Cummins/Onan — TESTING GENERATOR STATOR
For these Cummins/Onan models: MDL3, MDL4, MDL6.
Applies to: Cummins Onan Mdl3, Cummins Onan Mdl4, Cummins Onan Mdl6
Procedure
- Remove rotor leads F1+ and F2- from the rotating MEGGER OR INSULATION RESISTANCE METER CA-1010 rectifier assemblies.
- Connect test leads between F1+ and rotor shaft.
- If less than 100,000 ohms, rotor is questionable.
Source: manual:934-0500 Onan MDL3 MDL4 MDL6 Marine Genset Service manual (08-1991).pdf. Figures and steps are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.