Generac MCG1000MT2 — Shutting Down and Restarting the Generator
Maintenance · Generator set
For the Generac MCG1000MT2, from the Generac owner's manual.
Applies to: Generac MCG1000MT2, Mitsubishi S12H-Y2PTAW-1 engine
Before you start
- NEVER perform routine service unless all electrical components are shut off.
Procedure
- Ensure power to the load can be interrupted and warn equipment users.
- Push the Gen-Set button on the controller to open the Main Circuit Breaker (MCB).
- Allow the unit to cool down (running at no-load) for approximately five minutes.
- Push the Stop/Reset (O) button on the controller.
- Turn the battery disconnect switch to the OFF position.
- Perform the necessary maintenance checks or tasks.
- Turn the battery disconnect to the ON position.
- Push the Start (I) button on the controller.
- Verify all engine/generator parameters are correct, then push the Gen-Set button to close the MCB.
- Make a last visual inspection of the unit.
Specs & values
- Cool down at no-load approximately five minutes
Full service-parts list: Generac MCG1000MT2 →
Source: Generac owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.