Kohler 14RCA / 20RCA — Controller Fault Reset
Testing & diagnosis · RDC2 controller
For the Kohler 14RCA / 20RCA, from the Kohler operator's manual.
Applies to: Kohler 14RCA, Kohler 20RCA, Kohler CH 740 engine, Kohler CH1000 engine
Before you start
- Identify and correct cause before resetting
Procedure
- While fault message is displayed, press Select to go to Overview menu.
- Press Select again; active fault message is displayed.
- Press Select; Confirm Clear Fault: NO is displayed.
- Press Up arrow; Confirm Clear Fault: YES is displayed.
- Press Select to enter YES and clear fault.
- Press Select to return to Overview menu; controller changes to OFF mode.
- Press AUTO to put generator set into automatic mode.
Full service-parts list: Kohler 14RCA →, Kohler 20RCA →
Source: Kohler operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.