Home›Repair guides›Magnum›Manual Starting of the Generator

Magnum — Manual Starting of the Generator

Operation

From a Magnum operator's manual covering: MMG320, MMG320 Super Start, MMG405, MMG405 Super Start, MMG465. Check it applies to your exact model before use.

Applies to: Magnum MMG320, Magnum MMG320 Super Start, Magnum MMG405, Magnum MMG405 Super Start, Magnum MMG465, John Deere RG6090HF485 engine, John Deere RG6135HF485 engine

Before you start

  • CARBON MONOXIDE: USING A GENERATOR INDOORS CAN KILL YOU IN MINUTES!

Procedure

  1. Move the control ON/OFF toggle switch to the CONTROL ON/I position.
  2. LCD window indicates MAN mode and Ready; Ready/Manual LED is lit.
  3. Press the green ENGINE START button.
  4. Prestart (Preheat) screen is displayed with a countdown from 20 seconds to zero.
  5. Starting screen is displayed; the engine cranks and starts running.
  6. Running screen displays.
  7. LCD toggles between Generator Display Screen and Engine Display Screen.
  8. If engine does not start, controller pauses 15 seconds and makes two more attempts (three total).
  9. If no start after three cycles, LCD shows SD Start Fail; wait two minutes and press FAULT RESET.
  10. Engine speeds up to a constant 1800 rpm.
  11. Check for excessive noise or vibration and coolant, oil or fuel leaks before applying loads.
  12. Check AC output voltage; fine adjust with the fine voltage adjustment screw if needed.
  13. Check frequency reads approximately 60 Hz with no loads.
  14. Switch main circuit breaker ON, then convenience outlet breakers as needed.

Specs & values

  • 1800 rpm
  • 60 Hz

Full service-parts list: Magnum MMG320 →

Source: Magnum operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.