Cummins/Onan — Stopping at Switch Panel (Manual Mode)

Operation · PowerCommand 3200 control panel

From a Cummins/Onan operator's manual — check it applies to your exact model before use.

Applies to: Cummins/Onan DFE, Cummins/Onan DFEJ, Cummins/Onan DFEK, Cummins/Onan QSX15 engine

Before you start

  • Moving the 0/Manual/Auto switch to the 0 position causes an immediate engine shutdown (bypasses Cool-down At Idle) and displays a Cool-down Interrupted Warning message.

Procedure

  1. With the 0/Manual/Auto switch in the Manual position, press the Manual Run/Stop button to complete the normal (Local Start) shutdown sequence.
  2. The set stops after the Cool-down At Idle Timer (0 to 10 minutes) times out.
  3. If necessary, the set continues to run after time-out until coolant reaches normal operating temperature.

Specs & values

  • Cool-down At Idle Timer: 0 to 10 minutes

Full service-parts list: Cummins/Onan DFE →, Cummins/Onan DFEJ →, Cummins/Onan DFEK →

Source: Cummins/Onan operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.