Generac MCG1000MT2 — Shutting Down the Unit
Operation · Generator set
For the Generac MCG1000MT2, from the Generac owner's manual.
Applies to: Generac MCG1000MT2, Mitsubishi S12H-Y2PTAW-1 engine
Before you start
- Check with personnel using power before shutting down.
Procedure
- Open the Main Circuit Breaker (MCB) by pushing the Gen-Set button on the controller.
- Allow the unit to cool down (running at no-load) for approximately five minutes.
- Push the Stop (O) button on the controller.
- Turn the battery disconnect switch to the OFF position.
Specs & values
- Cool down at no-load approximately five minutes
Full service-parts list: Generac MCG1000MT2 →
Source: Generac owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.