Generac — Break-in Procedure

Operation · Generator

From a Generac owner's manual — check it applies to your exact model before use.

Applies to: Generac GT-990 engine, Generac GH-410 engine

Procedure

  1. Set the Auto/Off/Manual switch to AUTO.
  2. Turn OFF the utility power supply to the transfer switch.
  3. Unit starts and transfer switch transfers to standby.
  4. Load to approximately 25% rated load and run for one hour.
  5. Run one hour at 50% rated load.
  6. Run one hour at 75% rated load.
  7. Run one hour at 100% rated load.
  8. Turn ON utility power; unit runs one minute then shuts down.
  9. Allow the unit to cool.
  10. Set switch to OFF; remove 5A and 15A fuses; disconnect battery cables.
  11. Drain the oil and replace the oil filter; refill with synthetic oil.
  12. Reconnect battery cables and insert the 5A and 15A fuses.

Specs & values

  • Run at 25%, 50%, 75% and 100% rated load, one hour each

Source: Generac owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.