Generac PRIMEPACT 70 — Testing the LP Gas System for Leaks

Installation · LP gas fuel system

For the Generac PRIMEPACT 70, from the Generac owner's manual.

Applies to: Generac PRIMEPACT 70, Generac GN-480 engine

Before you start

  • DO NOT USE ANY FLAME TO TEST FOR LEAKS.
  • Gaseous fuel lines between tank and secondary regulator are under positive pressure; outlet side of secondary regulator is negative pressure and can draw flame into a line or fitting causing an explosion.

Procedure

  1. Obtain a separate source of 12 volts DC to open the gaseous fuel solenoid valve.
  2. Test all connections, hoses, valve regulators, fittings and other fuel system parts.
  3. Test under gas or air pressure of not less than 90 psi (620 kPa).
  4. Use soap and water or an equivalent solution to check for leaks.
  5. Do not place the generator into service until the system is properly tested.

Tools required

  • Soap and water solution Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Leak test pressure not less than 90 psi (620 kPa)
  • NFPA Paragraph 318

Full service-parts list: Generac PRIMEPACT 70 →

Source: Generac owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.