HomeEnginesCummins/Onan QSK38-G18

Cummins/Onan QSK38-G18 Engine

The Cummins/Onan QSK38-G18 is a 37.8 L 12-cylinder turbocharged and low temperature after-cooled engine rated at 1800 rpm, producing up to 1659 kW. It powers generator sets from Cummins/Onan, including the C1250D6E and C1500D6E. It holds 117 L (30.9 gal) of oil and 272 L (71.9 gal) of coolant.

Also known as: Cummins Inc. QSK38-G18

Part of the Cummins/Onan QSK38 engine family — 7 variants share parts & fitment.

37.8 L
Displacement
12
Cylinders
1800 rpm
Rated speed
1659 kW
Gross power

Engine specifications

Oil capacity117.0 L
Coolant capacity272.0 L
Displacement37.8 L
Cylinders12
AspirationTurbocharged and low temperature after-cooled
Rated speed1800 rpm
Gross power1659 kW

Common problems

2
  • Derate
    Fix: The Derate function reduces output power of the genset in response to a fault condition. If a Derate command occurs while operating on an isolated bus, the control will issue commands to reduce the load on the genset via contact closures or Modbus. If a Derate command occurs while in utility parallel mode, the control will actively reduce power by lowering the base load kW to the derated target kW.
  • Battle short mode
    Fix: When enabled and the battle short switch is active, the control will allow some shutdown faults to be bypassed. If a bypassed shutdown fault occurs, the fault code and description will still be annunciated, but the genset will not shutdown. This will be followed by a fail to shutdown fault. Emergency stop shutdowns and others that are critical for proper operation (or are handled by the engine ECM) are not bypassed.

Compiled from service & troubleshooting documentation across every generator set that uses the Cummins/Onan QSK38-G18.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
Fuel40-50 Cetane numberASTM D975 No. 2-D300-500 ppm Sulfur
Fuel40-50 Cetane number, ASTM D975 No. 2-DASTM D975300-500 ppm Sulfur; #2 Diesel low-sulfur/ultra-low sulfur required for start-up

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Fault codes

9
CodeNameMeaningSeverityAction
27Low AC voltage shutdownVoltage on any phase has dropped below a preset value. Adjustable over a range of 50-95% of reference voltage, time delay 2-20 seconds. Default value is 85% for 10 seconds. Function tracks reference voltage. Control does not nuisance trip when voltage varies due to the control directing voltage to drop, such as during a V/Hz roll-off or synchronizing.ShutdownShutdown genset.
32Reverse power shutdownAdjustment range: 5-20% of standby kW rating, delay 1-15 seconds. Default: 10%, 3 seconds.ShutdownShutdown genset.
40Reverse Var shutdownShutdown level is adjustable: 15-50% of rated Var output, delay 10-60 seconds. Default: 20%, 10 seconds.ShutdownShutdown genset.
46Negative sequence overcurrent warningControl protects the generator from damage due to excessive imbalances in the three phase load currents and/or power factors.WarningWarning.
51Overcurrent warning/shutdownImplementation of the thermal damage curve with instantaneous trip level calculated based on current transformer ratio and application power rating.ShutdownShutdown or warning.
51GGround fault overcurrentControl detects a ground fault either by an external ground fault relay via a contact input or the control can measure the ground current from an external current transformer. Associated time delays and thresholds are adjustable via InPower or HMI.ShutdownShutdown or warning.
59High AC voltage shutdownOutput voltage on any phase exceeds preset values. Time to trip is inversely proportional to amount above threshold. Values adjustable from 105-125% of nominal voltage, with time delay adjustable from 0.1-10 seconds. Default value is 110% for 10 seconds.ShutdownShutdown genset.
81 uUnder frequency shutdownGenset output frequency cannot be maintained. Settings are adjustable from 2-10 Hz below reference governor set point, for a 5-20 second time delay. Default: 6 Hz, 10 seconds. Under frequency protection is disabled when excitation is switched off, such as when engine is operating in idle speed mode.ShutdownShutdown genset.
81oOver frequency shutdown/warningGenset is operating at a potentially damaging frequency level. Settings are adjustable from 2-10 Hz above nominal governor set point for a 1-20 second time delay. Default: 6 Hz, 20 seconds, disabled.WarningWarning or shutdown.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

1
Series C4E-1D Cast Iron Spring-Flex Mounting Installation installation

Tools: Wrench

  1. Space and arrange isolators per installation drawings; ship fully assembled.
  2. Set isolators on floor or sub-base; align centerlines with equipment mounting holes.
  3. Shim or grout as required; level all base plates at same elevation (1/4 in max difference).
  4. Unless specified, mountings need not be fastened to floor. If required, bolt through slots.
  5. Remove adjusting bolt C with nut B from top housing A; do not discard.
  6. Place machine onto top plate A; weight lowers upper housing onto lower housing.
  7. Align equipment mounting hole to top housing tapped hole.
  8. Turn nuts B up on leveling bolts so they will not interfere with leveling.
  9. Insert bolts C through machine base holes and hand-screw into tapped hole as far as possible.
  10. Adjust each isolator in sequence: screw down one complete turn on adjusting bolt.
  11. Adjust until 1/4 in gap is obtained on all mounts.
  12. Turn nut on adjusting bolt C down against machine leg and lock with wrench.
  13. Installation is complete.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Parts cataloged across the Cummins/Onan QSK38 family

4
Part #DescriptionCategory
MCBQSK0068Water Pump Gasket Setgasket
M-2885786Cylinder Liner Kitother_service
M-3007525Cylinder Liner Kitother_service
M-3022157Cylinder Linerother_service

Parts cataloged across all variants of this engine family — verify the exact part fits your specific variant and serial number before ordering.

Common questions

What is the oil capacity of the Cummins/Onan QSK38-G18?

The Cummins/Onan QSK38-G18 engine has an oil capacity of 117.0 liters.

What is the displacement of the Cummins/Onan QSK38-G18?

The Cummins/Onan QSK38-G18 has a displacement of 37.8 liters with 12 cylinders.

Which generators use the Cummins/Onan QSK38-G18 engine?

The Cummins/Onan QSK38-G18 powers 2 generator set(s), including Cummins/Onan C1250D6E, Cummins/Onan C1500D6E.

What is a common problem with the Cummins/Onan QSK38-G18 engine?

A commonly reported issue on generators using the Cummins/Onan QSK38-G18 is: Derate. Fix: The Derate function reduces output power of the genset in response to a fault condition. If a Derate command occurs while operating on an isolated bus, the control will issue commands to reduce the load on the genset via contact closures or Modbus. If a Derate command occurs while in utility parallel mode, the control will actively reduce power by lowering the base load kW to the derated target kW..