Generac — Break-in Procedure
Operation · Generator
From a Generac owner's manual — check it applies to your exact model before use.
Applies to: Generac GT-990 engine, Generac GH-410 engine
Procedure
- Set the Auto/Off/Manual switch to AUTO.
- Turn OFF the utility power supply to the transfer switch.
- Unit starts and transfer switch transfers to standby.
- Load to approximately 25% rated load and run for one hour.
- Run one hour at 50% rated load.
- Run one hour at 75% rated load.
- Run one hour at 100% rated load.
- Turn ON utility power; unit runs one minute then shuts down.
- Allow the unit to cool.
- Set switch to OFF; remove 5A and 15A fuses; disconnect battery cables.
- Drain the oil and replace the oil filter; refill with synthetic oil.
- Reconnect battery cables and insert the 5A and 15A fuses.
Specs & values
- Run at 25%, 50%, 75% and 100% rated load, one hour each
Source: Generac owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.