Home›Repair guides›Cummins/Onan›Returning the Unit to Service After Storage

Cummins/Onan — Returning the Unit to Service After Storage

Maintenance · generating plant

From a Cummins/Onan owner's manual covering: 10HQ, 10HQ-150R, 15HQ, 15HQ-150R, 15HQ-4R30. Check it applies to your exact model before use.

Applies to: Cummins/Onan 10HQ, Cummins/Onan 10HQ-150R, Cummins/Onan 15HQ, Cummins/Onan 15HQ-150R, Cummins/Onan 15HQ-4R30, Continental F162 engine

Before you start

  • Always connect the ground cable lastly.

Procedure

  1. Remove protective grease coatings and wipe the unit clean.
  2. Inspect unit for damage and service as needed.
  3. Remove the plug from the exhaust outlet.
  4. Remove, clean and adjust spark plugs; crank engine by hand to distribute oil.
  5. Examine all fuel, oil and water lines and connections; service as needed.
  6. Refill cooling system; refill crankcase and air cleaner with correct oil.
  7. Check for leaks and correct before starting.
  8. Connect battery cables, grounding cable last; start in the regular manner.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Full service-parts list: Cummins/Onan 10HQ →, Cummins/Onan 10HQ-150R →, Cummins/Onan 15HQ →, Cummins/Onan 15HQ-150R →, Cummins/Onan 15HQ-4R30 →, Continental F162 engine →

Source: Cummins/Onan owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.