Qc1002 Controller

The Qc1002 is a generator-set controller. It is used on generator sets from Atlas Copco, John Deere and Volvo Penta, including the QAS 100 Pd, QAS 14, QAS 150 John Deere and QAS 20.

29
Generator sets
3
Brands
Diesel
Fuel

Generator sets using this controller

29

Used across brands: Atlas Copco, John Deere, Volvo Penta

Atlas Copco QAS 100 PdAtlas Copco QAS 14Atlas Copco QAS 150 John DeereAtlas Copco QAS 20Atlas Copco QAS 25Atlas Copco QAS 250 VolvoAtlas Copco QAS 250-330Atlas Copco QAS 45Atlas Copco QAS 500 VolvoAtlas Copco QAS 60 PdAtlas Copco QAS 600 VolvoAtlas Copco QAS 70-90-120 John DeereAtlas Copco QAS 80 PdAtlas Copco QAS 90-120Atlas Copco QAX 12Atlas Copco QAX 12 DdAtlas Copco QAX 12-20-30 DdAtlas Copco QAX 20 DdAtlas Copco QAX 30 DdAtlas Copco Qc1002John Deere QAS 150John Deere QAS 250John Deere QAS 250 ACJohn Deere QAS 330 ACJohn Deere QAS 70-90-120Volvo Penta QAS 125-150

Also fitted to: Atlas Copco QAX 20/24, Atlas Copco QAX 30/35.

Troubleshooting

34

Symptoms & remedies

SymptomCauseRemedy
After being excited alternator does not exciteConnections are interruptedCheck connection cables as per attached drawings
After being excited the alternator still gives 0 VoltConnections are interruptedCheck connection cables, measure winding resistances and compare with values mentioned in the alternator manual
After being excited the alternator still gives 0 Volt.Connections are interrupted.Check connection cables, measure winding resistances and compare with values mentioned in the alternator manual.
Alternator does not exciteBlown fuseReplace fuse
Alternator gives 0 VoltBlown fuse.Replace fuse.
Bad compressionRestriction in air filter/cleaner or induction system
Black exhaust smokeRestriction in air filter/cleaner or induction system; Fault in atomisers or atomisers of an incorrect type; Fault in cold start system; Wrong type or grade of fuel used; Restriction in exhaust pipe; Engine temperature is too low; Incorrect valve tip clearances; Engine overload
Blue or white exhaust smokeWrong grade of lubricating oil; Fault in cold start system; Engine temperature is too low
Crankcase pressureRestriction in breather pipe
Failed regulator.Substitute regulator.
High fuel consumptionRestriction in air filter/cleaner or induction system; Fault in atomisers or atomisers of an incorrect type; Fault in cold start system; Wrong type or grade of fuel used; Restricted movement of engine speed control; Restriction in exhaust pipe; Engine temperature is too low; Incorrect valve tip clearances
High voltage at no loadVoltage potentiometer out of settingReset voltage potentiometer
Higher than rated voltage at loadVoltage potentiometer out of settingReset voltage potentiometer
Intervention by protection.Current too high, power factor lower than 0.8; speed lower than 10% of rated speed. Failed regulator. Substitute regulator.
Intervention of protection.Check frequency/voltage regulator.
Low voltage at no loadVoltage potentiometer out of settingReset voltage potentiometer
Lower than rated voltage at loadVoltage potentiometer out of settingReset voltage potentiometer
MisfireRestriction in a fuel pipe; Fault in fuel lift pump; Dirty fuel filter element; Air in fuel system; Fault in atomisers or atomisers of an incorrect type; Fault in cold start system; Engine temperature is too high; Incorrect valve tip clearances
No residual voltage.Excite the alternator by applying a 12V battery voltage with a 30 W resistor in series on the + and - terminals of the electronic regulator, respecting the polarities.
Not enough powerRestriction in a fuel pipe; Fault in fuel lift pump; Dirty fuel filter element; Restriction in air filter/cleaner or induction system; Air in fuel system; Fault in atomisers or atomisers of an incorrect type; Restriction in fuel tank vent; Wrong type or grade of fuel used; Restricted movement of engine speed control; Restriction in exhaust pipe; Engine temperature is too high; Engine temperature is too low
Regulator out of setting.Regulate stability of regulator by acting on STABILITY potentiometer.
Rotating bridge failure.Check diodes, disconnect cables.
The engine does not start or is difficult to startStarter motor turns engine too slowly; Fuel tank empty; Fault in fuel control solenoid; Restriction in a fuel pipe; Fault in fuel lift pump; Dirty fuel filter element; Air in fuel system; Fault in atomisers; Cold start system used incorrectly; Fault in cold start system; Restriction in fuel tank vent; Wrong type or grade of fuel used; Restriction in exhaust pipe
The engine knocksFault in fuel lift pump; Fault in atomisers or atomisers of an incorrect type
The engine runs erraticallyFault in fuel control
The engine shuts down after approx. 15 sec.Bad connection towards oil pressure
The engine starts and stopsDirty fuel filter element
The engine temperature is too highRestriction in air filter/cleaner or induction system
The pressure of the lubricating oil is too highWrong grade of lubricating oil
The pressure of the lubricating oil is too lowWrong grade of lubricating oil; Not enough lubricating oil in sump; Defective gauge; Dirty lubricating oil filter element
The starter motor turns the engine too slowlyBattery capacity too low; Bad electrical connection; Fault in starter motor; Wrong grade of lubricating oil
Unstable voltageSpeed variation in engineCheck regularity of rotation
VibrationFault in atomisers or atomisers of an incorrect type
Winding failure.Check windings.