185-5421Plug, Glow2Glow plug Amazon eBay $35.00
185-7444Filter, Oil1Oil filter Amazon eBay $29.95 NAPA $9.09 KuduParts $11.00 FridayParts $13.23
511-0197V-Belt1Belt Amazon eBay
541-1524Pump ImpellerImpeller eBay $122.63
1000-1500Electric Frying Pan or Wok1200Service part / kit Amazon eBay
1400-2000Air ConditionerService part / kit Amazon eBay
200-500Electric BlanketService part / kit Amazon eBay
200-600Radio1Service part / kit Amazon eBay
250-750Electric BroomService part / kit Amazon eBay
300-700RefrigeratorService part / kit Amazon eBay
350-1000Electric Stove Element Power Consumption (watts)Service part / kit Amazon eBay
50-200Electric Blanket Power Consumption (watts)1Service part / kit Amazon eBay
500-1200Electric Hair DryerService part / kit Amazon eBay
524-0118Molybdenum disulfide pasteService part / kit eBay
550-750Coffee Percolator Power Consumption (watts)Service part / kit Amazon eBay
600-1000Refrigerator1Service part / kit Amazon eBay
800-1500Coffee PercolatorService part / kit Amazon eBay
981-0176Redistribution or publication of this document, by any means, is strictly prohibited. CaliforniaService part / kit Amazon eBay

Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.

Available documents

Operator's manual — 981-0176 ONAN MDKBH Marine Genset Operator's manual (06-2005) (Cummins/Onan)Operator's manual — Manual Operador Marino QD 6kWz (Cummins/Onan)Reference — 0059599 (Cummins/Onan)Parts manual — 0043090 (Cummins/Onan)Parts manual — F-1379-EN (Cummins/Onan)Service manual — 900-0620B Onan MDKAU MDKBH Repair Times (Onan Corporation (Cummins Power Generation))Service manual — 981-0542 Onan MDKBH Service Manual (11-2005) (Cummins/Onan)Service manual — 981-0643 Onan MDKBH Installation Manual (6-2005) (Cummins/Onan)Service manual — 981-0647 Onan MDKBH Spec A-E Installation Manual (10-2013) (Cummins/Onan)

This page was generated from the 9 manufacturer documents above by automated extraction; every figure shown is copied from one of them. How the data is compiled.

Full service, cheapest listings

Priced items from this model's own parts manual.

Fuel filter 149-2106$34.99
Oil filter 185-7444$9.09
2 priced items$44.08