Home›Repair guides›Generac›Drying the Generator

Generac NP-30G / NP-40G — Drying the Generator

Maintenance · AC Generator Stator

For the Generac NP-30G / NP-40G, from the Generac service manual.

Applies to: Generac NP-30G, Generac GN-190 / GN-220 engine, Generac GN-190 or GN-220 (see NOTE 2) engine, Generac GN-220 engine

Procedure

  1. If insulation resistance is low, dry the winding before operating.
  2. Method A (heating units): enclose the generator in a covering and install heating units to raise temperature about 15-18 F (8-10 C) above ambient.
  3. Method B (forced air): use a portable forced air heater, directing heated air into the generator air intake openings; run the unit at no-load.
  4. Air temperature at point of entry into the generator should not exceed 150 F (66 C).
  5. Retest insulation resistance; replace the Stator if it still fails after cleaning and drying.

Tools required

  • Heating units or portable forced air heater Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Heating units raise temperature about 15-18 F (8-10 C) above ambient
  • Air at intake must not exceed 150 F (66 C)

Full service-parts list: Generac NP-30G →

Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.