Home› Troubleshooting›Kohler 12TRES

Kohler 12TRES Troubleshooting

Kohler 12TRES troubleshooting: 46 fault codes and 178 symptom-cause-remedy entries from the manufacturer's own service documentation.

Kohler 12TRES — full specs, parts & maintenance.

All Kohler fault codes →

Troubleshooting

224

Fault codes

CodeMeaningCauseRemedy
AFAuxiliary fault input shutdown — Indicates a shutdown initiated by pushing the emergency stop switch. (TRES models only) Not used on RES models.Check the position of the emergency stop button. (TRES models only)
HEHigh engine temperature shutdown — Shutdown occurs if the engine coolant temperature exceeds the maximum temperature for more than 5 seconds. This function becomes active after the engine reaches the crank disconnect speed.Check for blocked air inlets and exhaust outlets.
LOPLow oil pressure shutdown — Shutdown occurs if a low oil pressure condition exists for more than 5 seconds. This function becomes active 30 seconds after the engine has reached crank disconnect speed (30 second inhibit). Note: The low oil pressure shutdown does not protect against low oil level. Check the oil level at the engine.Check for leaks in the lubrication system.; Check the oil level and add oil if the level is low.
OCOvercrank shutdown — Shutdown occurs after 3 unsuccessful starting attempts. The crank cycle is set for three starting attempts of 15 seconds cranking and 15 seconds rest.Check the fuel supply, spark plug, and battery.; Check for loose connections.; Contact an authorized distributor/dealer for service if problem continues.
OCLocked rotor — The generator set also shuts down on OC if no engine rotation is sensed during cranking. Shuts down 3 seconds after the fault is detected.
OFOverfrequency shutdown — Shutdown occurs when the governed frequency exceeds 110% of the system’s frequency setpoint for more than 5 seconds. This function becomes active 10 seconds after engine start (10 second inhibit).Contact an authorized distributor/dealer for service if problem continues.
OSOverspeed shutdown — Shutdown occurs if the engine speed exceeds 110% of the normal running speed for more than 0.3 seconds.Contact an authorized distributor/dealer for service if problem continues.
OUOvervoltage shutdown — Shutdown occurs if the voltage exceeds 120% of the system nominal voltage for more than 2 seconds.Contact an authorized distributor/dealer for service if problem continues.
UFUnderfrequency shutdown — Shutdown occurs if the governed frequency falls below 54 Hz for more than 5 seconds. Shutdown also occurs if the governed frequency falls below 56.5 Hz for more than 60 seconds. This function becomes active 10 seconds after engine start. (10 second inhibit).Reduce the load and restart the generator set.; Contact an authorized distributor/dealer for service if problem continues.
UUUndervoltage shutdown — Shutdown occurs if the voltage falls below 80% of the nominal system voltage for more than 10 seconds.Reduce the load and restart the generator set.; Contact an authorized distributor/dealer for service if problem continues.
HBHigh battery voltage warning — Fault code is displayed if the engine starting battery voltage rises above 16 VDC for more than 30 seconds when the engine is running. Not operative during the engine crank cycle, this fault condition does not inhibit engine starting. The fault condition clears when the battery voltage returns to an acceptable level.Check the battery rating and condition.; Check the battery charger operation.
LBLow battery voltage warning — Fault code is displayed if the engine starting battery voltage falls below 11 VDC for more than 30 seconds when the engine is not running. Not operative during the engine crank cycle, this fault condition does not inhibit engine starting. The fault condition clears when the battery voltage returns to an acceptable level.Check the battery rating and condition.; Check the battery charger operation.; Charge or replace the battery.
Locked rotorThe generator set also shuts down on OC if no engine rotation is sensed during cranking. Shuts down 3 seconds after the fault is detected.
F3Blown fuse F3, controllerReplace fuse; if fuse blows again, check circuit and components.
F2Blown fuse F2, relay interface board (RIB)Replace fuse. If fuse blows again, disconnect the board leads one at a time to identify the cause of the blown fuse: Lead 70A at the fuel valve; Lead IGN at the ignition module; Lead 71A at the starter relay; Leads FP and FN at the rotor. Repair or replace the component causing the blown fuse. If fuse continues to blow and the previous step did not identify the cause, check the continuity of leads FP and FN and the leads from the P14 connector. Replace any bad leads. Use a pin pusher to remove leads from the connector, if necessary. If replacing the leads does not solve the problem, replace the RIB.
F2Blown fuse F2 (ADC-RES)Replace fuse. If fuse blows again, disconnect the leads one at a time to identify the cause of the blown fuse: Lead 70C at the fuel valve; Lead IGN at the ignition module; Lead 71A at the starter relay; Leads FP and FN at the rotor. Repair or replace the component causing the blown fuse. If fuse continues to blow and the previous step did not identify the cause, check the continuity of leads FP and FN and the leads from the P14 connector. Replace any bad leads. Use a pin pusher to remove leads from the connector, if necessary. If replacing the leads does not solve the problem, replace the controller circuit board.
F1Aux. winding fuse F1 blownCheck fuse F1 and replace if blown. If fuse blows again, check stator
K3Flash relay (K3) on RIB (ADC 2100)Check flash LED on RIB; Check fuse F2 and troubleshoot RIB
K3Flash relay (K3) on controller board (ADC-RES)Check fuse F2; Check flash LED1 on controller board. If LED1 indicates power to K3 but relay does not operate, replace controller circuit board
HBHigh battery voltage warning — Fault code is displayed if the engine starting battery voltage rises above 16 VDC for a 12 VDC system or above 30 VDC for a 24 VDC system for more than one minute when the engine is not running. This fault condition does not inhibit engine starting. The fault condition clears when the battery voltage returns to a voltage within the limits for more than 10 seconds.High battery voltageCheck the battery rating and condition; Check the battery charger operation
LBLow battery voltage warning — Fault code is displayed if the engine starting battery voltage falls below 8 VDC for a 12 VDC system or below 16 VDC for a 24 VDC system for more than one minute when the engine is not running. This fault condition does not inhibit engine starting. The fault condition clears when the battery voltage returns to a voltage within the limits for more than 10 seconds.Low battery voltageCheck the battery rating and condition; Check the battery charger operation; Charge or replace the battery
AFAuxiliary fault — Not used on these models.
HEHigh engine temperature — Shutdown occurs if the engine coolant temperature exceeds the maximum temperature for more than 5 seconds. This protective becomes active after the engine reaches crank disconnect speed.High engine temperatureCheck for blocked air inlets and exhaust outlets
LCLLow coolant level — Not used on air-cooled models.
LOCLoss of coolant — Not used on air-cooled models.
LOPLow oil pressure — Shutdown occurs if a low oil pressure condition exists for more than 5 seconds. This protective becomes active 30 seconds after the engine has reached crank disconnect speed (30 second inhibit). Note: The low oil pressure shutdown does not protect against low oil level.Low oil pressureCheck the oil level at the engine; Check for leaks in the lubrication system; Check the oil level and add oil if the level is low; Check low oil pressure switch connections and operation; Check the oil pump and lubrication system
OCOvercrank — Shutdown occurs after 3 unsuccessful starting attempts. The crank cycle is set for three starting attempts of 15 seconds cranking and 15 seconds rest.OvercrankCheck the fuel supply valves and pressure; Check spark plug and battery; See Troubleshooting Chart, generator set cranks but does not start
OCOvercrank — The generator set shuts down on an overcrank fault if no engine rotation is sensed. Shuts down after 3 seconds of cranking or 1 second after the fault is detected.No engine rotation sensedCheck mag pickup connections and operation; Check for a locked rotor
OFOverfrequency — Shutdown occurs when the governed frequency exceeds 110% of the system's frequency setpoint for more than 5 seconds. This protective becomes active 10 seconds after engine start (10 second inhibit).OverfrequencyCheck system frequency setting (parameter UU) on controller; Measure output frequency and adjust, if necessary; Check governor system condition and operation
OSOverspeed — Shutdown occurs if the engine speed exceeds 115% of the normal running speed for more than 0.3 seconds.OverspeedCheck governor settings and operation
OUOvervoltage — Shutdown occurs if the voltage exceeds 120% of the system nominal voltage for more than 2 seconds.OvervoltageCheck AC voltage; Check wiring and connections
UFUnderfrequency — Shutdown occurs when the governed frequency falls below 90% of the nominal system frequency for more than 5 seconds. This protective becomes active 10 seconds after engine start (10 second inhibit).UnderfrequencyReduce the load and restart the generator set
UUUndervoltage — Shutdown occurs if the voltage falls below 80% of the nominal system voltage for more than 10 seconds.UndervoltageReduce the load and restart the generator set; Check wiring and connections; Check controller configuration, system voltage and frequency (parameter UU); Check AC voltage and adjust, if necessary; Replace the SCR module and test voltage again; Separately excite unit; Check stator continuity
SCF0Software Communication Fault 0 — Indicates a software or communication problem within the ADC 2100Software or communication problem within the ADC 2100Replace the controller
AFAuxiliary fault — Indicates a shutdown initiated by the emergency stop switch or a tripped circuit breaker. (TRES models only)Shutdown initiated by the emergency stop switch or a tripped circuit breakerCheck the position of the emergency stop button. (TRES models only)
OCOvercrank — Locked rotor. The generator set shuts down on an overcrank fault if no engine rotation is sensed. Shuts down 3 seconds after the fault is detected.No engine rotation sensedCheck mag pickup connections and operation; Check for a locked rotor
OSOverspeed — Shutdown occurs if the engine speed exceeds 110% of the normal running speed for more than 0.3 seconds.OverspeedCheck governor settings and operation
UFUnderfrequency — Shutdown occurs when the governed frequency falls below 54 Hz for more than 5 seconds. This protective becomes active 10 seconds after engine start. (10 second inhibit).UnderfrequencyReduce the load and restart the generator set
SCF0Software Communication Fault 0 — Indicates a software or communication problem within the ADC-RES.Software or communication problem within the ADC-RESReplace the controller
OFOverfrequency shutdown — Shutdown occurs when the governed frequency exceeds 110% of the system's frequency setpoint for more than 5 seconds. This function becomes active 10 seconds after engine start (10 second inhibit).Contact an authorized distributor/dealer for service if problem continues.
F2The generator set does not crank — Fuse F2 blownFuse F2 blownReplace the fuse. Contact an authorized distributor/dealer for service if fuse blows repeatedly.
F3The generator set does not crank — Fuse F3 blownFuse F3 blownReplace the fuse. Contact an authorized distributor/dealer for service if fuse blows repeatedly.
F1No AC output — Auxiliary winding fuse (F1) blownAuxiliary winding fuse (F1) blownReplace the fuse. Contact an authorized distributor/dealer for service if fuse blows repeatedly.
F3Generator set stops suddenly — Controller fuse (F3) blownController fuse (F3) blownReplace the fuse. If the fuse blows again, contact an authorized distributor/dealer.
F1Generator set stops suddenly — Auxiliary winding fuse (F1) blownAuxiliary winding fuse (F1) blownReplace the fuse. Contact an authorized distributor/dealer for service if fuse blows repeatedly.
F2The battery is discharged, but the charger has power and is operating. — Blown fuse.Blown fuse.Check the 5-amp fuse F2 (5A-T) inside the battery charger and replace if necessary. Check inline fuse F4 and replace if necessary.

Symptoms & remedies

SymptomCauseRemedy
Controller LED display is offNo power to the controller: Controller fuse (F3) is blown.Replace the fuse. If the fuse blows again, contact an authorized distributor/dealer.
Controller LED display is offLow or no battery voltage.Check connections.; Check the engine starting battery and battery charger. See Figure 4-3.
Controller LED display is offGenerator set master switch is in the OFF/RESET position.Move generator set master switch to the AUTO or RUN position. In AUTO, the display will not turn on until the first start command is received.
Controller LED display is offThe controller is in sleep mode. See Section 2.4.2.Controller display will activate when a remote start command is received or the generator set master switch is moved to the RUN position. Use the remote switch to start generator set and activate the controller display, if desired. See Section 2.4.; Controllers with application code version 1.13 or higher can be configured to enable or disable the sleep mode. See the generator set Installation Manual for instructions.
The generator set does not crank.Fault shutdownCheck for a fault code on the controller display. See Section 2.6.
The generator set does not crank.Battery weak or deadCheck power to the battery charger.; Recharge or replace the battery.
The generator set does not crank.Battery charger fuse blownReplace the fuse. Contact an authorized distributor/dealer for service if fuse blows repeatedly.
The generator set does not crank.Battery connections reversed or poorCheck the connections.
The generator set does not crank.Fuse F2 blownReplace the fuse. Contact an authorized distributor/dealer for service if fuse blows repeatedly.
The generator set does not crank.Fuse F3 blownReplace the fuse. Contact an authorized distributor/dealer for service if fuse blows repeatedly.
The generator set does not crank.Generator set master switch in the OFF positionMove the master switch to AUTO for remote start or to RUN for local start.
The generator set cranks but does not start, starts hard, lacks power, or operates erratically.Air cleaner cloggedClean and/or replace the air cleaner.
The generator set cranks but does not start, starts hard, lacks power, or operates erratically.Battery weak or deadCheck power to the battery charger.; Recharge or replace the battery.
The generator set cranks but does not start, starts hard, lacks power, or operates erratically.Battery connection poorClean and tighten the battery connections.
The generator set cranks but does not start, starts hard, lacks power, or operates erratically.Spark plug wire connection looseCheck the spark plug wires.
The generator set cranks but does not start, starts hard, lacks power, or operates erratically.Low oil pressure shutdownCheck the oil level.
The generator set cranks but does not start, starts hard, lacks power, or operates erratically.Fuel pressure insufficientCheck the fuel supply and valves.
The generator set cranks but does not start, starts hard, lacks power, or operates erratically.Engine malfunctionContact an authorized distributor/dealer.
No AC output.AC circuit breaker in the OFF positionPlace the circuit breaker in the ON position.
No AC output.AC circuit breaker tripping because of overloadReduce the load on the generator set.
No AC output.AC circuit breaker tripping because of short circuitContact an authorized distributor/dealer for service.
No AC output.Auxiliary winding fuse (F1) blownReplace the fuse. Contact an authorized distributor/dealer for service if fuse blows repeatedly.
Low output or excessive drop in voltage.Generator set overloadedReduce the load.
Generator set stops suddenly.Low oil pressure shutdownCheck the oil level. Check for signs of oil leaks.
Generator set stops suddenly.Out of fuelCheck fuel supply.
Generator set stops suddenly.Overcrank shutdownReset the controller. If the overcrank fault occurs again, contact an authorized distributor/dealer.
Generator set stops suddenly.Controller fuse (F3) blownReplace the fuse. If the fuse blows again, contact an authorized distributor/dealer.
Generator set stops suddenly.Overspeed shutdownReset the controller. If the overspeed fault occurs again, contact an authorized distributor/dealer.
Generator set stops suddenly.Generator set master switch in the OFF/RESET positionMove the switch to the correct position (RUN or AUTO).
Generator set stops suddenly.Remote stop command received from a remote switch or ATSCheck the remote switch position.
Generator set stops suddenly.Engine malfunctionContact an authorized distributor/dealer.
Generator set stops suddenly.Auxiliary winding fuse (F1) blownReplace the fuse. Contact an authorized distributor/dealer for service if fuse blows repeatedly.
Red LED stays on for more than 24 hoursOne or more inoperative or damaged cells.Load test the battery and replace, if necessary
Red LED stays on for more than 24 hoursBattery charger has reduced its output voltage below the normal level due to a DC overload or a DC short.Remove the source of the overload or short. Disconnect the battery charger’s black (NEGATIVE) ring terminal from the battery. Reapply AC power and the green LED only should now light.
Red LED stays on for more than 24 hoursOnboard DC systems are drawing more current than the battery charger can replace.Turn off all DC equipment while charging.
Red and green LEDs stay on for more than 24 hoursOnboard DC systems are drawing between 1.5 and 5 amps.Turn off all DC equipment while charging.
Red and green LEDs stay on for more than 24 hoursOne or more inoperative or damaged cells.Load test the battery and replace, if necessary
Red and green LEDs stay on for more than 24 hoursExtremely low AC voltage at the battery charger.Apply a higher AC voltage source or reduce the length of the extension cord.
Green LED stays on when the battery is known to be lowOpen DC output fuse.Replace AGS-10 fuse.
Green LED stays on when the battery is known to be lowFaulty or contaminated terminal connections.Clean and tighten or repair all terminal connections.
Green LED stays on when the battery is known to be lowOne or more inoperative or damaged cells.Load test the battery and replace, if necessary.
Neither of the LEDs turn on when the AC power is appliedNo AC power available at the battery charger.Connect AC power or reset the AC breaker on the main panel.
Neither of the LEDs turn on when the AC power is appliedComponent failure.Replace battery charger.
Green LED is off and there is no output voltage.No power to the battery charger.Check the power supply to the charger.; Check the upstream circuit breakers and fuses.; Check fuse FS (1A-T) inside the battery charger.
Abnormal low voltage, charger is operating.The battery completely discharged and the charger is operating at the current limit.Disconnect the battery and verify that the charger output is 13.2 VDC.; Reconnect the charger and allow time for the battery to recharge. The battery voltage should rise gradually.; Test the battery.
The battery is discharged, but the charger has power and is operating.Blown fuse.Check the 5-amp fuse F2 (5A-T) inside the battery charger and replace if necessary.; Check inline fuse F4 and replace if necessary.
Generator set does not crankWeak or dead batteryRecharge or replace battery. If battery is weak or dead, check battery charger fuse, power supply, and operation.
Generator set does not crankBattery connectionsCheck for reversed or poor battery connections.
Generator set does not crankOpen circuit in engine/controller connectionsCheck for loose connections. Check the wire harness continuity.
Generator set does not crankCrank relay on relay interface board (ADC 2100)Check connections to the RIB. Check for 12VDC to the RIB on lead 71N. Check for a good ground connection (lead 16N). Check crank relay K2 operation (LED3). Replace the RIB if relay does not operate.
Generator set does not crankCrank relay K3 on controller circuit board (ADC-RES)Check connections to the controller. Check for a good ground connection. Check LED3 to verify 12 VDC to relay K3. If LED3 is not lit, check for 12 VDC to the board. If LED3 is lit but the relay does not operate, replace the controller circuit board.
Generator set does not crankGenerator set master switchCheck connections to the master switch. Test function of master switch.
Generator set does not crankPoor ground (--) connectionClean and retighten.
Generator set does not crankStarter relayCheck connections to the starter relay. Check continuity of circuit. Check that the starter relay picks up when 12VDC is applied at lead 71A connection.
Generator set does not crankStarterCheck starter connections. Rebuild or replace starter.
Generator set does not crankControllerCheck controller connections and operation. Check for power to the controller. Move generator set master switch to OFF/RESET and then to RUN.
Cranks but does not startNo fuelOpen (turn on) manual fuel valve. Check fuel supply tank (LP).
Cranks but does not startInsufficient fuel pressureCheck fuel pressure to the generator set. Verify adequate fuel pressure and pipe size for the generator set plus all other gas appliances.
Cranks but does not startFuel regulator/valveCheck regulator/valve operation.
Cranks but does not startSpark plugs or spark plug connectionsCheck spark plug wires and connections. Replace or clean and regap spark plugs.
Cranks but does not startLoose connection or open circuitCheck for loose or open connection at the fuel valve (lead 70A) and at the engine spark control module (leads IGN and 70A). Check controller/engine wiring continuity.
Cranks but does not startAir cleaner cloggedClean or replace.
Cranks but does not startMagnetic pickupCheck for 1.75 volts or higher from the magnetic pickup during cranking. A lower signal will cause the stepper motor to open and close during cranking. Measure the resistance across the magnetic pickup according to the procedure in Section 6.9.4. Replace the mag pickup if the resistance is more than 20% higher or lower than the specified value.
Cranks but does not startIncorrect controller configurationCheck for correct controller configuration settings.
Cranks but does not startIgnition system spark control or ignition coilTest and/or replace components.
Cranks but does not startDigital spark advance ignition (DSAI) connections (12kW only)Connect for natural gas. Disconnect for LP. Check for loose connections.
Cranks but does not startNo engine rotation sensed (check for an overcrank fault shutdown)Check mag pickup connections, air gap, resistance, and operation. Check for locked rotor.
Starts hardLow battery voltageCheck battery voltage and battery charger connections, power supply, and operation.
Starts hardAir cleaner cloggedReplace element.
Starts hardFuel mixture adjustment incorrectAdjust fuel valve.
Starts hardDSAI leads incorrectly connected or disconnected (12kW only)Connect for natural gas. Disconnect for LP.
Starts hardSpark plug(s)Replace or regap spark plug(s).
Starts hardSpark plug wire(s)Check spark plug wires and connections. Replace spark plug wires.
Starts hardIgnition components (spark control or ignition module)Test/replace ignition components.
Starts hardInsufficient fuel pressureCheck fuel pressure.
Starts hardWorn piston rings, valvesCheck compression.
Starts but shuts downFault shutdownCheck for a fault shutdown code on the controller’s LED display. Correct the fault and then move the generator set master switch to OFF/RESET to reset the controller.
Stops suddenlyFault shutdownCheck for a fault shutdown code on the controller’s LED display. Correct the fault and then move the generator set master switch to OFF/RESET to reset the controller.
Stops suddenlyNo fuelTurn on fuel supply.
Stops suddenlyFuel line restrictionInspect fuel lines.
Stops suddenlyFuel lines too longCheck fuel line length.
Stops suddenlyAir cleaner cloggedReplace element.
Stops suddenlyBlown fuseCheck fuses F1, F2 and F3. Replace any blown fuses. If fuse blows again, test generator components.
Stops suddenlySpark plug(s)Replace and regap plug(s).
Stops suddenlyEngine overheated (hot engine only)Check air intake, fuel adjustment, oil level, air inlet/outlet.
Stops suddenlyLow oil pressure (LOP) switchAttempt startup. If unit shuts down, remove lead from LOP switch and reset controller. A successful restart attempt indicates a faulty LOP shutdown switch. Note: Check engine oil pressure before performing test and/or replacing LOP shutdown switch.
Stops suddenlyFuel valve/fuel regulatorCheck regulator/valve operation.
Stops suddenlyEngine overloadedReduce electrical load.
Stops suddenlyLoss of generator output voltage to controllerCheck connections at P15 plug. Check continuity of AC sensing leads 11 and 44.
Stops suddenlyMagnetic pickup connectionsCheck for loose connections to the mag pickup.
Stops suddenlyIgnition moduleTest and/or replace.
Stops suddenlyK3 (flash) relay on RIB (ADC 2100)Check for Flash LED illumination. Check fuse F2. Replace relay board.
Stops suddenlyK3 (flash) relay on controller board (ADC-RES)Check for Flash LED1 illumination. Check fuse F2. If LED1 is lit but relay does not operate, replace controller board.
Operates erraticallyAir cleaner cloggedReplace element.
Operates erraticallySpark plug(s)Replace and regap plugs.
Operates erraticallySpark plug wire(s)Replace spark plug wires.
Operates erraticallyDSAI leads incorrectly connected or disconnected (12kW only)Connect for natural gas. Disconnect for LP.
Operates erraticallyFuel line restrictionCheck fuel lines.
Operates erraticallyFuel mixture adjustment incorrectCheck and/or adjust.
Operates erraticallyMagnetic pickup connectionsCheck for loose connections to the mag pickup.
Operates erraticallyGovernor adjustment incorrectAdjust governor stability.
Operates erraticallyIgnition systemTest and/or replace components.
Operates erraticallyInadequate cooling (hot engine only)Inspect air inlet and outlet.
Operates erraticallyCarbon buildup in engineClean cylinder head.
Operates erraticallyEngine valves not seating correctlyCheck cylinder pressures with leakdown test. Inspect valves and valve seats.
Lacks powerAir intake restriction, inadequate coolingInspect air intakes and exhaust for obstructions. Check air cleaner.
Lacks powerGenerator overloadedReduce load.
Lacks powerSpark plug(s)Replace and regap plug(s).
Lacks powerSpark plug wire(s)Replace spark plug wires.
Lacks powerDSAI leads incorrectly connected or disconnected (12kW only)Connect for natural gas. Disconnect for LP.
Lacks powerInsufficient fuel pressureCheck fuel pressure at carburetor outlet.
Lacks powerFuel line restrictionCheck fuel pipe size.
Lacks powerFuel regulatorCheck function of fuel regulator.
Lacks power — Engine not running at rated rpmEngine not running at rated rpmCheck controller settings for unit configuration (UC) and engine type (EC); Adjust governor speed
Lacks power — Engine power lossEngine power lossRefer to the engine service manual for troubleshooting and repair instructions
Lacks power — Governor malfunction or misadjustmentGovernor malfunction or misadjustmentTest/readjust governor
Lacks power — Ignition systemIgnition systemTest and/or replace
Lacks power — OverheatsInadequate coolingInspect cooling system for air intake obstructions
Lacks power — OverheatsFuel mixture adjustment incorrectReadjust fuel mixture. Note: Adjusting the fuel mixture may void the emission certification
Low output or excessive drop in voltage — Generator overloadedGenerator overloadedReduce load
Low output or excessive drop in voltage — Incorrect controller configurationIncorrect controller configurationCheck and adjust the controller configuration parameters
Low output or excessive drop in voltage — Incorrect controller voltage settingsIncorrect controller voltage settingsCheck and adjust the controller voltage settings
Low output or excessive drop in voltage — Alternator or control systemAlternator or control systemPerform separate excitation procedure to isolate problem to the alternator or the control system
Low output or excessive drop in voltage — SCR moduleSCR moduleCheck wiring and connections to the SCR module; Check auxiliary winding fuse F1; Replace SCR module and test voltage
Low output or excessive drop in voltage — ControllerControllerCheck controller settings. Check controller fuse, wiring and connections; Before replacing controller, replace SCR module and test voltage
Low output or excessive drop in voltage — Rotor (open, grounded, or shorted windings)Rotor (open, grounded, or shorted windings)Test and/or replace
Low output or excessive drop in voltage — Stator (open, grounded, or shorted windings)Stator (open, grounded, or shorted windings)Test and/or replace
Low output or excessive drop in voltage — Brush connectionBrush connectionCheck for loose brush connections; Check the resistance through the brushes. Resistance through the brushes should be low, 0.1--0.2 ohms without meter lead resistance
Low output or excessive drop in voltage — Low engine speed causing voltage roll-offLow engine speed causing voltage roll-offCheck system voltage/frequency (Uu) and engine type (Ec) parameters; Adjust engine governor speed; Troubleshoot engine
Light flicker — Voltage stability (gain) settingVoltage stability (gain) settingCheck and adjust the voltage stability (gain) setting using the controller keypad
High output voltage — Incorrect controller configurationIncorrect controller configurationCheck and adjust the controller configuration parameters
High output voltage — Incorrect controller voltage settingsIncorrect controller voltage settingsCheck and adjust the controller voltage settings
High output voltage — Engine speed too highEngine speed too highCheck engine speed using tachometer or frequency meter; Adjust governor as necessary
High output voltage — Loose voltage sensing connectionsLoose voltage sensing connectionsCheck connections: stator leads 11 and 44 and P15 controller connection
High output voltage — SCR moduleSCR moduleCheck wiring and connections to the SCR module; Check auxiliary winding fuse F1 (lead 55); Replace SCR module and recheck voltage
High output voltage — ControllerControllerCheck fuses, wiring and connections. Before replacing controller, replace SCR module and test voltage
No output voltage — AC output circuit breaker openAC output circuit breaker openCheck for AC voltage on the generator side of circuit breaker. If there is AC voltage on the generator side of the breaker, then a problem in the load circuits is causing the line circuit breaker to trip. Check for and correct short circuits or overloading on the load side before resetting the circuit breaker
No output voltage — Alternator or control systemAlternator or control systemPerform separate excitation procedure to isolate the problem to the alternator or the control system. Then troubleshoot the alternator or control system components as follows
No output voltage — SCR moduleSCR moduleCheck auxiliary winding fuse F1; Replace SCR module and test voltage
No output voltage — ControllerControllerCheck controller settings. Check wiring and connections. Before replacing controller, replace SCR module and check voltage
No output voltage — Open wiring, terminal, or pin in buildup circuit or SCR module circuitOpen wiring, terminal, or pin in buildup circuit or SCR module circuitCheck continuity
No output voltage — BrushesBrushesInspect brushes and replace if worn; Check for brushes sticking in brush holder or broken brush spring
No output voltage — Rotor connectionsRotor connectionsCheck for open circuit in rotor connection circuit (leads FN and FP to SCR and RIB)
No output voltage — Rotor slip rings dirty or corrodedRotor slip rings dirty or corrodedCheck slip ring condition
No output voltage — Rotor (open, grounded, or shorted windings)Rotor (open, grounded, or shorted windings)Check voltage and continuity
No output voltage — Stator (open, grounded, or shorted windings)Stator (open, grounded, or shorted windings)Check voltage and continuity
Noisy operation — Exhaust system leaksExhaust system leaksCheck and replace as necessary
Noisy operation — Engine not running smoothlyEngine not running smoothlySee Generator set operates erratically in this table
Noisy operation — Broken or damaged vibromount(s)Broken or damaged vibromount(s)Check and replace as necessary
Noisy operation — Loose or vibrating sheet metal/housingLoose or vibrating sheet metal/housingRetighten screws, replace rivets
Noisy operation — Exhaust piping or air inlets/outlets not securely installedExhaust piping or air inlets/outlets not securely installedInspect for loose parts and secure if necessary
Noisy operation — Excessive engine/generator vibrationExcessive engine/generator vibrationCheck, rotor, crankshaft, bearing, etc. (disassembly of engine and/or alternator may be required)
Controller troubleshooting — ControllerControllerCheck controller settings; Adjust controller settings as required; Check for power to the controller at lead PF1; Check/replace fuse F3. Check battery; Check controller fuse F3; Replace controller fuse; Check controller wiring and connections; Tighten connections and/or replace wiring; Replace SCR module and recheck voltage; Replace the SCR module; Perform all tests listed under high output voltage; Replace the controller only if previous steps do not solve the problem
Controller troubleshooting — SCR moduleSCR moduleCheck wiring and connections to the SCR module; Tighten connections and/or replace wiring to the SCR module; Test the SCR module using the procedure in Section 6.8; Replace the SCR module and recheck voltage; Check auxiliary winding fuse F1 (lead 55); Replace auxiliary winding fuse F1 (lead 55)
Controller LED display is offThe controller is in sleep mode. See Section 2.5.2.Controller display will activate when a remote start command is received or the generator set master switch is moved to the RUN position. Use the remote switch to start generator set and activate the controller display, if desired. See Section 2.5.; Controllers with application code version 1.13 or higher can be configured to enable or disable the sleep mode. See the generator set Installation Manual for instructions.
The generator set does not crankFault shutdownCheck for a fault code on the controller display. See Section 2.7.
The generator set does not crankBattery weak or deadCheck power to the battery charger; Recharge or replace the battery.
The generator set does not crankBattery charger fuse blownReplace the fuse. Contact an authorized distributor/dealer for service if fuse blows repeatedly.
The generator set does not crankBattery connections reversed or poorCheck the connections.
The generator set does not crankGenerator set master switch in the OFF positionMove the master switch to AUTO for remote start or to RUN for local start.
The generator set cranks but does not start, starts hard, lacks power, or operates erraticallyAir cleaner cloggedClean and/or replace the air cleaner.
The generator set cranks but does not start, starts hard, lacks power, or operates erraticallyBattery weak or deadCheck power to the battery charger; Recharge or replace the battery.
The generator set cranks but does not start, starts hard, lacks power, or operates erraticallyBattery connection poorClean and tighten the battery connections.
The generator set cranks but does not start, starts hard, lacks power, or operates erraticallySpark plug wire connection looseCheck the spark plug wires.
The generator set cranks but does not start, starts hard, lacks power, or operates erraticallyLow oil pressure shutdownCheck the oil level.
The generator set cranks but does not start, starts hard, lacks power, or operates erraticallyFuel pressure insufficientCheck the fuel supply and valves.
The generator set cranks but does not start, starts hard, lacks power, or operates erraticallyEngine malfunctionContact an authorized distributor/dealer.
No AC outputAC circuit breaker in the OFF positionPlace the circuit breaker in the ON position.
No AC outputAC circuit breaker tripping because of overloadReduce the load on the generator set.
No AC outputAC circuit breaker tripping because of short circuitContact an authorized distributor/dealer for service.
Low output or excessive drop in voltageGenerator set overloadedReduce the load.
Generator set stops suddenlyLow oil pressure shutdownCheck the oil level. Check for signs of oil leaks.
Generator set stops suddenlyOut of fuelCheck fuel supply.
Generator set stops suddenlyOvercrank shutdownReset the controller. If the overcrank fault occurs again, contact an authorized distributor/dealer.
Generator set stops suddenlyOverspeed shutdownReset the controller. If the overspeed fault occurs again, contact an authorized distributor/dealer.
Generator set stops suddenlyGenerator set master switch in the OFF/RESET positionMove the switch to the correct position (RUN or AUTO).
Generator set stops suddenlyRemote stop command received from a remote switch or ATSCheck the remote switch position.
Generator set stops suddenlyEngine malfunctionContact an authorized distributor/dealer.

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.

Common questions

Kohler 12TRES: Generator set stops suddenly — what causes it?

Documented causes: Low oil pressure shutdown; Out of fuel; Overcrank shutdown; Controller fuse (F3) blown. See the table for the matching fixes.

Kohler 12TRES: Stops suddenly — what causes it?

Documented causes: Fault shutdown; No fuel; Fuel line restriction; Fuel lines too long. See the table for the matching fixes.

Kohler 12TRES: The generator set cranks but does not start, starts hard, lacks power, or operates erratically — what causes it?

Documented causes: Air cleaner clogged; Battery weak or dead; Battery connection poor; Spark plug wire connection loose. See the table for the matching fixes.