Kohler 20RES — Clearing a Fault on the RDC2 Controller

Testing & diagnosis

For the Kohler 20RES, from the Kohler operator's manual.

Applies to: Kohler 20RES, Kohler CH1000 engine

Before you start

  • Always identify and correct the cause before resetting.

Procedure

  1. Identify and correct the cause of the fault shutdown before resetting the controller.
  2. While the fault message is displayed, press Select to go to the Overview menu.
  3. Press Select again; the active fault message is displayed.
  4. Press Select; Confirm Clear Fault: NO is displayed.
  5. Press Down arrow; Confirm Clear Fault: YES is displayed.
  6. Press Select to enter YES and clear the fault.
  7. Press Select to return to the overview menu; the controller changes to OFF mode.
  8. Press AUTO to put the generator set into automatic mode.

Full service-parts list: Kohler 20RES →

Source: Kohler operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.