Home›Repair guides›Generac›Auto (Remote) Starting of the Unit

Generac MCG1000MT2 — Auto (Remote) Starting of the Unit

Operation · Remote start circuit

For the Generac MCG1000MT2, from the Generac owner's manual.

Applies to: Generac MCG1000MT2, Mitsubishi S12H-Y2PTAW-1 engine

Before you start

  • Follow all safety warnings on isolating the generator with a transfer switch if used as a standby power supply.

Procedure

  1. Perform a manual start of the unit at least once to verify that the engine is operating correctly.
  2. Connect the remote start wires to terminals #12 and #34 on TB4.
  3. Remove the jumper wire from the terminal block and the engine will stop; reconnect remote start switch wires.
  4. Confirm the unit is in Auto Mode; the LCD window should show "Auto Mode" at the top of the screen.
  5. The unit is now ready for remote starting.

Tools required

  • Jumper wire minimum 16 gauge Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Remote start terminals #12 and #34 on TB4
  • TB4 located behind the main circuit breaker panel, on the left side

Full service-parts list: Generac MCG1000MT2 →

Source: Generac owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.