Home›Repair guides›Cummins/Onan›Starting at Control Panel (PCC)

Cummins/Onan — Starting at Control Panel (PCC)

Operation · PowerCommand Control 3100

From a Cummins/Onan owner's manual — check it applies to your exact model before use.

Applies to: Cummins/Onan DFE, Cummins/Onan KTA19 engine

Procedure

  1. Move Run/Off/Auto switch to the Run position.
  2. Starter begins cranking; after a few seconds engine starts and starter disconnects.
  3. If engine does not start, starter disengages and control indicates overcrank shutdown.
  4. To clear overcrank, place switch in Off and momentarily press Reset.
  5. Wait two minutes for starter to cool, then repeat starting procedure.

Specs & values

  • Overcrank continuous cranking 75 seconds
  • Cycle cranking 3, 4, or 5 cycles

Full service-parts list: Cummins/Onan DFE →

Source: Cummins/Onan owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.