Cummins/Onan MDL3 Generator Set

The Cummins/Onan MDL3 is a 12 kW (12.5 kVA) No.2 Diesel standby generator set powered by a Cummins/Onan 3A1.7 engine. It is available at 344 V, 3-phase and 50 Hz. It holds about 6 L (1.6 gal) of oil and 10 L (2.6 gal) of coolant, with a maximum ambient rating of 30 °C. Starting uses 1 group-12 battery rated 500 CCA at 12 V. An integrated tank holds 57 L (15.1 gal).

12 kW
Standby
6.0 L
Oil capacity
2
Document types

How to read your Cummins/Onan serial & model number →

Specifications

FuelNo.2 Diesel
Frequency50.0 Hz
Standby power12 kW
Standby kVA12
Prime power10 kW
Oil capacity6.0 L
Voltage options344 V
Phase3
Power factor0.8
Battery group12
Battery cranking500 CCA
Battery voltage12 V
Battery quantity1
Coolant capacity10 L
Max ambient[30, 40] °C
Fuel tank57.0 L

Engine

Cummins/Onan 3A1.7
Rated speed1800 rpm

Maintenance & consumables

for the Cummins/Onan 3A1.7
ItemSpecCapacityPart #Interval
Air filterCheck for oil, fuel, cooling and exhaust system leaks. Check exhaust system audibly and visually. find
Fuel filterFSl496 PartsGeek
Oil filter500 hr find
Belt60 pounds (267 N)3 hr find
Coolant
Coolant filter find
Oil

Common questions

What is the power rating of the Cummins/Onan MDL3?

The Cummins/Onan MDL3 is rated 12 kW standby (12.5 kVA).

What engine does the Cummins/Onan MDL3 use?

The Cummins/Onan MDL3 is powered by the Cummins/Onan 3A1.7 engine.

What fuel does the Cummins/Onan MDL3 use?

The Cummins/Onan MDL3 runs on No.2 Diesel.

Troubleshooting

6

Symptoms & remedies

SymptomCauseRemedy
Engine does not crank.Battery dead.Check battery per Checkout [A] and recharge or replace. Check battery charger operation per jumper battery cable B+ connection to 81 starter solenoid terminal. Does engine crank? If no, check battery cables for clean tight connections and motor-if bad, repair or replace. (ref. Checkout [B]). Check B1 starter solenoid With S11 in Start position, is battery voltage present between K11 terminal S and ground? If not, check B+_/wiring between K11 and B1 solenoid terminal. Replace if bad. If K11 does not energize, test per Checkout [D] and replace if bad. Is battery voltage present at B1 solenoid terminal with S11 in Start position. Check breakers CB11, CB13, or fuse F1. Check S11 and replace if bad. Check B+/wiring to S11 start terminal and K11 -S terminal.
Engine cranks but does not start.Heater circuit operating improperly or incorrect fuel.Check heater solenoid K13 per Checkout [HI. Check diodes CR2 and CR3, wiring, heaters, and resistors START. Check fuel supply system: fuel tank level, shutoff valves, fuel lines and connections, fuel filters, transfer pump and injection blue-white, and fuel flow steady from fuel return line. Check fault reset breaker. Check B+ circuit through K11-I to Engine monitor board terminal All-1, All-CB12 Line, All-SW B+, to K1. Does K1 fuel solenoid energize when S l l is in Start position? Incorrect fuel? See Operator’s Manual recommendations.
Engine starts but stops after running several seconds.A fault condition indicated by fault breaker CB12 on control panel or DC control breaker trips when the generator set is started.Check for a possible fault condition. If none, check fault monitors S1 through S5 and fault breaker CB12 for improper wiring. Check all B+ wiring for shorts to ground.
NO AC OUTPUT VOLTAGE AT RATED ENGINE RPMCheck lead continuity between AC terminals on A1 and terminals 2 and 3 on VR21 per TEST [Ml. Replace defective field breaker. Remove one lead from breaker and check continuity with ohmmeter. Is breaker open? Is control panel field breaker CB21 on?
Voltage is unstable, high or lowPush to reset breaker. Does generator AC output voltage build up? If no, flash exciter field per TEST [D]. Does generator output voltage build up?
Residual voltage across terminals 2 and 3 of VR21 is less than 5 to 10 VACDisconnect stator leads from leads 1 and 2 from AC across the leads. Is residual voltage 4 and 5,5 VDC or more now? Check reactor CMR21 and transformer T21 per TESTS (B) and (E). For shorts per TEST [MI.

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.

Parts

15
Part #DescriptionQtySystem
102-3456Drip Pan1Drip pan PartsGeek
102-7890Hold Down Clamps or Through Bolts (1/2 inch [13 mm])2Hold down clamps or through bolts PartsGeek
122-0602Fuel Filter Element ESN 5312 6274 and Below MDL3Fuel filter PartsGeek
122-0764Fuel Filter Element ESN 5312 6275 and Up MDL3Fuel filter PartsGeek
149-1758Fuel Filter Element MDL3, MDL4Fuel filter PartsGeek
149-2289Glow Plug MDL3, MDL4, MDL6 (12 Volt)Glow plug PartsGeek
333-0220Glow Plug MDL3, MDL4, MDL6 (12 Volt)Glow plug PartsGeek
511-0147-14Water Pump Belt MDL3, MDL4, MDL6Water pump belt PartsGeek
FSl245Battery1Battery PartsGeek
FSl496Fuel Filter1Fuel filter PartsGeek
yl67B-2Fuel Line TeeFuel filter PartsGeek
934-05001Service part / kit PartsGeek
934-06021Service part / kit PartsGeek
SG13753rAC Control BreakersService part / kit PartsGeek
sa377Resonator1Service part / kit PartsGeek

Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.

Fuel consumption

RatingLoadL/hgal/h
Prime
Prime50%3.0
Prime100%6.1
Standby

Available documents

Parts manual — 934-0229 Onan MDL3 MDL4 MDL6 (spec A) Marine Genset Parts manual (01-2010) (Cummins/Onan)Service manual — 934-0124 Onan MDL3 MDL4 MDL6 Marine Genset Operator's manual (03-1992)Service manual — 934-0500 Onan MDL3 MDL4 MDL6 Marine Genset Service manual (08-1991) (Cummins/Onan)Service manual — 934-0602 Onan MDL3 MDL4 MDL6 Marine Genset Installation manual (01-1991) (Cummins/Onan)