Cummins/Onan KTA38 Engine

The Cummins/Onan KTA38 is a 38 L 12-cylinder turbocharged and after cooled engine. It powers generator sets from AKSA and Cummins/Onan, including the AC1026-38, 625.0 DFZ, 650.0 DFZ and 750.0 DFZ. It holds 129 L (34.1 gal) of oil and 308 L (81.4 gal) of coolant.

Also known as: Cummins KTA38

Part of the Cummins/Onan KTA38 engine family — 13 variants share parts & fitment.

38.0 L
Displacement
12
Cylinders
129.0 L
Oil capacity

Engine specifications

Oil capacity129.0 L
Coolant capacity308.0 L
Displacement38.0 L
Cylinders12
Aspirationturbocharged and after cooled

Maintenance schedule

ItemSpecCapacityPart #Interval
Air filterDry replaceable element2500 hr
Fuel filterDual spin on paper element fuel filters with standard water separator1800 hr
Oil filterCummins OEF148-90002500 hr Amazon eBay
Battery890 amps at ambient temperature 32 °F (0 °C)1800 hr
BeltStandard2500 hr
CoolantAntifreeze 50/50 (Ethylene glycol)3600 hr
Oil10W-405.2 L3600 hr
Spark plugStandard2500 hr

Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.

Service specifications

60
TypeItemValueUnitCondition
ClearanceFloat switch assembly float lift clearance below C-clip stop1/8inch (3 mm)use a feeler gauge
ClearanceGenerator-to-engine angular alignment (T.I.R.).001 in. per inch of radius (center of shaft to indicator axis), maximumin750 kW gensets and larger
OtherAVR Droop setting5% at full load, 0 PF
OtherAVR voltage regulation (load regulation)approximately ±0.5% RMS
OtherBattery specific gravity (high ambient, above 95F/35C)1.225recommended to reduce electrolyte loss
OtherBattery specific gravity (recharge threshold)below 1.260
OtherGOV GAIN default value for paralleling applications70%
OtherOver/Under Frequency Sensor Module - Over Hz Set, 50 Hz nominal55Hzreset 53 Hz
OtherOver/Under Frequency Sensor Module - Over Hz Set, 60 Hz nominal65Hzreset 63 Hz
OtherOver/Under Frequency Sensor Module - Under Hz Set, 50 Hz nominal45Hzreset 47 Hz
OtherOver/Under Frequency Sensor Module - Under Hz Set, 60 Hz nominal55Hzreset 57 Hz
OtherOver/Under Voltage Sensor Module time delaytypically 25 percent, approximately 2.5seconds
OtherOvercrank cranking limit75secondsthree 15-second cranking cycles with two 15-second rest periods
OtherREG VHZ (underfrequency roll-off) adjustable range1 through 50; normal range 7 through 21
OtherStart delay adjustment range0 to 300seconds
OtherStop delay adjustment range0 to 600seconds
OtherUnder Frequency Roll Off (UFRO) knee point, 50 Hz units48 to 49Hz
OtherUnder Frequency Roll Off (UFRO) knee point, 60 Hz units58 to 59Hz
PressureEngine oil pressure - K19 normal50-70psi (345-482 kPa)run mode
PressureEngine oil pressure - K38 normal45-65psi (310-448 kPa)run mode
PressureEngine oil pressure - K50 normal50-70psi (345-482 kPa)run mode
PressureEngine oil pressure - L10/M11 normal30-50psi (207-345 kPa)run mode
PressureEngine oil pressure - NTA 855 normal35-50psi (241-345 kPa)run mode
PressureEngine oil pressure - V28 normal50-90psi (345-620 kPa)run mode
PressureEngine oil pressure shutdown limit - L10/M1120psi (138 kPa)run mode value
PressureEngine oil pressure shutdown limit - L10/M118psi (55 kPa)idle mode value
PressureEngine oil pressure warning limit - L10/M1112psi (83 kPa)idle mode value
PressureEngine oil pressure warning limit - L10/M1125psi (172 kPa)run mode value
PressureK19 engine idle oil pressure20psi (138 kPa)idle
PressureK19 engine normal oil pressure50-70psi (345-482 kPa)normal run
PressureK19 oil pressure shutdown/warning limitsshutdown 35 psi (241 kPa) run; warning 40 psi (276 kPa) run; shutdown 10 psi (69 kPa) idle; warning 15 psi (103 kPa) idlepsi (kPa)
PressureK38 engine idle oil pressure20psi (138 kPa)idle
PressureK38 engine normal oil pressure45-65psi (310-448 kPa)normal run
PressureK38 oil pressure shutdown/warning limitsshutdown 35 psi (241 kPa) run; warning 40 psi (276 kPa) run; shutdown 10 psi (69 kPa) idle; warning 15 psi (103 kPa) idlepsi (kPa)
PressureK50 engine idle oil pressure20psi (138 kPa)idle
PressureK50 engine normal oil pressure50-70psi (345-482 kPa)normal run
PressureK50 oil pressure shutdown/warning limitsshutdown 35 psi (241 kPa) run; warning 40 psi (276 kPa) run; shutdown 10 psi (69 kPa) idle; warning 15 psi (103 kPa) idlepsi (kPa)
PressureL10/M11 engine idle oil pressure15psi (103 kPa)idle
PressureL10/M11 engine normal oil pressure30-50psi (207-345 kPa)normal run
PressureL10/M11 oil pressure shutdown limit20psi (138 kPa)run mode value
PressureL10/M11 oil pressure shutdown limit8psi (55 kPa)idle mode value
PressureL10/M11 oil pressure warning limit12psi (83 kPa)idle mode value
PressureL10/M11 oil pressure warning limit25psi (172 kPa)run mode value
PressureLow oil pressure shutdownbelow 14psi (97 kPa)time delayed ~10 seconds following starter disconnect
PressureNTA 855 engine normal oil pressure35-50psi (241-345 kPa)normal run
PressureNTA 855 oil pressure shutdown limit25psi (172 kPa)run mode value
PressureNTA 855 oil pressure shutdown limit8psi (55 kPa)idle mode value
PressureNTA 855 oil pressure warning limit12psi (83 kPa)idle mode value
PressureNTA 855 oil pressure warning limit30psi (207 kPa)run mode value
PressurePre-low oil pressure warning20 or lesspsi (138 kPa)
PressureV28 engine idle oil pressure20psi (138 kPa)idle
PressureV28 engine normal oil pressure50-90psi (345-620 kPa)normal run
PressureV28 oil pressure shutdown/warning limitsshutdown 35 psi (241 kPa) run; warning 40 psi (276 kPa) run; shutdown 10 psi (69 kPa) idle; warning 15 psi (103 kPa) idlepsi (kPa)
ResistanceCircuit breaker insulation resistance (ground indication)less than 100,000ohmstested with 500V insulation resistance meter
ResistanceCoolant temperature sender resistance500 to 2kohms
ResistanceCurrent transformer (PT) primary1K-2.5Kohms
ResistanceCurrent transformer (PT) secondary140-225ohms
ResistanceExciter rotor winding resistance (per pair)approximately 0.136ohms
ResistanceExciter stator winding - frame size 4C/4D/4E/4F0.136ohmsat 68°F (20°C) + 10%
ResistancePMG stator resistance (HC4)4.6ohms

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
Coolantsoft water / E.G. / DCA mixtureCooling system to be filled with soft water/E.G./DCA mixture (on-site review checklist).
FuelDieselDay tank fuel transfer pump maintains reservoir of diesel fuel in the day tank.
GreaseLithium based grease, Mobilux No. 2 or Shell Alvania R3-30°C to 120°C2.74 oz (81 ml)End bearing lubricant; grease equally divided between bearing, bearing cap cavity and bearing cartridge cavity.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Fault codes

52
CodeNameMeaningSeverityAction
101IDLE MODEIndicates that the engine is operating in idle mode. Grounding the engine idle input causes generator build-up to be inhibited and the engine to be governed at 800 RPM.WarningRemove ground from engine idle input to return to normal speed and voltage.
102EMERGENCY STOPIndicates local or remote Emergency Stop.ShutdownTurn the switch clockwise and allow it to pop out (local only). Move the Run/Off/Auto switch to Off. Press the Reset switch. Select Run or Auto, as required.
200LOW OIL PRESSUREIndicates engine oil pressure has dropped to an unacceptable level.WarningIf generator is powering critical loads and cannot be shut down, wait until next shutdown period and then follow 201-SHUTDOWN procedure. Access the Oil Pressure menu prior to clearing the fault.
201LOW OIL PRESSUREIndicates engine oil pressure has dropped below the shutdown trip point.ShutdownCheck oil level, lines and filters; replenish if low; reset control and restart.
204OIL PRES SENDERIndicates that the control has sensed that the engine oil pressure sender is out of its working range.WarningCheck that the engine oil pressure sender is properly connected.
210LOW COOLANT TEMPWarning occurs when engine coolant temperature is 70°F (21°C) or lower.WarningIndicates engine coolant heater is not operating or is not circulating coolant. Check coolant heater power supply, low coolant level, and heater element current draw.
211HIGH COOLANT TEMPIndicates the engine coolant temperature is getting close to the recommended maximum temperature limit: 215° F (102° C) − standby or 207° F (97° C) − primary.WarningReduce load if possible; check air inlets and outlets and remove obstructions to airflow.
212HIGH COOLANT TEMPIndicates engine has overheated (coolant temperature above 215° F (102° C) − standby or 207° F (97° C) − primary).ShutdownAllow engine to cool; check airflow, fan belt, coolant mixture, blower fan and circulation pumps.
213COOLANT SENDERResistance of the coolant temperature sender is out of range.WarningCheck the resistance of the sender; should be 500 to 2k ohms.
214LOW COOLANT LVLIndicates engine coolant level has fallen below the trip point.WarningCheck coolant level in radiator and coolant recovery bottle; replenish if low; look for leaks.
215LOW COOLANT LVLIndicates engine coolant level has fallen below the trip point.ShutdownAllow engine to cool; check coolant level and leakage points; reset control and restart.
220MAG PICKUPMag pickup speed indication is not being sensed or does not match generator set output frequency.ShutdownRestart and check RPM; check PCC model setting; inspect and test MPU.
221FAIL TO CRANKPossible fault with control or starting system.ShutdownCheck fuse F3 on the Engine Interface board. Check for poor battery cable connections; clean battery cable terminals and tighten. Recharge or replace a discharged or defective battery.
222OVERCRANKPossible fuel system problem.ShutdownCheck for empty fuel tank, leaks, plugged fuel lines; replace dirty fuel or air filter; reset and restart.
223OVERSPEEDIndicates engine has exceeded normal operating speed. (115% ±1% of nominal).ShutdownCheck mechanical fuel linkage and actuator; check governor output module (A38) and digital board (A32).
224FAIL TO SYNCHRONIZEGenerator set has not synchronized to the system bus within the allowable time frame.WarningCheck governor system stability; adjust governing and synchronizer parameters; check fuel system.
226FAIL TO CLOSEParalleling breaker has been given a signal to close, but has not closed properly.ShutdownVerify breaker charging mechanism; check close signal; verify auxiliary contact signals.
230LOW DC VOLTAGEIndicates battery voltage is below 10 VDC.WarningRecharge or replace the battery; check the battery charger fuse. Clean and tighten battery cable connections. Check engine DC alternator; replace if normal charging voltage is not obtained. Check float level if applicable.
231HIGH DC VOLTAGEIndicates battery voltage exceeds 32 VDC.WarningLower battery charger float level if applicable; check engine DC alternator.
232WEAK BATTERYIndicates battery voltage drops below 60% of nominal for two seconds, during starting.WarningSee LOW DC VOLTAGE 230.
240LOW FUEL−DAYIndicates day tank fuel supply is running low.WarningCheck fuel supply and replenish as required.
241LOW FUELLow fuel signal received.WarningCheck fuel supply and replenish; check for short to ground in external wiring.
250EEPROM ERRORPCC memory error; data corruption of critical operating parameters.ShutdownPerform initial start setup procedure; replace digital board (A32) if fault repeats.
251EEPROM ERRORPCC memory error; data corruption of noncritical operating parameters.WarningPerform adjustment and calibration procedures; replace digital board (A32) if fault repeats.
252EEPROM ERRORPCC memory error; data corruption of noncritical operating parameters.WarningVerify selected values; repeat save operation; replace digital board (A32) if fault repeats.
260CUSTOMER FAULT 1When a customer defined input is closed to ground, the corresponding fault message is displayed. Default message; editable for customer site requirements.WarningIsolate source of false signal; repair external wiring or replace A34.
261GROUND FAULTWhen a customer defined input is closed to ground, the corresponding fault message is displayed. Default message; editable for customer site requirements.WarningIsolate source of false signal; repair external wiring or replace A34.
262RUPTURE BASINWhen a customer defined input is closed to ground, the corresponding fault message is displayed. Default message; editable for customer site requirements.WarningIsolate source of false signal; repair external wiring or replace A34.
263HIGH GEN TEMPWhen a customer defined input is closed to ground, the corresponding fault message is displayed. Default message; editable for customer site requirements.WarningIsolate source of false signal; repair external wiring or replace A34.
270PHASE ROTATIONThe phase relationship between the generator set and the system bus is not matched.ShutdownVerify genset phase rotation matches bus; verify control wiring to bus PT module.
272FIRST STARTPowerCommand control is not receiving a proper signal from the system master first start sensor.WarningVerify Master First Start Sensor and interconnection wiring.
301HIGH AC VOLTAGEOne or more phase voltages exceeded 130% of nominal, or exceeded 110% of nominal for 10 seconds.ShutdownCheck PCC, alternator, excitation circuit, and PT/CT module wiring.
303LOW AC VOLTAGEOne or more phase voltages dropped below 85% of nominal for 10 seconds.ShutdownCheck PMG/field wiring, rotating rectifier, load and connectors.
313UNDER FREQUENCYIndicates that engine speed has dropped below 90% of nominal for 10 seconds. Five seconds before shutdown, a Load Dump signal is initiated.ShutdownCheck fuel supply, intake air supply and load.
320OVERCURRENTIndicates that generator output current has exceeded 110% of rated for 60 seconds.WarningCheck load and load lead connections.
321OVERCURRENTIndicates that generator output current has exceeded 110% of rated, and that a PCC time/current calculation has initiated an overcurrent shutdown.ShutdownCheck load and load lead connections.
322SHORT CIRCUITIndicates that generator output current has exceeded 175% of rated.ShutdownCheck load and load lead connections.
330OVERLOADThree-phase power output exceeds 105% of standby (or 115% of prime) rating.WarningCheck load and load lead connections.
335REVERSE POWERPower is flowing into the generator set rather than out from the unit.ShutdownVerify CT connections, load sharing lines, and generator set frequency/voltage.
337LOSS OF EXCITATIONAlternator excitation system is improperly adjusted or has failed.ShutdownCheck output voltage calibration, load sharing lines, and leading power factor loads.
FAULT 1Fault 1Undedicated customer-defined fault; may be programmed as timed or non-timed shutdown or fault light only.
FAULT 2Fault 2Undedicated customer-defined fault, same features as Fault 1.
HI ENG TEMPHigh Engine TemperatureEngine shut down due to critically high coolant temperature (above 215F/102C).Shutdown
LO FUELLow FuelFuel supply is marginally low, if equipped (Detector-12).Warning
LO OIL PRESLow Oil PressureEngine shut down due to critically low oil pressure (below 14 psi/97 kPa).Shutdown
LOW ENG TEMPLow Engine TemperatureEngine water jacket temperature is 70F/21C or lower; indicates possible inoperative coolant heater (Detector-12).Warning
OVERCRANKOvercrankStarter locked out because of excessive cranking time (limited to 75 seconds).Shutdown
OVERSPEEDOverspeedEngine shut down because of excessive speed.Shutdown
PRE HI ENG TEMPPre-High Engine TemperatureCoolant temperature is marginally high (205F/97C or higher).WarningAttend to when generator set is shut down.
PRE LO OIL PRESPre-Low Oil PressureEngine oil pressure is marginally low (20 psi/138 kPa or less).WarningAttend to when generator set is shut down.
RUNRunGreen lamp comes on when both primary and secondary starter circuits open after unit starts.Info
SWITCH OFFSwitch OffGenerator set is not in automatic start operation mode (flashing red).Info

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Aligning Generator with Engine (Angular Alignment) adjustment

⚠ Accidental starting of the generator set during this procedure presents the hazard of severe personal injury or death.

Tools: Dial indicator, Shims

  1. Disconnect the negative (-) battery cable(s) before beginning.
  2. Fasten a dial indicator to the generator shaft or cooling fan with the sensing point on the capscrew head or flat surface of the drive disc at the bolt circle diameter.
  3. Bar the engine over in a clockwise rotation as viewed from engine flywheel; do not allow it to roll back on compression.
  4. Determine the total indicator reading (T.I.R.) as the sum of the maximum positive and negative dial indicator readings over one revolution.
  5. Measure the distance from the center of the generator shaft to the indicator measuring point.
  6. Measure the distance from the generator side of the flex discs to the center of the generator mounting bolt.
  7. Compare the distances; multiply this ratio times one half the T.I.R. to approximate the amount of shims to remove or add.
Angular Alignment Procedure (Generator to Engine) adjustment

⚠ Accidental starting during this procedure presents the hazard of severe personal injury or death.

⚠ Do not bar engine over by prying on fan blade.

Tools: dial indicator

  1. Disconnect the negative (-) battery cable(s) before beginning.
  2. Fasten a dial indicator to the generator shaft or cooling fan with sensing point resting on the drive disc capscrew head/flat surface at the bolt circle diameter.
  3. Bar the engine over in a clockwise rotation as viewed from the engine flywheel; do not allow it to roll back on compression at the end of travel of each reading.
  4. Record the total indicator reading (T.I.R.) as the sum of the maximum positive and negative dial indicator readings over one engine revolution.
  5. Compare the measured T.I.R. to the maximum allowed (.001 in. per inch of radius from center of shaft to indicator axis); add or remove shims under the generator mounting feet to correct.
Axial Alignment Procedure (Generator to Engine) adjustment

Tools: dial indicator

  1. Fasten a dial indicator holding device to the skid base, engine block, or generator shell with the sensor point resting on the generator shaft hub.
  2. Bar the engine over in a clockwise rotation through a couple of rotations, recording indicator readings at eight equally spaced points around the shaft diameter to obtain axial T.I.R.
  3. Reduce the measured T.I.R. runout by one half if excessive vibration remains after angular alignment.
Generator/PCC Control Isolation Procedure diagnostic

⚠ HIGH VOLTAGE. Touching uninsulated high voltage parts inside the control box can result in severe personal injury or death.

Tools: Voltmeter, Jumpers, 12 volt battery

  1. Throw the line circuit breaker OFF and shut down the set.
  2. Remove accessory box cover; remove plug P10 from A37 J10.
  3. Prepare to measure output voltage across generator terminals.
  4. Connect 12V battery jumpers to X (P10-6 red) and XX (P10-3 brown).
  5. Check polarity; incorrect polarity makes the test inconclusive.
  6. Start set and connect battery negative to the XX lead.
  7. Rated or higher balanced voltage means generator circuitry is OK.
  8. Unbalanced voltage: troubleshoot main stator; low voltage: exciter/field.
Insulation Resistance (Megger) & Polarization Index (PI) Testing diagnostic

⚠ The windings of medium-voltage (601 through 15,000 volts) generator sets must be dry before the generator is operated.

Tools: Megger or insulation resistance meter, Grounding cluster, High voltage gloves

  1. Perform the Generator Set Grounding Procedure.
  2. Disconnect plug J10 from A37 and AC control leads 4,5,6,7,8.
  3. If RTD option installed, ground all six RTD temperature leads (18 leads).
  4. Perform Insulation Resistance Test and PI Test for desired windings.
  5. Megger test: apply voltage for up to one minute.
  6. PI test: apply voltage for ten minutes; record 1-minute and 10-minute readings.
  7. PI ratio of 2 or greater is good for new and in-service sets.
  8. Investigate and correct low readings before returning set to service.
Megger and PI Test diagnostic

⚠ Medium-voltage (601 to 15,000 volts) windings must be dry before the generator is operated.

Tools: Megger or Insulation Resistance Meter, Wheatstone bridge or digital ohmmeter, Grounding Cluster

  1. Perform the Generator Set Grounding Procedure.
  2. Disconnect plug J10 from the voltage regulator output module and the AC control leads (marked 4, 5, 6, 7, 8).
  3. If RTD option installed, ground all six RTD temperature leads (18 leads total).
  4. Perform the Winding Resistance Test for the desired windings.
  5. Perform the Insulation Resistance (Megger) Test and PI Test for the desired windings.
  6. Megger test: apply voltage for up to one minute.
  7. PI test: apply voltage for ten minutes; record resistance at one minute and ten minutes.
  8. PI is the ten-minute reading divided by the one-minute reading; ratio of two or greater is good.
Testing Diodes diagnostic

⚠ Layers of dust can cause diodes to overheat and fail. Brush dust off regularly.

Tools: Ohmmeter

  1. Disconnect the diode pigtails from the terminal posts.
  2. Using an ohmmeter, measure resistance between pigtail and mounting plate.
  3. Reverse meter test probes and repeat the tests.
  4. Resistance should be high in one direction and low in the other.
  5. If high or low in both directions, replace the diode.
Testing the Float Switch Assembly diagnostic

Tools: Ohmmeter, Feeler gauge

  1. Remove the fuel pump control cover, disconnect the wiring jack and unscrew the assembly from the top of the day tank.
  2. With an ohmmeter, test for electrical continuity between each pair of colored leads while holding the assembly vertical; all readings should be zero.
  3. Lift each float, in turn, to 1/8 inch (3 mm) below the C-clip stop above it and test for continuity; all readings should be infinity.
  4. Use pipe thread sealant when replacing the assembly.
Testing the PMG diagnostic

⚠ HAZARDOUS VOLTAGE. Touching uninsulated parts inside the control housing and power output boxes can result in severe personal injury or death.

Tools: Digital multimeter, Wheatstone bridge or digital ohmmeter

  1. Disconnect PMG leads PMG 2, PMG 3, PMG 4 from connectors in AC harness.
  2. Start the engine and let speed stabilize.
  3. Measure voltage across lead pairs PMG 2&3, 3&4, 4&2.
  4. Voltage should be at least 150 VAC for 50 Hz sets, 180 VAC for 60 Hz.
  5. Stop set; measure resistance across the lead pairs with a Wheatstone bridge.
Current Transformer (CT) Installation installation

⚠ Improper installation of CTs will cause a “335 Reverse Power” shutdown error.

  1. Orient CT dot toward the generator (conventional current into dot).
  2. Route U/A, V/B, W/C load leads through CT21, CT22, CT23.
  3. 6 lead sets: route generator output leads through the CTs.
  4. 12 lead sets: route load wires through the CTs.
  5. Connect CT secondary wire 1 to CT pin 1; 2/3 to pin 2 (high voltage) or pin 3 (low voltage).
Fuel Transfer Pump Motor Connections installation
  1. Remove the end bell cover for access to the motor wiring terminals.
  2. Disconnect the brown lead from motor terminal P103-3 and connect it to terminal P103-6.
  3. Disconnect the red lead from motor terminal P103-2; reconnect to the piggy-back terminal on the lead at motor terminal P103-3.
  4. Cut the white lead from its ring connector at motor terminal P103-4 and strip 1/2 inch (12 mm) of insulation for splicing to harness lead P103-WHITE.
  5. Connect each lead of the five-lead wiring harness to the motor terminal or lead marked on it.
  6. Connect the red motor lead to the piggy-back terminal at motor terminal P103-3.
  7. Secure the end bell cover.
Magnetic Speed Pickup Unit (MPU) Installation installation

⚠ Do not use fan blade to bar over engine. That can damage blades and cause property damage and personal injury.

  1. Bar the engine until a flywheel gear tooth lines up in center of mounting hole.
  2. Thread the sensor in gently by hand until it just touches the gear tooth.
  3. Back it out one quarter turn.
  4. Set the locknut.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
12 lead generator setsLoad wires are routed through the CTsReconnectable gensets (12 leads) have dual secondary CTs (3 pins); CT wire 2/3 to pin 2 (high voltage) or pin 3 (low voltage).
6 lead generator setsGenerator output leads are routed through the CTsNon-reconnectable gensets (6 leads) have single secondary CTs (2 pins).
Cummins PowerCommand generic AC Reconnect Wiring Diagram 625-2755 (Rev. D) and 625-3100 (Rev. F)Applies to models DFAA, DFAB, DFAC, DFBF, DFCB, DFCC, DFEB, DFEC, DFFB, DFGA, DFGB, DFJA, DFJB, DFJC, DFJD, DFLB, DFLC, DFLD, DFMB (625-2755) and models DFAA-DFMB plus DFCE, DFED, DQAA, DQAB, DQBA, DQBB (625-3100).
A (U)CT21U load leads (A phase)CT dot must face the generator; CT terminal 1 connects to metering circuit, terminal 2/3 to ground.
B (V)CT22V load leads (B phase)CT dot must face the generator; terminal 1 to metering circuit, terminal 2/3 to ground.
C (W)CT23W load leads (C phase)CT dot must face the generator; terminal 1 to metering circuit, terminal 2/3 to ground.
110/190, 115/2003Code 31Reconnectible stator
120/2083Code 4460 Hz
120/208, 127/2203Code 519Reconnectible stator
120/2403Code 5D460 Hz
127/2203Code 8460 Hz
139/2403Code $ (99 on nameplate)4No Standard Voltage Code, number 99 is marked on the nameplate for reference information
200/3463Code 523Reconnectible stator
220/3803Code 7460 Hz
220/380, 230/4003Code 520Reconnectible stator
240/4163Code 7X460 Hz
240/416, 254/4403Code 521Reconnectible stator
240/416, 254/4403Code 522Reconnectible stator
240/4803Code 6D460 Hz
277/4803Code 4X460 Hz
347/6003Code 9X460 Hz

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Parts cataloged across the Cummins/Onan KTA38 family

93
Part #DescriptionCategory
UC224CAlternator Modelalternator
UC274FAlternator Modelalternator
052045Lead Acid Battery - Dry (Export)battery
011261Battery Lead (-VE)battery_lead
011262Battery Lead (+VE)battery_lead
011270Battery Lead, +vebattery_lead
035095Clamp Boltbolt
427560Battery Boot, Single Outletboot
427561Battery Boot, Copper Linkboot
035090Battery Clampclamp
049001Clipclip
010156Heater Hose Connectionconnection
0101591” NPT x 16 I/D Hose Connectorconnector
0300-4623-26DFJD (600V)current_transformer
0300-4623-51DFJD BR (0-480V)current_transformer
149-1689Element (Dual Fuel/Water Separator)fuel_filter
FF202Fuel, Spin-Onfuel_filter
FS1216Fuel/Water Sep Spin-Onfuel_filter
155-0675Gasket (Water Outlet)gasket
155-1030Gasket (Exhaust Header)gasket
415-0486Gasket (Fuel Tank - Overhead/Underground Supply)gasket
526-0063Gasket (Fuel Tank)gasket
M-4352580Upper Gasket Setgasket
503-0359Hose (Cooling System - Standpipe)hose
503-0788Hose (Cooling System - Standpipe)hose
3822575Injector and valve adjustment kitinjector
011281STR/STR - STR/Earth Lead (-VE)lead
011250Battery Linklink
05086111/4’’ NPT x 1’’ NPT Hex Nipplenipple
715250M8 Steel Wing Nutsnut
151-0399Controller (Electric Governor)other_service
151-0419Actuator (Electric Governor)other_service
159-0020Cap, Tankother_service
307-0839Valve, Solenoid (Cooling System - Standpipe)other_service
307-1861Valve, Solenoid (Overhead Supply)other_service
309-0407Valve, Float (Overhead Supply)other_service
3096680Piston STC 13.8:1 Ratioother_service
3096681Piston KT Series 15.5:1 Ratioother_service
3096682Piston KTA Series 14.5:1 Ratioother_service
3096683Piston 13.5:1 Ratioother_service
3096684Piston KTA 15.7:1 Ratioother_service
3096685Piston STC 13.9:1 Ratioother_service
331-0027Switch, Thermostaticother_service
332-2634Clamp, Retainer 4 Prior To December 1996 Production (Mounted On Top And Side Of Control Box Wrapper)other_service
3628731Piston STC Kitother_service
3630913Piston KTA-50-G7other_service
3631241Piston Kit STC 13.9:1 Ratioother_service
3631242Piston Kit 13.5:1 Ratioother_service
3631243Piston Kit KTA 15.7:1 Ratioother_service
3631244Piston Kit KTA Series 14.5:1 Ratioother_service
3631245Piston Kit KT Series 15.5:1 Ratioother_service
3631246Piston Kit STC 13.8:1 Ratioother_service
3803530Piston Assembly STCother_service
3804747Piston Kit KTA-50-G7other_service
3804885Piston KTA-50-G8/G9other_service
4089847Piston Kit GTA38/19other_service
4090013Piston Kit KTA-38-M2other_service
4090029Piston Kit QSK19CEother_service
4090181Piston GTA38/19other_service
4097889Piston KTA-38-M2other_service
4910463Piston QSK19R/Mother_service
4910465Piston QSK Seriesother_service
4916177Piston GTA/GQSK19other_service
4918058Piston QSK19CEother_service
4922319Piston QSK19Cother_service
4955233Piston Kit QSK19R/Mother_service
4955235Piston Kit QSK Seriesother_service
4955236Piston Kit QSK19Cother_service
4955238Piston Kit GTA/GQSK19other_service
508-0018Washer, Insulating (1/4" ID)other_service
518-0548-24Clamp, Retainer Begin December 1996 Production (Mounted On Top And Side Of Control Box Wrapper On The Side Towards The Control Box Cover)other_service
518-0548-42Clamp, Retainer 4 Prior To December 1996 Production (Mounted On Top And Side Of Control Box Wrapper)other_service
960-0104other_service
960-0142other_service
960-0263other_service
960-0606other_service
960-0609other_service
M-3804747Piston Kitother_service
V2403-M-E3BGEngine Modelother_service
05050151Reducer, 1/2” x 1/8” NPTreducer
706187M4 x 12 mm Steel Cheesehead Screwscrew
01930388Sender, Oil Temperaturesensor
150-0717Switch Assembly, Overspeedsensor
151-0411Pickup, Magneticsensor
960-0504PCC Control Service Manualservice_manual
960-0507Detector Control Service Manualservice_manual
010167Heater Supportsupport
03090269Switch, Low Engine Temperature (LET)switch
418520Battery Terminal, On Lineterminal
010112Thermostatthermostat
309-0243Valve, Control - Temperature Regulatingthermostat
035105Battery Traytray
716007M4 Plain Washer, Thick, Steel, Form Awasher

Parts cataloged across all variants of this engine family — verify the exact part fits your specific variant and serial number before ordering.

Common questions

What is the oil capacity of the Cummins/Onan KTA38?

The Cummins/Onan KTA38 engine has an oil capacity of 129.0 liters.

What is the displacement of the Cummins/Onan KTA38?

The Cummins/Onan KTA38 has a displacement of 38.0 liters with 12 cylinders.

Which generators use the Cummins/Onan KTA38 engine?

The Cummins/Onan KTA38 powers 12 generator set(s), including AKSA AC1026-38, Cummins/Onan 625.0 DFZ, Cummins/Onan 650.0 DFZ, Cummins/Onan 750.0 DFZ, Cummins/Onan C1000D5B.

How often should you change the oil in the Cummins/Onan KTA38?

The Cummins/Onan KTA38 oil change interval is every 3600 hours.