Manufacturer-documented fuel consumption for 7 260–265 kW Diesel generator sets — median 16.59 gal/h at full load, 8.94 gal/h at half load.
Compare 260–265 kW Diesel generator specs side-by-side →
| Model | kW | gal/h @ 50% | gal/h @ 100% | Tank (L) | Runtime @ 50% (h) |
|---|---|---|---|---|---|
| MQ Power MQP240 | 260 | 11.07 | 19.02 | — | — |
| FG Wilson P330-5 | 264 | 8.80 | 16.59 | 694 | 20.8 |
| FG Wilson SL330E3 | 264 | — | 16.11 | 800 | — |
| FG Wilson SW330E1 | 264 | — | 16.35 | 263 | — |
| MQ Power DCA300SSJU4F | 264 | 9.09 | 17.25 | 380 | 11.0 |
| Olympian GEH330-1 | 264 | 8.80 | 15.72 | 617 | 18.5 |
| SDMO R330K | 264 | — | 19.65 | 97 | — |
Figures from each model’s own manufacturer documentation (spec sheets and manuals); runtime = documented tank capacity ÷ consumption at 50% load. Verify against the datasheet for your exact configuration.
Across 7 models with manufacturer data, full-load consumption runs 15.72–19.65 gal/h (median 16.59); at 50% load the median is 8.94 gal/h.
At 50% load, documented tank sizes give 11.0–20.8 hours (median 18.5 h) across 3 models.