Home›Controllers›SYNC2 HSB

SYNC2 HSB Controller

The SYNC2 HSB is a generator-set controller. It is used on generator sets from Generac, including the G0070420.

17
Generator sets
Generac
Brand
9–22 kW
Power range
2
Fuel types

Generator sets using this controller

17

Also fitted to: Generac 11 kW, Generac 16 kW, Generac 20 kW, Generac 22 kW, Generac 9 kW.

Engines paired with this controller

3

Troubleshooting

60

Fault codes

CodeMeaningCauseRemedy
0Utility failureCrank and start engine, transfer load to Generator if Utility returns above 75% nominal for 15 seconds
1Engine won’t crank.
10Defective Low Coolant Level Switch
11Defective AUTO/OFF/MANUAL switch
1100Overcrank — Condition - Engine Cranks but will not StartUnit turns over but will not start. Controller is receiving signal on Wire 18.Problem 17
1100Overcrank — Condition - Engine Cranks but will not Start (5 crank attempts). Unit turns over but will not start. Controller is receiving signal on Wire 18.Problem 17
1101Overcrank — Engine/Starter ProblemLimiting number of cranking cycles to protect the starter motor. If the engine has tried to crank for 10 times unsuccessfully, this will trigger.
1101Overcrank — Engine/Starter Problem. Limiting number of cranking cycles to protect the starter motor.If the engine has tried to crank for 10 times unsuccessfully, this will trigger.
12Open/disconnected wire #15A between AUTO/OFF/MANUAL switch and Control Module circuit board.
1200Overspeed — ALARMProlonged (60 Hz on a 50 Hz unit, 72Hz on 60Hz unit) over specified Hz for 3 seconds. Possible cause: Stepper motor/mixer body assembly issueTest 12
1200Overspeed — ProlongedOver 72 Hz for 3 seconds. Possible cause: Stepper motor/mixer body assembly issue.Test 12
1200Overspeed — Prolonged (60 Hz on a 50 Hz unit, 72Hz on 60Hz unit) Over specified Hz for 3 seconds.Stepper motor/mixer body assembly issueTest 12
1205Overspeed — ALARMInstantaneous (62 Hz on a 50 Hz unit, 75Hz on 60Hz unit) over specified Hz for 0.1 second (100 milliseconds). Possible cause: Stepper motor/mixer body assembly issueTest 12
1205Overspeed — InstantaneousOver 75 Hz for .1 second (100 milliseconds). Possible cause: Stepper motor/mixer body assembly issue.Test 12
1205Overspeed — Instantaneous (62 Hz on a 50 Hz unit, 75Hz on 60Hz unit) Over specified Hz for 0.1 second (100 milliseconds).Stepper motor/mixer body assembly issueTest 12
1207Overspeed — ALARMMonitors zero cross timing of the AVR to determine the alternator frequency which is a speed indicator. Set for 150 milliseconds of 4500 rpm or higher. Used if the normal ignition pulse sequence(s) are not being seen by the controllerTest 64 and Test 60
1207Overspeed — Monitors zero cross timing of the AVR to determine the alternator frequency which is a speed indicator. Set for 150 milliseconds of 4500 rpm or higher. Used if the normal ignition pulse sequence(s) are not being seen by the controller.Test 64 and Test 60
13Engine starts then shuts down.
1300Low Oil Pressure — ALARMOccurred while running. The default Extended alarm for low oil pressureCheck oil level and pressure
1300Low Oil Pressure — Occurred while runningThe default Extended alarm for low oil pressure.Check oil level and pressure. Test 61
1300Low Oil Pressure — Occurred while running. The default Extended alarm for low oil pressure.Check oil level and pressure. Test 61
1400High Temperature — ALARMCondition - Air Flow Impeded / Flow IssueCheck the inlet/outlet for debris; check temperature sensor and wiring
1400High Temperature — Condition - Air Flow Impeded / Flow IssueCheck the inlet/outlet for debris. Check temperature sensor and wiring. Test 62
1501RPM Sensor — ALARMTwin Cylinder+Running. Twin Cylinder Running faults to RPM Sensor Loss. Possible Causes: air pocket in fuel line, dirty fuel, missing ignition pulse (loss of one of the primary coils)Test 50 and Test 64
1501RPM Sensor — Twin Cylinder+RunningTwin Cylinder Running faults to RPM sensor loss. Possible Causes: air pocket in fuel line, dirty fuel, missing ignition pulse (loss of one of the primary coils).Test 50 and Test 64
1501RPM Sensor — Twin Cylinder+Running. Twin Cylinder Running faults to RPM Sensor Loss.Air pocket in fuel line; dirty fuel; missing ignition pulse (loss of one of the primary coils)Test 50 and Test 64
1505RPM Sensor — ALARMTwin Cylinder+Cranking. Twin Cylinder Cranking faults to RPM sensor loss. Possible Cause: starter motor issue, missing ignition pulse (loss of one of the primary coils)If engine cranks, Test 64; if engine does not crank, Problem 15
1505RPM Sensor — Twin Cylinder+CrankingTwin Cylinder Cranking faults to RPM sensor loss Possible Cause: starter motor issue, missing ignition pulse (loss of one of the primary coils).If engine cranks, Test 64. If engine does not crank, Problem 15.
1505RPM Sensor — Twin Cylinder+Cranking. Twin Cylinder Cranking faults to RPM sensor loss.Starter motor issue; missing ignition pulse (loss of one of the primary coils)If engine cranks, Test 64. If engine does not crank, Problem 15.
1511RPM Sensor — ALARMSingle Cylinder+Running. Single Cylinder Running RPM sensor loss. Possible Causes: air pocket in fuel line, dirty fuel. Loss of ignition pulseTest 50 and Test 64
1511RPM Sensor — Single Cylinder+RunningSingle Cylinder Running with Low Fuel Pressure faults to RPM sensor loss Possible Causes: air pocket in fuel line, dirty fuel.Test 50 and Test 64
1511RPM Sensor — Single Cylinder+Running. Single Cylinder Running RPM sensor loss.Air pocket in fuel line; dirty fuel; loss of ignition pulseTest 50 and Test 64
1515RPM Sensor — ALARMSingle Cylinder+Cranking. Single Cylinder Cranking faults to RPM sensor loss. Possible Cause: starter motor and/or engine issue. Loss of ignition pulseIf engine cranks, Test 64; if engine does not crank, Problem 15
1515RPM Sensor — Single Cylinder+CrankingSingle Cylinder Cranking faults to RPM sensor loss Possible Cause: starter motor issue.If engine cranks, Test 64. If engine does not crank, Problem 15.
1515RPM Sensor — Single Cylinder+Cranking. Single Cylinder Cranking faults to RPM sensor loss.Starter motor and/or engine issue; loss of ignition pulseIf engine cranks, Test 64. If engine does not crank, Problem 15.
1600Underspeed — ALARMCondition - Unit is Overloaded (55 Hz for 60 Hz for 30 sec, 40 Hz for 50 Hz unit). Unit is Overloaded slowing engine speed, fuel supply low or throttle control problemProblem 3, or Test 50, or Test 12
1600Underspeed — Condition - Unit is OverloadedUnit is Overloaded slowing engine speed, fuel supply low or throttle control problem.Problem 1, Test 50 or Test 12
1600Underspeed — Condition - Unit is Overloaded (55 Hz for 60 Hz for 30 sec, 40 Hz for 50 Hz unit). Unit is Overloaded slowing engine speed.Fuel supply low; throttle control problemProblem 3, or Test 50, or Test 12
1603UnderspeedThe engine never comes up to 3700 RPM.Check fuel selection and fuel supply
1603Underspeed — The engine never comes up to 3600 RPM.Check fuel selection and fuel supply
1800Overvoltage — ALARMProlonged Over-VoltagePreliminary Output Voltage Test (firmware v1.12 and above). Note: Update controller to latest firmware
1800Overvoltage — Prolonged Over-VoltageProblem 2; Preliminary Output Voltage Test (firmware v1.12 and above). Note: Update controller to latest firmware.
1900Undervoltage — ALARMProlonged Under-Voltage. Undervoltage due to loss of voltage. Below 80% for 10+ secondsPreliminary Output Voltage Test (firmware v1.12 and above). Note: Update controller to latest firmware
1900Undervoltage — Prolonged Under-VoltageUndervoltage due to loss of voltage for some time (10+ seconds).Test 5
1900Undervoltage — Prolonged Under-Voltage. Undervoltage due to loss of voltage. Below 80% for 10+ seconds.Preliminary Output Voltage Test (firmware v1.12 and above). Note: Update controller to latest firmware.
1901Undervoltage — ALARMInstantaneous. Undervoltage due to sudden loss of voltage. (Voltage less than 15 sec 2 sec+)Preliminary Output Voltage Test (firmware v1.12 and above). Note: Update controller to latest firmware
1901Undervoltage — InstantaneousUndervoltage due to sudden loss of voltage.Problem 1
1901Undervoltage — Instantaneous. Undervoltage due to sudden loss of voltage. (Voltage less than 15 sec 2 sec+)Preliminary Output Voltage Test (firmware v1.12 and above). Note: Update controller to latest firmware.
1902Undervoltage — ALARMBoth Zero Crosses missing. Undervoltage due to faulty excitation winding, or zero cross circuit, or circuit in general. Possible cause: loose wiring, field boost hardware failure. (Both zero cross missing greater than 1.5 sec)Problem 2
1902Undervoltage — Both Zero Crosses missingUndervoltage due to faulty excitation winding, or zero cross circuit, or circuit in general. Possible cause: loose wiring, field boost hardware failureProblem 1
1902Undervoltage — Both Zero Crosses missing. Undervoltage due to faulty excitation winding, or zero cross circuit, or circuit in general. (Both zero cross missing greater than 1.5 sec)Loose wiring; field boost hardware failurePreliminary Output Voltage Test (firmware v1.12 and above). Note: Update controller to latest firmware.
1906Undervoltage — ALARMSingle Zero Cross missing. Undervoltage due to faulty excitation winding, zero cross circuit, or circuit in general. Possible cause: field boost hardware failure. (One zero cross missing greater than 1.5 sec)
1906Undervoltage — Single Zero Cross missingUndervoltage due to faulty excitation winding, zero cross circuit, or circuit in general. Possible cause: field boost hardware failureProblem 1
1906Undervoltage — Single Zero Cross missing. Undervoltage due to faulty excitation winding, zero cross circuit, or circuit in general. (One zero cross missing greater than 1.5 sec)Field boost hardware failurePreliminary Output Voltage Test (firmware v1.12 and above). Note: Update controller to latest firmware.
2Engine cranks but won't start
2099Wiring ErrorCustomer connection low voltage and high voltage wires are crossed.Check customer connection in generator
2099Wiring Error — ALARMMis-wired. Customer connection low voltage and high voltage wires are crossed
2099Wiring Error — Mis-wired. Customer connection low voltage and high voltage wires are crossed.Check customer connection in generator
2100Overload Remove LoadOverloaded - Default (Output Current Method). Unit is overloaded, one of the two CTs is detecting an overload condition.Check transfer switch loadshed functionality. (Change load dynamics or utilize loadshed). Remove Load
2100Overload Remove Load — ALARMOverloaded - Default (Output Current Method). Unit is overloaded. One or both CT(s) detecting an overload conditionCheck transfer switch loadshed functionality. (Change load dynamics or utilize loadshed)

Fault codes and symptom→remedy steps extracted from this controller’s service/owner documentation; verify against the official manual before servicing. Aggregated from the service documentation of generator sets built on this controller.