Generac — Return to Service After Storage

Maintenance · Engine/Generator

From a Generac service manual covering: GN-190, GN-220, NP-30G, NP-40G. Check it applies to your exact model before use.

Applies to: Generac NP-30G, Generac GN-190 / GN-220 engine, Generac GN-220 engine

Procedure

  1. Verify correct oil is in the crankcase by checking the tag; if necessary drain and refill with recommended oil.
  2. Check the battery; fill all cells to proper level with distilled water (DO NOT USE TAP WATER).
  3. Recharge the battery to a 100 percent state of charge or replace if defective.
  4. Turn OFF all electrical loads; start the engine at no-load and let it warm up.
  5. Apply electrical loads to at least 50% of the unit's rated capacity.
  6. When thoroughly warmed up, turn off or disconnect all electrical loads, then shut the engine down.