Home›Repair guides›Kohler›Fuel Metering Valve Adjustment Procedure

Kohler — Fuel Metering Valve Adjustment Procedure

Adjustments

From a Kohler service manual covering: 12RES, 12TRES, 8.5RES. Check it applies to your exact model before use.

Applies to: Kohler 12RES, Kohler 12TRES, Kohler 8.5RES, Kohler CH20 engine, Kohler CH 740 engine

Before you start

  • Adjusting fuel metering valves on emission-certified gensets may void the emission certification. Only trained authorized technicians may adjust.

Procedure

  1. Disable genset (master switch OFF, disconnect battery charger).
  2. Remove oxygen sensor plug from exhaust manifold and install oxygen sensor.
  3. Connect oxygen sensor to engine starting battery, control module, and voltmeter.
  4. Reconnect battery charger, start genset, and run to normal operating temperature.
  5. Apply rated load; measure oxygen sensor output voltage (potential to ground).
  6. Adjust fuel metering valve to obtain specified oxygen sensor output.
  7. Seal metering valve adjustment screws with thread sealant.
  8. Remove load and cool genset 5-10 minutes; stop genset.
  9. Disconnect battery negative lead first; allow exhaust to cool.
  10. Remove oxygen sensor and reinstall exhaust plug with antiseize; reconnect battery negative lead last and battery charger.

Tools required

  • Digital voltmeter (DVM) Amazon
  • UEGO oxygen sensor service kit GM29385 Amazon
  • Load bank Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Oxygen sensor reading 8.5 kW: natural gas 2.40 ±0.05 VDC, LP 2.25 ±0.05 VDC
  • Oxygen sensor reading 12 kW: natural gas 2.60 ±0.05 VDC, LP 2.60 ±0.05 VDC

Full service-parts list: Kohler 12RES →, Kohler 12TRES →, Kohler 8.5RES →

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.