Home›Repair guides›Kohler›Voltage Calibration Using RDC2 Controller Keypad and Menus

Kohler 24RCL / 30RCLH — Voltage Calibration Using RDC2 Controller Keypad and Menus

Adjustments

For the Kohler 24RCL / 30RCLH, from the Kohler service manual.

Applies to: Kohler 24RCL, Kohler KG2204 engine

Procedure

  1. With the generator set off, connect a digital multimeter to measure output voltage across L1 and L2
  2. Start the generator set by pressing RUN
  3. Navigate to the Generator Metering menu
  4. Press Select to display Volts L1-L2 and compare to the voltmeter reading
  5. If incorrect, press Select, use up/down arrows to adjust voltage to match the voltmeter, press Select to save
  6. Wait 30-60 seconds for the reading to stabilize
  7. For three-phase models, repeat for L2-L3 and L3-L1
  8. Step to Return and exit the Generator Metering menu
  9. Press OFF to stop the generator set

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Full service-parts list: Kohler 24RCL →

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.