Operation

From a Generac service manual — check it applies to your exact model before use.

Applies to: Generac GH-410 engine, Generac GT-530 engine, Generac GT-530 engine, Generac GT-990 engine

Before you start

  • Be sure to turn off all power voltage supplies to the transfer switch before attempting manual operation.

Procedure

  1. On the generator panel, set the AUTO-OFF-MANUAL switch to OFF.
  2. Turn OFF the utility power supply to the transfer switch using whatever means provided.
  3. Set the generator main line circuit breaker to OFF (or open).
  4. Remove the manual transfer handle from the enclosure.
  5. Place the open end of the manual transfer handle over the transfer switch operating lever.
  6. To connect LOAD terminal lugs to the utility power source, move the handle upward.
  7. To connect LOAD terminals to the standby power source, move the handle downward.
  8. Actuate the switch to UTILITY and to STANDBY several times. Make sure no evidence of binding or interference is felt.
  9. When satisfied that manual transfer switch operation is correct, actuate the main contacts to their UTILITY position.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.