PowerCommand 3.3 ( Capable) Controller

The PowerCommand 3.3 ( Capable) is a generator-set controller. It is used on generator sets from Cummins/Onan, including the C1250D6E and C1500D6E.

2
Generator sets
Cummins/Onan
Brand
1250–1500 kW
Power range
Diesel
Fuel

Generator sets using this controller

2

Engines paired with this controller

1

Troubleshooting

2

Symptoms & remedies

SymptomRemedy
Battle short modeWhen enabled and the battle short switch is active, the control will allow some shutdown faults to be bypassed. If a bypassed shutdown fault occurs, the fault code and description will still be annunciated, but the genset will not shutdown. This will be followed by a fail to shutdown fault. Emergency stop shutdowns and others that are critical for proper operation (or are handled by the engine ECM) are not bypassed.
DerateThe Derate function reduces output power of the genset in response to a fault condition. If a Derate command occurs while operating on an isolated bus, the control will issue commands to reduce the load on the genset via contact closures or Modbus. If a Derate command occurs while in utility parallel mode, the control will actively reduce power by lowering the base load kW to the derated target kW.

Fault codes and symptom→remedy steps extracted from this controller’s service/owner documentation; verify against the official manual before servicing. Aggregated from the service documentation of generator sets built on this controller.