Generac — Setting the Exercise Timer
Operation · Control panel / Set Exercise switch
From a Generac service manual — check it applies to your exact model before use.
Applies to: Generac GH-410 engine, Generac GT-530 engine, Generac GT-530 engine, Generac GT-990 engine
Before you start
- The exerciser will need to be reset every time the 12 volt battery is disconnected and then reconnected, and when the 15A fuse is removed.
Procedure
- Verify that the AUTO/OFF/MANUAL switch is set to AUTO.
- Press and hold the "Set Exercise Time" switch for several seconds, then release.
- All the red LEDs will flash for approximately 10 seconds and then stop.
- Once the red LEDs stop flashing, the generator will start and run for approximately 12 minutes and then shut down.
- The exerciser is now set to run at this time of day each week.
Specs & values
- Exercise run time is approximately 12 minutes.
Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.