| Clearance | Belt tensioning spring compression, side bolts | 5/8 | inch | between washer and bearing carrier |
| Clearance | Belt tensioning spring compression, stator stud nuts | 1/2 | inch | between washer and support slide |
| Clearance | Exhaust system to combustible material | 3 | inch | |
| Gap | Ignition magneto (armature) to flywheel air gap | 0.012" to 0.015" | inch | |
| Gap | Spark plug gap | 0.030 | inch (0.8 mm) | |
| Gap | Spark plug gap | 0.040 | inch | |
| Gap | Spark plug gap | 1.02 | mm | |
| Other | AC voltage regulation | 115 | volts | at 60 Hertz AC frequency |
| Other | Compression ratio | 8.6 to 1 | | |
| Other | Nominal starter amp draw in generator | 60 | Amps | |
| Other | Normal battery charge output | 0.8 to 2 | Amps | no load to full load |
| Other | Rotor amp draw | 0.85 | A | ±20% current draw |
| Other | Rotor amp draw | 0.87-.79 | A | ±20% current draw |
| Other | Rotor amp draw | 1.2 | A | ±20% current draw |
| Other | Starter motor maximum amps | 50 | Amps | bench test |
| Pressure | Engine oil pressure (low oil pressure switch test) | above 10 | psi | engine running |
| Pressure | Fuel pump outlet pressure | 2.0 to 3.5 | psi | |
| Pressure | LP fuel system leak test pressure | 90 | psi | |
| Pressure | LP gas pressure at LPG shut off valve inlet | 11-14 | inches water column | |
| Pressure | LP gas pressure at gaseous fuel solenoid valve and secondary regulator inlet | 11 | inches water column | optimum |
| Pressure | LP gas pressure at inlet to gaseous fuel solenoid and secondary regulator | 11 | inches water column | |
| Pressure | LP gas pressure to solenoid valve | 14 | inches water column | do NOT exceed |
| Pressure | LP gas system leak test pressure | 90 | psi (620 kPa) | not less than, test with soap and water solution |
| Pressure | LP primary regulator maximum outlet pressure | 14 | inches water column | do not exceed |
| Pressure | Low oil pressure switch trip point | below 10 | psi | switch closes below this pressure |
| Resistance | AC power winding (11P-22P, 11S-22S, 33-44) | 0.157 - 0.182 | ohms | at 20°C (68°F), tolerance ±5% |
| Resistance | AC power winding (11P-22P, 11S-22S, 33-44) | 0.209 - 0.242 | ohms | at 20°C (68°F), tolerance ±5% |
| Resistance | AC power winding (11P-22P, 11S-22S, 33-44) | 0.280 - 0.320 | ohms | at 20°C (68°F), tolerance ±5% |
| Resistance | Battery charge resistor (R1) | 1 | ohm, 25 watt | |
| Resistance | Battery charge winding (Wires 55 & 66) | 0.092 - 0.107 | ohms | at 20°C (68°F), tolerance ±5% |
| Resistance | Battery charge winding (Wires 55 & 66) | 0.100 - 0.116 | ohms | at 20°C (68°F), tolerance ±5% |
| Resistance | Battery charge winding (Wires 55 & 66) | 0.104 - 0.120 | ohms | at 20°C (68°F), tolerance ±5% |
| Resistance | Battery charge winding (Wires 55 & 77) | 0.076 - 0.088 | ohms | at 20°C (68°F), tolerance ±5% |
| Resistance | Battery charge winding (Wires 55 & 77) | 0.087 - 0.101 | ohms | at 20°C (68°F), tolerance ±5% |
| Resistance | Battery charge winding (Wires 55 & 77) | 0.100 - 0.116 | ohms | at 20°C (68°F), tolerance ±5% |
| Resistance | Bi-metal heater assembly resistance | 37 | ohms | ±20% |
| Resistance | Choke solenoid coil resistance | 3.7 | ohms | |
| Resistance | Excitation 'DPE' winding (Wires 2 & 6) | 1.12 - 1.30 | ohms | at 20°C (68°F), tolerance ±5% |
| Resistance | Excitation 'DPE' winding (Wires 2 & 6) | 1.41 - 1.63 | ohms | at 20°C (68°F), tolerance ±5% |
| Resistance | Excitation 'DPE' winding (Wires 2 & 6) | 1.59 - 1.84 | ohms | at 20°C (68°F), tolerance ±5% |
| Resistance | Fuel solenoid coil resistance (gasoline) | 38.0 | ohms | |
| Resistance | LPG fuel solenoid coil resistance | 30-32 | ohms | |
| Resistance | Rotor minimum insulation resistance | 1.5 | megohms | |
| Resistance | Rotor winding (slip ring to slip ring) | 10.81 | ohms | at 20°C (68°F), tolerance ±5% |
| Resistance | Rotor winding (slip ring to slip ring) | 14.50 - 16.0 | ohms | at 20°C (68°F), tolerance ±5% |
| Resistance | Rotor winding (slip ring to slip ring) | 14.88 | ohms | at 20°C (68°F), tolerance ±5% |
| Resistance | Starter contactor relay coil resistance | 155 | ohms | |
| Resistance | Stator minimum insulation resistance (120 VAC) | 1.12 | megohms | per formula (rated volts/1000)+1 |
| Speed | 2-pole rotor speed for 60 Hertz | 3600 | rpm | |
| Speed | Engine cranking speed for spark test | 350 | rpm or more | cranking |
| Speed | Engine governor speed | 2200 | rpm | |
| Speed | Engine governor speed | 2571 | rpm | |
| Speed | Governed no-load rotor speed | 3720 | rpm | no electrical load |
| Speed | No-load AC output frequency | 62-63 | Hertz | no load |
| Speed | No-load frequency | 62 | Hz | governor set point, no electrical load |
| Speed | Rated horsepower | 27 | hp | at 3600 rpm |
| Speed | Rated rotor speed | 3600 | rpm | |
| Speed | Starter motor minimum rpm | 4500 | rpm | bench test |
| Temperature | Exhaust heat rise limit at combustible material | 117 | deg. F | above ambient air temperature |
| Temperature | High temperature switch actuation (LP models) | 284 | deg. F | |