Cummins/Onan — Starting at Control Panel (Detector)

Operation · Detector Control

From a Cummins/Onan owner's manual — check it applies to your exact model before use.

Applies to: Cummins/Onan DFE, Cummins/Onan KTA19 engine

Procedure

  1. Move Run-Stop-Remote switch on the DC panel to the RUN position.
  2. Starter begins cranking and after a few seconds engine should start.
  3. Starter disconnects automatically.
  4. To clear overcrank fault, place switch in STOP and momentarily press Reset.
  5. Wait two minutes for starter to cool, then repeat.

Specs & values

  • Cycle cranking: 15 seconds crank per cycle, 3 cycles
  • Optional overcrank control cranks up to 75 seconds