Home›Repair guides›Kohler›Controller Fault Reset

Kohler 14RCA / 20RCA — Controller Fault Reset

Testing & diagnosis · RDC2 controller

For the Kohler 14RCA / 20RCA, from the Kohler operator's manual.

Applies to: Kohler 14RCA, Kohler 20RCA, Kohler CH 740 engine, Kohler CH1000 engine

Before you start

  • Identify and correct cause before resetting

Procedure

  1. While fault message is displayed, press Select to go to Overview menu.
  2. Press Select again; active fault message is displayed.
  3. Press Select; Confirm Clear Fault: NO is displayed.
  4. Press Up arrow; Confirm Clear Fault: YES is displayed.
  5. Press Select to enter YES and clear fault.
  6. Press Select to return to Overview menu; controller changes to OFF mode.
  7. Press AUTO to put generator set into automatic mode.

Full service-parts list: Kohler 14RCA →, Kohler 20RCA →

Source: Kohler operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.