Generac — Checking Automatic Operation
Operation · Generator / transfer switch system
From a Generac service manual — check it applies to your exact model before use.
Applies to: Generac GH-410 engine, Generac GT-530 engine, Generac GT-530 engine, Generac GT-990 engine
Procedure
- Set generator main circuit breaker to its OFF (or open) position.
- Check that the AUTO-OFF-MANUAL switch is set to OFF.
- Turn off the utility power supply to the transfer switch using means provided.
- Manually set the transfer switch to the UTILITY position.
- Turn on the utility power supply to the transfer switch.
- Set the AUTO-OFF-MANUAL switch to AUTO. The system is now ready for automatic operation.
- Turn off the utility power supply to the transfer switch. The engine should crank and start and the transfer switch should connect load circuits to the standby side.
- With the generator running, turn ON the utility power supply; after about fifteen seconds the switch should transfer loads back to the utility power source.
- About one minute after retransfer, the engine should shut down.
Specs & values
- Retransfer time delay about 15 seconds; engine cool-down about 1 minute.
Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.