Home›Repair guides›Kohler›Checking Specific Gravity

Kohler 14RCA / 20RCA — Checking Specific Gravity

Maintenance · Battery

For the Kohler 14RCA / 20RCA, from the Kohler operator's manual.

Applies to: Kohler 14RCA, Kohler 20RCA, Kohler CH 740 engine, Kohler CH1000 engine

Before you start

  • Battery acid

Procedure

  1. Use battery hydrometer to check specific gravity of each cell.
  2. Read number at electrolyte level or adjacent to pointer.
  3. Correct reading for temperature using correction table if needed.
  4. Battery fully charged if specific gravity is 1.260 at 80°F (26.7°C).
  5. Charge battery if specific gravity is below 1.215 at 80°F (26.7°C).
  6. Difference between cells should not exceed 0.01.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Fully charged: 1.260 at 80°F (26.7°C)
  • Charge if below 1.215 at 80°F (26.7°C)
  • Cell difference max 0.01

Full service-parts list: Kohler 14RCA →, Kohler 20RCA →

Source: Kohler operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.

More Kohler repair guides →