Magnum MMG320 Generator Set

The Magnum MMG320 is a 278 kW (348 kVA) Diesel standby generator set powered by a John Deere 6090HF485 engine. It is available at 480 V, 3-phase, 60 Hz and rated 334.4 A. It holds about 34 L (9.0 gal) of oil and 70.9 L (18.7 gal) of coolant, with a maximum ambient rating of 120 °C. Starting uses 2 group-31 batteries rated 1000 CCA at 12 V. The set measures 3960×1520×2290 mm (155.9×59.8×90.2 in), weighs about 3646 kg (8038 lb) and produces 68 dBA at 23 m. An integrated tank holds 1738 L (459.1 gal), roughly 24 hours of runtime. The same 6090HF485 engine also powers generator sets from John Deere.

278 kW
Standby
9.0 L
Displacement
34.0 L
Oil capacity
3
Document types

Typical fuel consumption for 275–280 kW Diesel generators →

Compare with other 275–280 kW Diesel generators →

Service parts for the MMG320

Grouped by system, with how many of each the parts manual calls for.

Oil system

1 required

Prices captured from merchant listings; some links are affiliate links. Confirm against your serial number before ordering.

Specifications

FuelDiesel
Frequency60.0 Hz
Standby power278 kW
Standby kVA348
Prime power256 kW
EmissionsTier III approved
ControllerMagnum Digital (MDC)
Oil capacity34.0 L
AlternatorMarathon 432PSL6210
Voltage options480 V
Phase3
Rated current334.4 A
Power factor1
Circuit breaker1200 A
Battery groupGroup 31
Battery cranking1000 CCA
Battery voltage12V V
Battery quantity2
Coolant capacity70.9 L
Max ambient120°F °C
Dimensions (L×W×H)3960×1520×2290 mm
Dry weight3646 kg
Wet weight5215 kg
Sound level68.0 dBA @ 23 ft m
Fuel tank459.0 L
Tank runtime24 hr

Engine

John Deere 6090HF485
Oil capacity34.0 L
Coolant capacity38.0 L
Displacement9.0 L
Aspirationturbocharged, intercooled
Rated speed1500 rpm

Filters for the John Deere 6090HF485

5

Engine-mounted filters the filter manufacturers list for this engine family. These come from the engine, not from this generator set’s own parts list, so confirm against your serial number before ordering.

SystemFilterDescriptionCross-references
Oil filterP550938Lube Filter, CartridgeJOHN DEERE RE509672, JOHN DEERE RE530656, NAPA 1370, LIEBHERR 11212420 KuduParts $16.00
Fuel filterP550090Fuel Filter, In-LineJOHN DEERE AE20952, JOHN DEERE AT101565, ASV INCORPORATED 0201914, LOESING 025125 FridayParts $45.66
Fuel filterP502392Fuel Filter, BoxJOHN DEERE N378886, BALDWIN BF7912, SEPAR 01030, SEPAR 01030HV FridayParts $39.99
Fuel / water separatorP552952Fuel Filter, Water Separator Spin-OnJOHN DEERE DZ130550, JOHN DEERE RE532952, NAPA 3969, BALDWIN BF9866-O FridayParts $59.99
Fuel / water separatorP551858Fuel Filter, Water Separator Spin-OnJOHN DEERE AT365869, JOHN DEERE RE503676, NAPA 3780, BALDWIN BF1265 FridayParts $39.00 KuduParts $48.00

Same engine, other brands

1 brand

The John Deere 6090HF485 in this set also powers 1 generator set sold under 1 other brand. Service parts and maintenance intervals for the engine are shared; enclosure, alternator, controller and ratings are not.

BrandModels
John DeereQAS 330

Maintenance & consumables

for the John Deere 6090HF485
ItemSpecCapacityPart #Interval
Air filterReplace when restriction indicator gauge shows a vacuum of 20 in. H2O (yellow center bar reaches red section); replace primary air cleaner at 25 in. H2O—1500 hr
Fuel filterFuel Filter—2000 hr
Oil filterlast changed 10/25/2024RE5382458803 hr Amazon eBay $39.99 NAPA $33.32 KuduParts $16.00
BatteryGroup 31, 1000 CCA—500 hr
BeltFan Belt—2000 hr
CoolantConsult the engine operation and maintenance manual for coolant recommendations and proper mixture16.0—3000 hr
Coolant filterGlycol level in coolant—2000 hr
OilJohn Deere PLUS-50 or equivalent45.0—2000 hr
Spark plugSpark Plug—1000 hr

Compatible filters for the John Deere 6090HF485 — cross-referenced via Donaldson. Options to verify against your serial number, not confirmed for this exact unit.

  • Air filter: John Deere RE587794 John Deere 4S00686R John Deere AH115833 John Deere F071151 John Deere F071150
  • Fuel filter: John Deere N378886 John Deere AR103220 John Deere RE522688 John Deere AT365869 John Deere RE539465

Service intervals

21
ItemActionHoursMonthsNotes
Engine oil and oil filterChange250 hrFirst service — Change after first 100 hours, then every 250 hours. If John Deere PLUS-50 or equivalent is used, every 500 hours.
Oil vapor recirculation system/non-return valveCheck250 hr
Air intake hoses, connections, and systemCheck500 hr12 mo
BatteryInspect500 hr12 moService battery
Belt tensioner and belt wearCheck500 hr12 moAt 500 hour/12 month interval, remove belt and check for wear; inspect pulleys and bearings
Coolant pump weep hole foam filterCheck500 hr12 mo
Cooling systemCheck500 hr12 mo
Engine ground connectionCheck500 hr12 mo
Engine mountsCheck500 hr12 mo
Fuel filters/water separatorReplace500 hr12 moReplace fuel filters/clean water separator
Generator drive plate torqueCheck500 hr12 moSee page 45
Leveling jack(s)Lubricate500 hr12 mo
Oil vapor recirculation filterReplace500 hr12 mo
ThermostatsTest500 hr12 mo
Air cleaner elementsReplace2000 hr24 mo
Alternator and fan beltsReplace2000 hr24 mo
CoolantCheck2000 hr24 moAdd coolant
Electrical wiring and connectionsCheck2000 hr24 mo
Fuel systemDrain2000 hr24 moBleed fuel system
FusesCheck2000 hr24 mo
Engine oil filterChange8803 hrLast changed 10/25/2024, 8803HRS

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

27
TypeItemValueUnitCondition
OtherEngine hours at test steps8801.8 / 8801.9 / 8802.1 / 8802.4 / 8802.6 / 8802.9 / 8803hourswarm up through cool down
OtherFine voltage adjustment window (V Detect)45seconds
OtherFuel level low fuel shutdown setpoint5%
OtherFuel level low fuel warning setpoint15%
OtherLoad bank output (start / 15min / 30min / 45min / 1hr)270kWat ~324-327 A per phase, 482-484 V, 60 Hz, power factor 1
PressureAir filter restriction indicator - replace element20in. H2O
PressureAir filter restriction indicator - replace primary air cleaner25in. H2O
PressureEngine oil pressure, low oil pressure shut downless than 20psi (138 kPa)
PressureEngine oil pressure, normal operating35-80psi (241-552 kPa)engine running
PressureEngine oil pressure, verify within 5 seconds of start5psi (34 kPa)within 5 seconds of start
PressureOil pressure (warm up / start / 15min / 30min / 45min / 1hr / cool down)44 / 36 / 35 / 34 / 32 / 32 / 36not statedload bank test 10/25/2024
SpeedGenerator frequency, no load60.0Hzno load
SpeedOperating speed1800rpm
TemperatureAmbient temperature (warm up / start / 15min / 30min / 45min / 1hr / cool down)49 / 49°F / 49°F / 50°F / 50°F / 50°F / 50°F°Fload bank test 10/25/2024
TemperatureCoolant temperature (warm up / start / 15min / 30min / 45min / 1hr / cool down)104 / 185°F / 186°F / 186°F / 186°F / 188°F / 165°F°Fload bank test 10/25/2024
TemperatureCoolant temperature minimum display100°F (38°C)
TemperatureMaximum water/coolant temperature shut down230°F (110°C)
TemperatureViscous fan clutch temperature range170-200°F (77-93°C)
TorqueGenerator drive plate bolts33ft-lb (45 Nm)
TorqueShorting (link) board hardware25ft-lbs
TorqueTrailer wheel lug nuts, first pass20-25ft-lbs (27-33 Nm)
TorqueTrailer wheel lug nuts, second pass50-60ft-lbs (67-81 Nm)
TorqueTrailer wheel lug nuts, third pass90-120ft-lbs (122-162 Nm)
VoltageBattery voltage, normal reading on 12 volt systems13-14Vengine running
VoltageBattery voltage, normal reading on 24 volt systems24-26Vengine running
VoltageDC voltage (all steps)13.7Vload bank test 10/25/2024
VoltageVoltage regulation+/- 1%

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
Coolant60/40Cold weather applications
Engine oilJohn Deere PLUS-50 or equivalentConsult the engine operation and maintenance manual for the proper grade of oil, including special operating conditions. If John Deere PLUS-50 or equivalent is used, oil can be changed every 500 hours.
Fueldiesel459.0 galSteel, single wall fuel tank; 24 hr. run time – full load
GreaseHigh quality grease made specifically for lubrication of wheel bearingsTrailer wheel bearings; minimum lubrication every 12 months or 12,000 miles (19,312 km)

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Fault codes

31
CodeNameMeaningSeverityAction
AnInIOM SdAnInIOM SdShutdown alarm configurable on the input of IG-IOM/IGS-PTM.Shutdown
AnInIOM WrnAnInIOM WrnWarning alarm configurable on the input of IG-IOM/IGS-PTM.Warning
Battery FlatBattery Flat (low battery)If the controller switches off during starting sequence due to bad battery condition, it doesn't try to start again and activates this protection.Shutdown
Binary InputBinary InputConfigurable warning/shutdown alarms on the inputs of IL-NT.
ChrgAlternFailChrgAlternFailFailure of the alternator to charge the battery.Warning
EmergencyStopEmergencyStopIf the input Emergency Stop is opened or the red E-Stop button is pushed, shutdown is immediately activated.Shutdown
Engine Temp SdEngine Temp SdWater temperature is greater than Sd Water Temp setpoint.Shutdown
Engine Temp WrnEngine Temp WrnWater temperature is greater than Wrn Water Temp setpoint.Warning
Fgen<, >Fgen<, >The generator frequency is out of limits given by Gen >f and Gen <f setpoints.Shutdown
Fuel Level SdFuel Level SdFuel level is smaller than Sd Fuel Level setpoint (5%).Shutdown
Fuel Level WrnFuel Level WrnFuel level is smaller than Wrn Fuel Level setpoint (15%).Warning
GCB failGCB failFailure of the generator circuit breaker.Shutdown
Igen unblIgen unblThe generator current is unbalanced.Shutdown
Low BackupBattLow BackupBattRTC backup battery is flat (low).Warning
Oil Press SdOil Press SdOil pressure is smaller than Oil Press Sd setpoint.Shutdown
Oil Press WrnOil Press WrnOil pressure is smaller than Oil Press Wrn setpoint.Warning
OverloadOverloadThe load is greater than the value given by Overload setpoint.Shutdown
OverspeedOverspeedThe protection comes active if the speed is greater than Overspeed setpoint.Shutdown
ParamFailParamFailWrong checksum of parameters. Happens typically after downloading new firmware or changing of the parameter. The controller stays in INIT mode.Check all parameters, write at least one new parameter.
PickupFaultPickupFaultFailure of the magnetic pick-up sensor for speed measurement.Shutdown
Sd IOM failSd IOM failIOM/IGS-PTM module.Shutdown
SprinkIActiveSprinkIActiveThe protection is active if the output Sprinkler is closed.Warning
Start failedStart failedUnit did not start.Shutdown
Stop failStop failUnit did not stop.Shutdown
UbatUbatBattery voltage is out of limits given by Batt Undervolt setpoints.Warning
UnderspeedUnderspeedDuring starting, when the RPM reaches Starting RPM setpoint the starter switches off and speed can drop under Start RPM again; underspeed protection becomes active. Evaluation starts 5 seconds after start up.Shutdown
Vgen unbalVgen unbalThe generator voltage is unbalanced more than the value of Volt unbal setpoint.Shutdown
Vgen<, >Vgen<, >The generator voltage is out of limits given by Gen <V and Gen >V setpoints.Shutdown
Wrn ECU AlarmWrn ECU AlarmECU alarm list is not empty.Warning
Wrn RA15 failWrn RA15 failWarning alarm in case of lost connection to IGL=RA15 module.Warning
WrnMaintenanceWrnMaintenanceThe period for servicing is set by the WrnMaintenance setpoint. The protection comes active if the running hours of the engine reach this value (250 hours).Warning

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Adjusting the Display Back Lighting adjustment
  1. Press and hold Enter.
  2. Press the up or down buttons on the Diagnostics keypad to increase or decrease brightness.
  3. Release the Enter button when the desired brightness is attained.
Changing Output Voltage adjustment

⚠ NEVER ATTEMPT TO CHANGE THE VOLTAGE WHILE THE ENGINE IS RUNNING. LETHAL VOLTAGE MAY BE PRESENT AT THE CONNECTION LUGS ON THE SHORTING (LINK) BOARD.

Tools: Wrench, Torque wrench

  1. Shut the generator down and set main circuit breaker and control power switch to OFF.
  2. Remove all 1/2 in. nuts holding the shorting (link) board.
  3. Move the board to the lower position for 480/277V 3Ø or the upper position for 208/120V 3Ø.
  4. Replace all hardware and tighten to 25 ft-lbs of torque.
  5. Reinstall the reconnect box door and start the generator per the Pre-Start Check List.
Resetting of the Time to Service Reminder adjustment
  1. With the unit shut down, power up the controller with the Control On/Off toggle switch.
  2. Press Page Select, move the cursor down to Engine Protect and press Enter.
  3. Press Enter; the current run time in hours appears under WrnMaintenance.
  4. Press the up arrow and reset the current run time hour setting to 250.
  5. Press Enter to save the current run time hour setting.
  6. Move the CONTROL ON/I toggle switch to the CONTROL OFF/O position.
Checking Generator Drive Plate Torque maintenance

Tools: Torque wrench

  1. Disconnect the engine starting battery.
  2. Remove the generator fan guard.
  3. Torque each of the drive plate bolts to 33 ft-lb (45 Nm).
  4. Reinstall the generator fan guard and reconnect the battery.
Trailer Wheel Bearings maintenance

Tools: Grease gun

  1. Remove the small rubber plug on the grease cap.
  2. Attach a standard grease gun fitting to the grease zerk fitting.
  3. Pump grease into the fitting until new grease is visible around the nozzle.
  4. Wipe any excess grease from the hub and replace the rubber plug.
AUTO (Remote) Starting of the Generator operation
  1. Perform a manual start of the generator at least once to verify correct operation.
  2. Press the AUTO button; LCD window highlights AUTO in the upper left corner.
  3. Close the main circuit breaker (set to ON/I).
  4. Secure the generator by closing and locking all access doors.
  5. The generator is now ready for remote starting.
Auto Exercise Timer operation

⚠ The controller must be in AUTO mode to run at the programmed time.

  1. Press the PAGE SELECT button until Password appears at the top of the screen.
  2. Press the down arrow to select Date/Time and press ENTER.
  3. Press the down arrow to select Timer1 Repeat and press ENTER; choose the day(s) and press ENTER.
  4. Select Timer1 ON Time and press ENTER; adjust the desired start time.
  5. Select Timer1Duration and press ENTER; set the run duration.
  6. Press PAGE SELECT three times to return to the main menu.
  7. Press the AUTO button to switch modes to automatic.
Auxiliary Fuel Tank Option operation
  1. Shut down the unit and check that the internal tank fuel level is above five percent.
  2. Attach the auxiliary fuel tank fuel lines to the AUXILIARY FUEL INLET and AUXILIARY FUEL OUTLET fittings.
  3. Open the AUXILIARY FUEL INLET and AUXILIARY FUEL OUTLET valves inside the right front door.
Fuel Transfer Pump Option operation
  1. Shut down the unit (not required if external bulk supply is already connected).
  2. Attach the external bulk fuel supply to the FUEL TRANSFER INLET fitting.
  3. Turn on the fuel transfer switch.
Manual Starting of the Generator operation

⚠ CARBON MONOXIDE: USING A GENERATOR INDOORS CAN KILL YOU IN MINUTES!

  1. Move the control ON/OFF toggle switch to the CONTROL ON/I position.
  2. LCD window indicates MAN mode and Ready; Ready/Manual LED is lit.
  3. Press the green ENGINE START button.
  4. Prestart (Preheat) screen is displayed with a countdown from 20 seconds to zero.
  5. Starting screen is displayed; the engine cranks and starts running.
  6. Running screen displays.
  7. LCD toggles between Generator Display Screen and Engine Display Screen.
  8. If engine does not start, controller pauses 15 seconds and makes two more attempts (three total).
  9. If no start after three cycles, LCD shows SD Start Fail; wait two minutes and press FAULT RESET.
  10. Engine speeds up to a constant 1800 rpm.
  11. Check for excessive noise or vibration and coolant, oil or fuel leaks before applying loads.
  12. Check AC output voltage; fine adjust with the fine voltage adjustment screw if needed.
  13. Check frequency reads approximately 60 Hz with no loads.
  14. Switch main circuit breaker ON, then convenience outlet breakers as needed.
Shutting Down the Generator operation

⚠ If the unit does not shut down within 15 seconds, a Stop Fail alarm is displayed.

  1. Open all circuit breakers to remove loads from the generator.
  2. Let the engine run approximately five minutes to allow it to cool down.
  3. Push the red ENGINE STOP button; a 15 second Stop Value timer starts.
  4. Move the CONTROL ON/OFF toggle switch to the CONTROL OFF/O position.
Towing the Trailer operation
  1. Use the jack to raise or lower the trailer onto the hitch; lock the hitch coupling.
  2. Attach the safety chains or cables to the vehicle and raise the jack foot completely.
  3. Connect trailer wiring; check stop and signal lights.
  4. Make sure all doors are properly latched.
  5. Check trailer tire inflation.
  6. Check the wheel lugs and tighten or replace any loose or missing.
  7. Limit highway towing speed to 45 mph (72 km/h).

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
Cam lock connectionsL1 - Black, L2 - Red, L3 - Blue, N (Neutral) - White, G (Ground) - GreenSeries 16 taper nose 400A, 600V cam locks; make all connections to one side only
1203Low DeltaT1, T2, T3, T4, T5, T6, T7, T8, T9, T10, T11, T12Dedicated 12 lead generators option
120/208Vthree phaseLow WyeLink / Reconnect Board
120/240Vsingle phaseZig Zag4 position phase switch option
120/240Vthree phaseDelta4 position phase switch option
208/1203Link board attached in 208 VOLT 3Ø position (upper position)T1, T2, T3, T4, T5, T6, T7, T8, T9, T10, T11, T12Shorting (link) board upper position
208/1203Low WyeT1, T2, T3, T4, T5, T6, T7, T8, T9, T10, T11, T12Dedicated 12 lead generators option
240/1201Low Zig ZagT1, T2, T3, T4, T5, T6, T7, T8, T9, T10, T11, T12Dedicated 12 lead generators option
240/1203High DeltaT1, T2, T3, T4, T5, T6, T7, T8, T9, T10, T11, T12Dedicated 12 lead generators option
277/480Vthree phaseHigh WyeLink / Reconnect Board
480/2401High Zig ZagT1, T2, T3, T4, T5, T6, T7, T8, T9, T10, T11, T12Dedicated 12 lead generators option
480/2773High WyeT1, T2, T3, T4, T5, T6, T7, T8, T9, T10, T11, T12Dedicated 12 lead generators option
480/2773Link board attached in 480 VOLT 3Ø position (lower position)T1, T2, T3, T4, T5, T6, T7, T8, T9, T10, T11, T12Shorting (link) board lower position

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

How many kW is the Magnum MMG320?

The Magnum MMG320 is rated 278 kW standby (348.0 kVA).

What engine is in the Magnum MMG320?

The Magnum MMG320 is powered by the John Deere 6090HF485 engine.

What fuel does the Magnum MMG320 use?

The Magnum MMG320 runs on Diesel.

How much oil does the Magnum MMG320 take?

The John Deere 6090HF485 engine in the Magnum MMG320 has an oil capacity of 34.0 liters.

What is the cooling system capacity of the Magnum MMG320?

The Magnum MMG320 cooling system holds 70.9 liters (18.7 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.

What is the continuous rating of the Magnum MMG320?

The Magnum MMG320 is rated 256 kW prime (320 kVA), against 278 kW standby.

How loud is the Magnum MMG320?

The Magnum MMG320 is rated at 68.0 dBA at 23 ft m, per the manufacturer specification sheet.

How much does the Magnum MMG320 weigh?

The Magnum MMG320 has a dry weight of 3646 kg (8038 lb).

How big is the fuel tank on the Magnum MMG320?

The Magnum MMG320 has a 459 liter (121 US gallon) fuel tank, giving about 24 hours of runtime.

What voltages is the Magnum MMG320 available in?

The Magnum MMG320 is offered in 480 V, 3-phase.

What size battery does the Magnum MMG320 need?

The Magnum MMG320 uses 2 batteryies, 12V V each, 1000 CCA, group Group 31, per the manufacturer specification sheet.

Which alternator is fitted to the Magnum MMG320?

The Magnum MMG320 uses a Marathon 432PSL6210 alternator.

What oil filter does the Magnum MMG320 use?

The Magnum MMG320 uses oil filter part number RE538245.

Which fuel filter part number does the Magnum MMG320 take?

The Magnum MMG320 uses fuel filter part numbers JOHN DEERE N378886, JOHN DEERE AR103220.

What air filter does the Magnum MMG320 use?

The Magnum MMG320 uses air filter part numbers JOHN DEERE RE587794, JOHN DEERE 4S00686R.

Troubleshooting

6

Symptoms & remedies

SymptomCauseRemedy
LOW FUEL LEVEL SHUT DOWNFuel level is low or fuel tank has leaks.Check and refill fuel. Inspect for leaks.
LOW OIL PRESSURE SHUT DOWNOil pressure is less than 20 psi (138 kPa).Check oil level, inspect for leaks, check oil pressure sender.
LOW COOLANT LEVEL SHUT DOWNCoolant level is low or coolant lines have leaks.Check and refill coolant. Inspect for leaks. Check engine oil for contamination.
HIGH COOLANT TEMPERATURE SHUT DOWNCoolant temperature is 230°F (110°C) or more.Check coolant level, add if necessary. Inspect for leaks. Check radiator shroud and ducting. Adjust water pump belt tension.
OVERCRANK SHUT DOWNEngine will not start.Check fuel level, fuel pump operation, air filter for blockage. Refer to engine manual for additional troubleshooting.
OVERSPEED OR UNDERSPEED SHUT DOWNEngine speed is above or below 60.0 Hz.Disconnect loads and check frequency. Adjust engine speed as needed.

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.

Parts

2
Part #DescriptionQtySystem
CB125110-200Coolant heater, HotStart, 2500W, 120V1Service part / kit eBay
GM106699-SBattery (Kohler)1Service part / kit Amazon eBay

Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.

Fuel consumption

RatingLoadL/hgal/h
Prime50%34.19.0
Prime75%50.713.4
Prime100%67.817.9

Available documents

Spec sheet — MMG320 Mobile (Magnum)Spec sheet — Magnum-MMG320-spec-sheet (Magnum)Operator's manual — Magnum-Mobile-Products-manual-operations-Diesel-Generator-MMG320-MMG405-MMG465D. (Magnum)Reference — Magnum-MMG320-SN-1302032-Load-Test-Report-and-Inspection-Checklist (Magnum)

This page was generated from the 4 manufacturer documents above by automated extraction; every figure shown is copied from one of them. How the data is compiled.