Katolight — Manual Start
Operation · Generator set control panel
From a Katolight manual covering: 10.5 L, 12.5, D415FGJ4, D415FJJ4, D415FNJ4, D415FPJ4, D415FRJ4, D41S5FRJ4, KDGC-2001, KDGC-500, PowerTECH 10.5/12.5 L, UN-1GNOVOS. Check it applies to your exact model before use.
Applies to: Katolight D415FGJ4, Katolight D415FJJ4, Katolight D415FNJ4, Katolight D415FPJ4, Katolight D415FRJ4, Katolight D41S5FRJ4, John Deere 6125 HF 070 engine, John Deere 6125HF070 engine, Katolight 6125HF070 engine
Before you start
- Check operator's manual if engine does not start
Procedure
- Ventilate the space or open doors and windows.
- Open the generator circuit breaker.
- Place engine control in MANUAL/RUN position.
- Check frequency; 60 Hz rated speed within 3-5%.
- Check AC voltage and engine parameters on gauges.
- Close the generator circuit breaker.
Specs & values
- 60 Hz rated; governor set 60-63 Hz at no load
Full service-parts list: Katolight D415FGJ4 →, Katolight D415FJJ4 →, Katolight D415FNJ4 →, Katolight D415FPJ4 →, Katolight D415FRJ4 →, Katolight D41S5FRJ4 →, John Deere 6125 HF 070 engine →, John Deere 6125HF070 engine →
Source: Katolight manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.