Kohler 14RCA / 20RCA — Resetting the Controller after a Fault Shutdown

Testing & diagnosis · RDC2 controller

For the Kohler 14RCA / 20RCA, from the Kohler operator's manual.

Applies to: Kohler 14RCA, Kohler 20RCA, Kohler CH 740 engine, Kohler CH1000 engine

Before you start

  • Always identify and correct the fault cause before resetting

Procedure

  1. Identify and correct the cause of the fault shutdown
  2. Press Select to go to Overview menu while fault message displayed
  3. Press Select again to display active fault message
  4. Press Select; Confirm Clear Fault: NO displayed
  5. Press Up arrow; Confirm Clear Fault: YES displayed
  6. Press Select to enter YES and clear fault
  7. Press Select to return to overview menu; controller changes to OFF mode
  8. Press AUTO to return generator set to automatic mode

Full service-parts list: Kohler 14RCA →, Kohler 20RCA →

Source: Kohler operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.