Cummins/Onan — Starting at Switch Panel (Manual Mode)

Operation · PowerCommand 3200 control panel

From a Cummins/Onan operator's manual — check it applies to your exact model before use.

Applies to: Cummins/Onan DFE, Cummins/Onan DFEJ, Cummins/Onan DFEK, Cummins/Onan QSX15 engine

Procedure

  1. Move the 0/Manual/Auto switch to the Manual position and press the Manual Run/Stop button.
  2. The starter begins cranking and the engine starts; the starter disconnects.
  3. When coolant reaches operating temperature or warm-up at idle time delay is reached (0 to 300 seconds), the set ramps to rated speed and voltage.
  4. If the engine does not start, the starter disengages and the control indicates an overcrank shutdown.

Specs & values

  • Default start cycles: 3, composed of 15 seconds cranking and 15 seconds rest
  • Warm-up at idle time delay: 0 to 300 seconds

Full service-parts list: Cummins/Onan DFE →, Cummins/Onan DFEJ →, Cummins/Onan DFEK →

Source: Cummins/Onan operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.