| | Cam lock connections | L1 - Black, L2 - Red, L3 - Blue, N (Neutral) - White, G (Ground) - Green | Series 16 taper nose 400A, 600V cam locks; make all connections to one side only |
| 120 | 3 | Low Delta | T1, T2, T3, T4, T5, T6, T7, T8, T9, T10, T11, T12 | Dedicated 12 lead generators option |
| 120/208V | three phase | Low Wye | | Link / Reconnect Board |
| 120/240V | single phase | Zig Zag | | 4 position phase switch option |
| 120/240V | three phase | Delta | | 4 position phase switch option |
| 208/120 | 3 | Link board attached in 208 VOLT 3Ø position (upper position) | T1, T2, T3, T4, T5, T6, T7, T8, T9, T10, T11, T12 | Shorting (link) board upper position |
| 208/120 | 3 | Low Wye | T1, T2, T3, T4, T5, T6, T7, T8, T9, T10, T11, T12 | Dedicated 12 lead generators option |
| 240/120 | 1 | Low Zig Zag | T1, T2, T3, T4, T5, T6, T7, T8, T9, T10, T11, T12 | Dedicated 12 lead generators option |
| 240/120 | 3 | High Delta | T1, T2, T3, T4, T5, T6, T7, T8, T9, T10, T11, T12 | Dedicated 12 lead generators option |
| 277/480V | three phase | High Wye | | Link / Reconnect Board |
| 480/240 | 1 | High Zig Zag | T1, T2, T3, T4, T5, T6, T7, T8, T9, T10, T11, T12 | Dedicated 12 lead generators option |
| 480/277 | 3 | High Wye | T1, T2, T3, T4, T5, T6, T7, T8, T9, T10, T11, T12 | Dedicated 12 lead generators option |
| 480/277 | 3 | Link board attached in 480 VOLT 3Ø position (lower position) | T1, T2, T3, T4, T5, T6, T7, T8, T9, T10, T11, T12 | Shorting (link) board lower position |