Cummins/Onan — Changing Frequency and Reconnecting the Generator
Installation
From a Cummins/Onan service manual — check it applies to your exact model before use.
Applies to: Cummins/Onan MDKB, Cummins/Onan MDKBH
Before you start
- Disconnect the negative battery cable before removing a panel or access door.
Procedure
- Connect J5 to P6 for 60 Hz.
- Disconnect J5 from P7 for 50 Hz.
- Apply the appropriate reconfiguration label over the As Manufactured block on the nameplate.
- Reconnect the generator for the application voltage per the generator connection schematic.
- Note it may be necessary to change circuit breakers to provide required protection or full genset power.
- Adjust voltage if necessary.
Specs & values
- Configuration code number for this genset is 19
Full service-parts list: Cummins/Onan MDKB →, Cummins/Onan MDKBH →
Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.