Home› Troubleshooting›Generac NP-30G

Generac NP-30G Troubleshooting

Generac NP-30G troubleshooting: 11 fault codes and 142 symptom-cause-remedy entries from the manufacturer's own service documentation.

Generac NP-30G — full specs, parts & maintenance.

All Generac fault codes →

Troubleshooting

153

Fault codes

CodeMeaningRemedy
QAW WARNING
M01Low Oil Pressure ShutdownCheck the engine oil level. If necessary, add oil to the FULL mark.
M02High Temperature Shutdown
M03Overspeed ShutdownDo not attempt a manual adjustment to control engine speed.
M04Low Voltage Shutdown
C1Low Oil Pressure ShutdownCheck the engine oil level.
T1High Temperature Shutdown
S1Overspeed ShutdownDo not attempt a manual adjustment to control the engine speed.
V1Low Voltage Shutdown
C2High Temperature Shutdown
C4Low Voltage ShutdownDisconnect all loads the generator might power by whatever means provided, such as the recreational vehicle’s main circuit breaker.

Symptoms & remedies

SymptomCauseRemedy
Engine won't crank15 amp fuse is blownReplace 15 amp fuse
Engine won't crankLoose corroded or defective battery cablesTighten, clean or replace as necessary
Engine won't crankDefective engine Start/Stop switchReplace Start/Stop switch
Engine won't crankDefective starter contactorReplace contactor
Engine won't crankDefective starter motorReplace starter motor
Engine won't crankLow or defective batteryChange or replace battery
Engine cranks but won't startOut of fuelReplenish fuel
Engine cranks but won't startFuel pump is defectiveReplace fuel pump
Engine cranks but won't startOpen Wire #14 from Eng. Control Bd.Reconnect wire
Engine cranks but won't startEngine is floodedWait 5-10 min. before trying
Engine cranks but won't startSpark plug defectiveClean, regap or replace plug
Engine starts hard, runs rough, low full load powerAir cleaner plugged or damagedClean or replace as needed
Engine starts hard, runs rough, low full load powerDefective spark plugClean, regap or replace plug
Engine starts hard, runs rough, low full load powerLoose spark plug bootPress boot on securely
Engine starts, shuts down when Start/Stop switch is releasedEngine oil is lowCheck oil; add as needed
Engine starts, shuts down when Start/Stop switch is releasedEngine is overheatedCheck for adequate ventilation
Engine starts, shuts down when Start/Stop switch is releasedDefective Low Oil Pressure SystemHave serviced/replaced
Engine starts, shuts down when Start/Stop switch is releasedDefective Engine Control BoardHave board serviced/replaced
Engine starts, shuts down when Start/Stop switch is releasedDefective Computer Control BoardHave board serviced/replaced
Start/Stop switch at Stop, engine continues to runDefective Start/Stop switchReplace switch
Start/Stop switch at Stop, engine continues to runOpen/disconn
No AC voltage can be measured across Stator connections at the Battery Charge Rectifier (BCR)An open circuit condition probably exists in Wire 66 (Brown), or Wire 77 (Brown)
AC voltage is available to the Wire 66 and 77 terminals at the Battery Charge Rectifier, but no voltage or a low voltage is measured between the BCR's Wire 55 terminal and groundThe Battery Charge Rectifier (BCR) is defective
No AC voltage is measured at the Wires 66 and 77 terminals of the Battery Charge Rectifier, with the unit runningAn open circuit exists in the wire 66 or 77 circuit
AC voltage was present at the Wires 66 and 77 terminals of the Battery Charge Rectifier, but DC voltage is NOT present between the Battery Charge Rectifier's Wire 55 and frame groundThe Battery Charge Rectifier (BCR) is defective
The engine starts, but the Stepper Motor does not move, and engine shuts down after several secondsThe CCG circuit board's micro-controller may not be operating
Engine starts, but Stepper Motor does not move. The engine accelerates uncontrollably and shuts down when engine speed exceeds 4500 rpmA failure of the circuit board's Stepper Motor drive
Engine starts, but Stepper Motor does not move. Engine appears to operate too slowly; Engine is not able to handle the load and unit operates at low AC output voltage; After several seconds under load, AC output voltage is turned off (overload condition)A failure of the circuit board's Stepper Motor drive
The engine can be started, but shuts down after several secondsA timing detection failure may have occured (Timing winding, Wires TIM1, TIM2)
The engine speed and output voltage are erratic under constant load, but the AC output does not turn off intermittentlyErratic timing detection may have occured (Timing winding, Wires TIM1, TIM2)
Premature high temperature shutdownsSome early production units were equipped with a 265° F. switchThe 265° F. switch should be removed and replaced with the Part No. 94090 switch
Engine starts, accelerates, shuts down at 4500 rpmCarburetor linkage sticking with throttle stuck openRepair sticking throttle
Engine starts, accelerates, shuts down at 4500 rpmStepper Motor failed or seizedReplace Stepper Motor
Engine starts, accelerates, shuts down at 4500 rpmStepper Motor wire connections broken or disconnectedReconnect or repair
Engine starts, accelerates, shuts down at 4500 rpmStepper Motor not properly connectedReconnect wires
Overvoltage condition and speed control system cannot reduce output voltageCarburetor linkage sticking with throttle stuck partly openRepair sticking throttle
Overvoltage condition and speed control system cannot reduce output voltageStepper Motor failed or seizedReplace Stepper Motor
Overvoltage condition and speed control system cannot reduce output voltageConnection to Stepper Motor is broken/disconnected with throttle openRepair or replace connections
Overvoltage condition and speed control system cannot reduce output voltageStepper Motor not properly connectedReconnect Stepper Motor wires
Engine speed is maintained and no-load voltage is good. However, when load is applied output voltage drops and engine shuts downCarburetor linkage sticking with throttle partly openRepair sticking throttle
Engine speed is maintained and no-load voltage is good. However, when load is applied output voltage drops and engine shuts downStepper Motor failed or seizedReplace Stepper Motor
Engine speed is maintained and no-load voltage is good. However, when load is applied output voltage drops and engine shuts downConnection to Stepper Motor broken or disconnectedRepair or replace connections
Engine speed is maintained and no-load voltage is good. However, when load is applied output voltage drops and engine shuts downStepper Motor not properly connectedReconnect Stepper Motor
Engine does not accelerate when load is applied. After 10 seconds, engine shuts downCarburetor linkage sticking with throttle stuck closedRepair sticking throttle
Engine does not accelerate when load is applied. After 10 seconds, engine shuts downStepper Motor failed or seizedReplace Stepper Motor
Engine does not accelerate when load is applied. After 10 seconds, engine shuts downStepper Motor not properly connectedReconnect Stepper Motor
Engine speed and AC output voltage erratic under constant load. AC output does not turn off intermittentlyStepper Motor failureReplace Stepper Motor
Engine speed and AC output voltage erratic under constant load. AC output does not turn off intermittentlyConnection to Stepper Motor broken or disconnectedRepair or replace connections
Engine speed and AC output voltage erratic under constant load. AC output does not turn off intermittentlyStepper Motor not properly connectedReconnect Stepper Motor
Engine speed and AC output voltage erratic under constant load. AC output does not turn off intermittentlyCCG board failure (erratic detection of "zero voltage" crossings)Replace CCG Circuit Board
Engine starts but Stepper Motor does not move. Shut down occurs after several secondsPower Supply winding (PS1, PS2) is openRepair or replace bad wire(s) PS1/PS2 or replace Stator
Engine starts but Stepper Motor does not move. Shut down occurs after several secondsStator Timing winding is openRepair/replace bad wire(s) TIM1/TIM2 or replace Stator
Engine starts but Stepper Motor does not move. Shut down occurs after several secondsPower supply winding in Stator shorted to groundReplace Stator
Engine starts but Stepper Motor does not move. Shut down occurs after several secondsTiming winding in Stator shorted to groundReplace Stator
Engine starts but Stepper Motor does not move. Shut down occurs after several secondsCCG board does not detect "Zero Voltage" crossingsReplace CCG circuit board
Engine shuts down but overspeed above 4500 rpm did not occurOne of four power windings in Stator is openRepair/replace bad wire(s) AC1/AC2 or SL1/SL2 or replace Stator
Engine shuts down but overspeed above 4500 rpm did not occurMain windings shorted to groundReplace Stator
Engine shuts down but overspeed above 4500 rpm did not occurBad switch in GenistorReplace Genistor
Engine shuts down but overspeed above 4500 rpm did not occurNo gate connection between CCG board and GenistorRepair/replace bad wire(s) or replace bad CCG circuit board
Engine shuts down but overspeed above 4500 rpm did not occurNo connection between Genistor and Stator (AC1, AC2, SL1, SL2)Repair or replace connecting wire(s)
Engine shuts down but overspeed above 4500 rpm did not occurCCG board failureReplace CCG circuit board
AC output turns off intermittently. Then, engine runs at idle for 5 seconds. Finally, AC turns back on and unit runs normallyCCG board failureReplace CCG circuit board
Under heavy load, output turns off and engine speed drops to idleCCG circuit board failureReplace CCG circuit board
Engine cranks but won't startLoss of DC power supply from the Engine Controller circuit board to the Ignition Module via Wire 14Inspect the Wire 14 connections at the 4-tab connector; check Wire 14; if DC voltage is NOT indicated, go to Test 21; if DC voltage is good, go on to Test 18
Engine cranks but won't startA failure in the Engine Controller circuit board has occured and DC power is not being delivered to the Wire 14 circuitIf DC voltage was NOT indicated in Test 17, but IS indicated now, repair, reconnect or replace Wire 14 between board and Ignition Module; if no DC voltage in Test 3 but good voltage now, replace Wire 14 between board and fuel pump; if there is no DC output from the circuit board to Wire 14, replace the Engine Controller circuit board
Engine won't start or starts hard and runs roughCarburetionMake sure the fuel tank has an ample supply of clean fresh gasoline (gasoline fuel systems) or gaseous fuel; make sure all shutoff valves are open; adjust the carburetor as outlined on Page 3.4-2; make sure the automatic choke is working properly and that the choke closes completely; adjust or repair carburetor or fuel system as necessary
Engine will not start, spark plug is WETOverchoking; Water in fuel; Excessively rich fuel mixture; Intake valve stuck openAdjust or repair carburetor or fuel system as necessary
Engine will not start, spark plug is DRYCarburetor gasket(s) leaking; Fuel line plugged or shutoff valve not opening; Intake valve stuck closed; Inoperative fuel pump; Clogged fuel filterAdjust or repair carburetor or fuel system as necessary
Engine will not start or starts hard and runs roughA failure in the engine's mechanical systemPerform a compression check; if compression is poor, look for one or more of the following possible causes: Loose cylinder head bolts; Failed cylinder head gasket; Burned valves or valve seals; Insufficient valve clearance; Warped cylinder head; Warped valve stem; Worn or broken piston ring(s); Worn or damaged cylinder bore; Broken connecting rod
Engine starts, but then shuts down after startupA problem could exist in either the generator computer system or in the engine DC control systemIsolate the CCG system using the test fixture; if the engine starts and shuts down, check engine oil level (if oil level is low, replenish as necessary; if oil level is NOT low, go to Test 26); if engine was shutting down after startup, but does not shut down during this test, the problem is in the CCG system, go to Test 27
Engine starts, but then shuts down after startupLow engine oil levelReplenish as necessary
Engine starts, but then shuts down after startupOil pressure switchReplace oil pressure switch if it is bad
AC voltage was present at the Wires 66 and 77 terminals, but DC voltage is NOT present between the Battery Charge Rectifier's Wire 55 and frame groundThe Battery Charge Rectifier (BCR) is defective
Engine starts, but the Stepper Motor does not move, and engine shuts down after several secondsThe CCG circuit board's micro-controller may not be operating
Engine can be started, but shuts down after several secondsA timing detection failure may have occurred (Timing winding, Wires TIM1, TIM2)
Engine speed and output voltage are erratic under constant load, but the AC output does not turn off intermittentlyErratic timing detection may have occurred (Timing winding, Wires TIM1, TIM2)
Engine cranks but won't startA failure in the Engine Controller circuit board has occurred and DC power is not being delivered to the Wire 14 circuitIf DC voltage was NOT indicated in Test 17, but IS indicated now, repair, reconnect or replace Wire 14 between board and Ignition Module; if no DC voltage in Test 3 but good voltage now, replace Wire 14 between board and fuel pump; if there is no DC output from the circuit board to Wire 14, replace the Engine Controller circuit board
Engine will not start, spark plug is WETOverchokingAdjust or repair carburetor or fuel system as necessary
Engine will not start, spark plug is WETWater in fuelAdjust or repair carburetor or fuel system as necessary
Engine will not start, spark plug is WETExcessively rich fuel mixtureAdjust or repair carburetor or fuel system as necessary
Engine will not start, spark plug is WETIntake valve stuck openAdjust or repair carburetor or fuel system as necessary
Engine will not start, spark plug is DRYCarburetor gasket(s) leakingAdjust or repair carburetor or fuel system as necessary
Engine will not start, spark plug is DRYFuel line plugged or shutoff valve not openingAdjust or repair carburetor or fuel system as necessary
Engine will not start, spark plug is DRYIntake valve stuck closedAdjust or repair carburetor or fuel system as necessary
Engine will not start, spark plug is DRYInoperative fuel pumpAdjust or repair carburetor or fuel system as necessary
Engine will not start, spark plug is DRYClogged fuel filterAdjust or repair carburetor or fuel system as necessary
Premature high temperature shutdownsEarly production units were equipped with a 265° F. switchThe 265° F. switch should be removed and replaced with the Part No. 94090 switch
Engine speed is maintained and no-load voltage is good. However, when load is applied output voltage drops and engine shuts downConnections to Stepper Motor broken or disconnectedRepair or replace connections
Engine starts but Stepper Motor does not move. Shut down occurs after several secondsPower supply winding in Stator shorted to ground (See NOTE 1)Replace Stator
Priming function does not work15 amp fuse is badReplace bad fuse
Priming function does not workNo power to switch or low powerCheck battery and battery circuit (Wires 13 and 15); recharge or replace battery as required; repair or replace loose, corroded or bad battery cables or wires as necessary
Priming function does not workFuel pump does not workReplace pump if bad
Priming function does not workDefective wire 14ARepair or replace defective wire 14A
Priming function does not workDefective primer switchReplace switch if defective
Engine will not crank15 amp fuse badReplace bad fuse
Engine will not crankLow or no battery powerRecharge or replace battery; repair or replace bad cable(s)
Engine will not crankStarter contactor badReplace starter contactor
Engine will not crankStarter motor badReplace starter
Engine will not crankEngine Controller board power supply badReplace Engine Controller circuit board
Engine will not crankStart-stop switch badReplace bad switch or bad wire 17 or bad ground wire as necessary
Engine cranks but will not startLow fuel levelReplenish fuel supply
Engine cranks but will not startFuel filter badReplace filter
Engine won't start or starts hard and runs roughCarburetion problemAdjust or repair carburetor or fuel system as necessary
Engine will not start (spark plug WET)OverchokingAdjust or repair carburetor or fuel system as necessary
Engine will not start (spark plug WET)Water in fuelAdjust or repair carburetor or fuel system as necessary
Engine will not start (spark plug WET)Excessively rich fuel mixtureAdjust or repair carburetor or fuel system as necessary
Engine will not start (spark plug WET)Intake valve stuck openAdjust or repair carburetor or fuel system as necessary
Engine will not start (spark plug DRY)Carburetor gasket(s) leakingAdjust or repair carburetor or fuel system as necessary
Engine will not start (spark plug DRY)Fuel line plugged or shutoff valve not openingAdjust or repair carburetor or fuel system as necessary
Engine will not start (spark plug DRY)Intake valve stuck closedAdjust or repair carburetor or fuel system as necessary
Engine will not start (spark plug DRY)Inoperative fuel pumpAdjust or repair carburetor or fuel system as necessary
Engine will not start (spark plug DRY)Clogged fuel filterAdjust or repair carburetor or fuel system as necessary
Engine will not start or starts hard and runs rough (poor compression)Loose cylinder head bolts
Engine will not start or starts hard and runs rough (poor compression)Failed cylinder head gasket
Engine will not start or starts hard and runs rough (poor compression)Burned valves or valve seals
Engine will not start or starts hard and runs rough (poor compression)Insufficient valve clearance
Engine will not start or starts hard and runs rough (poor compression)Warped cylinder head
Engine will not start or starts hard and runs rough (poor compression)Warped valve stem
Engine will not start or starts hard and runs rough (poor compression)Worn or broken piston ring(s)
Engine will not start or starts hard and runs rough (poor compression)Worn or damaged cylinder bore
Engine will not start or starts hard and runs rough (poor compression)Broken connecting rod
Engine starts, but then shuts down after startupProblem in the generator computer system (CCG system)Go to Test 27
Engine starts, but then shuts down after startupDefective oil pressure switch or bad Wire 85 circuitReplace oil pressure switch if defective or repair Wire 85 circuit as necessary
Engine starts, but then shuts down after startupOil pressure actually lowSee Section 5.1, "ENGINE OIL SYSTEM"
Engine starts, but Stepper Motor does not move, and engine shuts down after several secondsCCG circuit board's micro-controller may not be operating
Engine starts, but Stepper Motor does not move. The engine accelerates uncontrollably and shuts down when engine speed exceeds 4500 rpmFailure of the circuit board's Stepper Motor drive
Engine starts, but Stepper Motor does not move. Engine appears to operate too slowly; engine is not able to handle the load and unit operates at low AC output voltage; after several seconds under load, AC output voltage is turned off (overload condition)Failure of the circuit board's Stepper Motor drive
Engine can be started, but shuts down after several secondsTiming detection failure (Timing winding, Wires TIM1, TIM2)
Engine speed and output voltage are erratic under constant load, but the AC output does not turn off intermittentlyErratic timing detection (Timing winding, Wires TIM1, TIM2)
No AC voltage can be measured across Stator connections at the Battery Charge Rectifier (BCR)Open circuit condition in Wire 66 (Brown) or Wire 77 (Brown)
AC voltage is available to the Wire 66 and 77 terminals at the Battery Charge Rectifier, but no voltage or a low voltage is measured between the BCR's Wire 55 terminal and groundBattery Charge Rectifier (BCR) is defectiveReplace Battery Charge Rectifier
No AC voltage measured at Wires 66 and 77 terminals of the Battery Charge Rectifier with unit runningOpen circuit exists in the wire 66 or 77 circuit
AC voltage present at Wires 66 and 77 but DC voltage NOT present between Battery Charge Rectifier Wire 55 and frame groundBattery Charge Rectifier (BCR) is defectiveReplace Battery Charge Rectifier
Genistor fails resistance/continuity testsGenistor defectiveReplace Genistor
Battery charge winding resistance not within specification (Wires 66 to 55 = 0.037-0.042 Ohm; Wires 77 to 55 = 0.037-0.042 Ohm)Stator Assembly defectiveReplace Stator Assembly
Problem in AC generator system when other components tested goodCCG circuit boardReplace the CCG circuit board and check unit operation
Engine shutdown initiated by CCG boardOver-voltage
Engine shutdown initiated by CCG boardUndervoltage (or overload)
Engine shutdown initiated by CCG boardOverspeed above 4500 rpm
Engine shutdown initiated by CCG boardZero current failure
Engine shutdown initiated by CCG boardConverter failure
Engine shutdown initiated by CCG boardMicroprocessor failure

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.

Common questions

Generac NP-30G: Engine will not start or starts hard and runs rough (poor compression) — what causes it?

Documented causes: Loose cylinder head bolts; Failed cylinder head gasket; Burned valves or valve seals; Insufficient valve clearance. See the table for the matching fixes.

Generac NP-30G: Engine cranks but won't start — what causes it?

Documented causes: Out of fuel; Fuel pump is defective; Open Wire #14 from Eng. Control Bd.; Engine is flooded. See the table for the matching fixes.

Generac NP-30G: Engine won't crank — what causes it?

Documented causes: 15 amp fuse is blown; Loose corroded or defective battery cables; Defective engine Start/Stop switch; Defective starter contactor. See the table for the matching fixes.