Home›Repair guides›Kohler›ON Load Test

Kohler — ON Load Test

Operation · Generator set

From a Kohler service manual covering: KD1250-4, KD1750, KD2000, KD2500, KD3250, KD4000, KD700-KD4000, TP-7143. Check it applies to your exact model before use.

Applies to: Kohler KD1250-4, Kohler KD1750, Kohler KD2000, Kohler KD2500, Kohler KD3250, Kohler KD4000

Before you start

  • Hazardous voltage. Moving parts. Operate only when all guards and electrical enclosures are in place.

Procedure

  1. Operate generator set under load for 30–60 minutes maintaining exhaust temperature at rated kW.
  2. Apply voltage and check for alarms or faults.
  3. Check for leaks, vibrations, or abnormal noises.
  4. Ensure exhaust gas color is normal.
  5. Check engine parameters (oil pressure, coolant temperature).
  6. Check electrical parameters (voltage, frequency, current, rotating magnetic field).
  7. If fitted, check automatic filling devices (fuel or oil).

Full service-parts list: Kohler KD1250-4 →, Kohler KD1750 →, Kohler KD2000 →, Kohler KD2500 →, Kohler KD3250 →, Kohler KD4000 →

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.