HomeControllersQc1002

Qc1002 Controller

The Qc1002 is a generator-set controller. It is used on generator sets from Atlas Copco, John Deere and Volvo Penta, including the QAS 100 Pd, QAS 14, QAS 150 John Deere and QAS 20.

30
Generator sets
3
Brands
13–13 kW
Power range
Diesel
Fuel

Generator sets using this controller

30

Used across brands: Atlas Copco, John Deere, Volvo Penta

Atlas Copco QAS 100 PdAtlas Copco QAS 14Atlas Copco QAS 150 John DeereAtlas Copco QAS 20Atlas Copco QAS 25Atlas Copco QAS 250 VolvoAtlas Copco QAS 250-330Atlas Copco QAS 45Atlas Copco QAS 500 VolvoAtlas Copco QAS 60 PdAtlas Copco QAS 600 VolvoAtlas Copco QAS 70-90-120 John DeereAtlas Copco QAS 80 PdAtlas Copco QAS 90-120Atlas Copco QAX 12Atlas Copco QAX 12-20-30 DdAtlas Copco Qc1002John Deere QAS 150John Deere QAS 250John Deere QAS 250 ACJohn Deere QAS 330 ACJohn Deere QAS 70-90-120Volvo Penta QAS 125-150

Also fitted to: Atlas Copco QAX 20/24, Atlas Copco QAX 30/35.

Engines paired with this controller

2

Troubleshooting

35

Symptoms & remedies

SymptomCauseRemedy
After being excited alternator does not exciteConnections are interrupted.Check connection cables as per attached drawings.
After being excited the alternator still gives 0 VoltConnections are interrupted.Check connection cables, measure winding resistances and compare with values mentioned in the alternator manual.
After being excited the alternator still gives 0 Volt.Connections are interrupted.Check connection cables, measure winding resistances and compare with values mentioned in the alternator manual.
Alternator does not exciteBlown fuse.Replace fuse.
Alternator gives 0 VoltBlown fuse.Replace fuse.
Checking ammeters P1, P2 and P3Measure by means of a clamp-on probe the outgoing current during the load. Compare the measured currents with the currents on the corresponding ammeters. Both readings should be the same.
Checking voltmeter P4Put a voltmeter in parallel with voltmeter P4 on the control panel. Check that the read-out of both voltmeters is the same. Stop the generator and disconnect one terminal. Check that the internal resistance of the voltmeter is high.
Current too high, power factor lower than 0.8; speed lower than 10% of rated speedFailed regulator.Substitute regulator.
Current too high, power factor lower than 0.8; speed lower than 10% of rated speed.Failed regulator.Substitute regulator.
Failed regulatorSubstitute regulator.
Failed regulator.Substitute regulator.
High fuel consumptionRestriction in air filter/cleaner or induction system.; Fault in atomisers or atomisers of an incorrect type.; Fault in cold start system.; Wrong type or grade of fuel used.; Restricted movement of engine speed control.; Restricted exhaust pipe.
High voltage at no loadVoltage potentiometer out of setting.Reset voltage.
Higher than rated voltage at loadVoltage potentiometer out of setting.Reset voltage potentiometer.
Insufficient residual voltageIncrease the speed by 15%.
Intervention by protectionCheck frequency/voltage regulator.
Intervention by protection.Check frequency/voltage regulator.
Intervention of protectionCheck frequency/voltage regulator.
Intervention of protection.Check frequency/voltage regulator.
Low voltage at no loadVoltage potentiometer out of setting.Reset voltage.
Lower than rated voltage at loadVoltage potentiometer out of setting.Reset voltage potentiometer.
MisfireRestriction in a fuel pipe.; Fault in fuel lift pump.; Dirty fuel filter element.; Air in fuel system.; Fault in atomisers or atomisers of an incorrect type.; Fault in cold start system.; Engine temperature is too high.; Incorrect valve tip clearances.
No residual voltageExcite the alternator by applying a 12V battery voltage with a 30 W resistor in series on the + and - terminals of the electronic regulator, respecting the polarities.
No residual voltage.Excite the alternator by applying a 12V battery voltage with a 30 W resistor in series on the + and - terminals of the electronic regulator, respecting the polarities.
Not enough powerRestriction in a fuel pipe.; Fault in fuel lift pump.; Dirty fuel filter element.; Air in fuel system.; Fault in atomisers or atomisers of an incorrect type.; Restriction in air filter/cleaner or induction system.; Air in fuel system.; Fault in atomisers or atomisers of an incorrect type.; Wrong type or grade of fuel used.; Restricted movement of engine speed control.; Restriction in exhaust pipe.; Engine temperature is too high.; Engine temperature is too low.
Regulator out of settingRegulate stability of regulator by acting on STABILITY potentiometer.
Regulator out of setting.Regulate stability of regulator by acting on STABILITY potentiometer.
Rotating bridge failureCheck diodes, disconnect cables.
Rotating bridge failure.Check diodes, disconnect cables.
The engine does not start or is difficult to startStarter motor turns engine too slowly.; Fuel tank empty.; Fault in fuel control solenoid.; Restriction in a fuel pipe.; Fault in fuel lift pump.; Dirty fuel filter element.; Air in fuel system.; Fault in atomisers.; Cold start system used incorrectly.; Fault in cold start system.; Restriction in fuel tank vent.; Wrong type or grade of fuel used.; Restriction in exhaust pipe.
The pressure of the lubricating oil is too lowWrong grade of lubricating oil.; Not enough lubricating oil in sump.; Defective gauge.; Dirty lubricating oil filter element.
The starter motor turns the engine too slowlyBattery capacity too low.; Bad electrical connection.; Fault in starter motor.; Wrong grade of lubricating oil.
Unstable voltageSpeed variation in engine.Check regularity of rotation.
Winding failureCheck windings.
Winding failure.Check windings.

Fault codes and symptom→remedy steps extracted from this controller’s service/owner documentation; verify against the official manual before servicing. Aggregated from the service documentation of generator sets built on this controller.