The Power Zone 200 is a generator-set controller. It is used on generator sets from Generac, including the G007258-0, G007259-0, G007323-0 and G007324-0.

9
Generator sets
Generac
Brand
10–28 kW
Power range
Bi-Fuel (NG/LP)
Fuel

Generator sets using this controller

9

Also fitted to: Generac 22 kW, Generac 24 KW, Generac 26 kW, Generac 28 kW, Generac Air-Cooled Residential Standby Generator.

Engines paired with this controller

2

Troubleshooting

40

Fault codes

CodeMeaningRemedy
000001DANGER
1Engine won’t crank.
10Defective Low Coolant Level Switch
11Defective AUTO/OFF/MANUAL switch
12Open/disconnected wire #15A between AUTO/OFF/MANUAL switch and Control Module circuit board.
13Engine starts then shuts down.
1501RPM Sensor ALARM
1900Prolonged Over-Voltage Undervoltage
1901Instantaneous Undervoltage
1902Undervoltage
2Engine cranks but won't start
2099Wiring Error ALARM
2100Stepper Overcurrent ALARM
2102Overloaded ALARM
2399Overload Remove Load ALARM
3Engine starts hard, runs rough.
4Engine oil level is low.
5Engine is overheated.
6Defective Low Oil Pressure Switch
7Defective Coolant Temperature Switch
8Defective Control Module circuit board
9Coolant Level is Low.
Battery is DeadProblem 22 – Battery is DeadTest 45 – Check Battery and Cables
Evolution E-Code 2400Engine Will Not Crank When Utility Power Source FailsTest 44 – Check 7.5 Amp Fuse Evolution Alarm Code 2400
Generator Will Not ExerciseProblem 20 – Generator Will Not ExerciseTest 45 – Check Battery and Cables
No Low Speed ExerciseProblem 21 – No Low Speed Exercise
Safety004Not statedEngine shutdown; restart after temperature returns to safe operating level; add oil and reset generator control board

Symptoms & remedies

SymptomCauseRemedy
Engine cranks but won't start1. Out of fuel. 2. Fuel solenoid (FS) is defective 3. Open Wire #14A from Engine Control circuit board. 4. Spark plugs defective. 5. Door on tank not closed.1. Replenish fuel. 2. Replace solenoid.* 3. Reconnect wire. 4. Clean, regap or replace plugs. 5. Close door on tank.
Engine oil level is low.1. Engine starts then shuts down. AUTO/OFF/MANUAL Switch at OFF, engine continues to run
Engine speed and frequency drop excessively under loadEngine may be underpowered; result of dirty air cleaner, loss of engine compression, faulty fuel settings, or incorrect ignition timingRefer to Section 4.5 Diagnostic Tests for repair procedures
Engine starts hard, runs rough.1. Flame arrestor (air cleaner) plugged or damaged. 2. Plugged fuel line. 3. Defective spark plugs. 4. Fuel pressure incorrect.
Engine won’t crank.1. 15 amp fuse blown. 2. Loose or corroded or defective battery cables. 3. Defective starter contactor. 4. Defective starter motor. 5. Dead or Defective Battery. 6. 5 amp fuse blown.1. Replace fuse. 2. Tighten, clean or replace battery cables as necessary. 3. Replace contactor.* 4. Replace starter motor.* 5. Remove, change or replace battery. 6. Replace fuse.*
Generator Produces High VoltageTEST 1 - CHECK AC OUTPUT VOLTAGE, HIGH -> TEST 11 - CHECK AC OUTPUT FREQUENCY, HIGH -> TEST 12 - CHECK STEPPER MOTOR CONTROL, REFER TO PROBLEM 1, TEST 3 - CALIBRATE VOLTAGE, VOLTAGE OUTPUT AT BREAKER IS BELOW 220 OR ABOVE 270 VOLTS -> VOLTAGE OUTPUT AT BREAKER IS BETWEEN 220-270 VAC -> FREQUENCY O.K., BUT VOLTAGE INCORRECT -> FREQUENCY AND VOLTAGE O.K. -> STOP TESTS
Generator Shuts Down for Under VoltagePerform FBCT, Preliminary Output Voltage Test (if Evolution non-Synergy with Firmware v1.12 or higher), TEST 4 - Fixed Excitation / Rotor Amp Draw, RE-TEST, REPLACE CONTROLLER if necessary, CHECK DMM FUSES, TEST 5 - SENSING CIRCUIT WIRES 11 AND 44, BAD -> TEST 6 - EXCITATION WINDING CIRCUIT 2 AND 6, BAD -> TEST 8 - RESISTANCE CHECK OF ROTOR CIRCUIT, GOOD -> TEST 7 - TEST STATOR, BAD -> PERFORM STATOR INSULATION RESISTANCE, REPLACE STATOR ONLY if necessary, TEST 10 - TEST ROTOR ASSEMBLY, BAD -> REPLACE ROTOR AND STATOR, BAD -> REPAIR OR REPLACE, BAD -> ROTOR CIRCUIT FAILURE, TEST 9 - CHECK BRUSHES & SLIP RINGS, GOOD -> BAD -> TEST 10 - TEST ROTOR ASSEMBLY, GOOD -> TEST 7 - TEST STATOR, BAD -> REPLACE ROTOR ONLY, BAD -> REPLACE ROTOR AND STATOR, PERFORM ROTOR INSULATION RESISTANCE TEST
High Temperature ALARMCheck the inlet/outlet for debris. Check temperature sensor and wiring.
Low Oil Pressure ALARMOccurred while running The default Extended alarm for low oil pressure. Check oil level and pressure.
No AC output from generator.Defective Control Module circuit boardReplace board.*
Overspeed ALARMProlonged (60 Hz on a 50 Hz unit, 72Hz on 60Hz unit) Over specified Hz for 3 seconds. Possible cause: Stepper motor/mixer body assembly issue.
Unstable Voltage or Incorrect Output Which is Not Triggering a ShutdownTEST 1 - CHECK AC OUTPUT VOLTAGE, ERRATIC -> PROCEED TO PROBLEM 3
Voltage and Frequency Drop Excessively When Loads Are AppliedTEST 14 - CHECK VOLTAGE AND FREQUENCY UNDER LOAD, BOTH LOW -> TEST 15 - CHECK FOR OVERLOAD CONDITION, NOT OVERLOADED -> GOOD -> IF RECONFIGURED TO LP GAS, VERIFY THAT PROPER PROCEDURE WAS FOLLOWED (REFER TO INSTALLATION MANUAL), GOOD -> OVERLOADED -> DISCONTINUE TESTING, REDUCE LOADS TO UNIT’S RATED CAPACITY, TEST 12 - CHECK STEPPER MOTOR CONTROL, GOOD -> BAD -> REPAIR OR REPLACE, LOOK FOR A SHORTED CONDITION IN A CONNECTED LOAD OR IN ONE OF THE LOAD CIRCUITS, GOOD -> TEST 7 - CHECK STATOR AC POWER WINDINGS, ENGINE CONDITION GOOD -> REPAIR OR REPLACE, BAD -> TEST 16 - CHECK ENGINE CONDITION, GOOD -> GO TO “PROBLEM 18 - ENGINE STARTS HARD AND RUNS ROUGH/LACKS POWER” SECTION 4.3

Fault codes and symptom→remedy steps extracted from this controller’s service/owner documentation; verify against the official manual before servicing. Aggregated from the service documentation of generator sets built on this controller.