Generac NP-30G / NP-40G — Return to Service After Storage
Maintenance · Engine
For the Generac NP-30G / NP-40G, from the Generac service manual.
Applies to: Generac NP-30G, Generac GN-190 / GN-220 engine, Generac GN-190 or GN-220 (see NOTE 2) engine, Generac GN-220 engine
Before you start
- DO NOT USE TAP WATER IN THE BATTERY.
Procedure
- Verify correct oil is in crankcase by checking the tag; drain and refill if necessary.
- Check battery; fill cells with distilled water and recharge to 100 percent or replace if defective.
- Turn OFF all electrical loads; start engine at no-load and let it warm up.
- Apply electrical loads to at least 50% of rated capacity.
- When thoroughly warmed up, turn off/disconnect all loads, then shut the engine down.
Specs & values
- Apply at least 50% of rated capacity
Full service-parts list: Generac NP-30G →
Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.