Home›Repair guides›Cummins/Onan›Reading Fault Codes Using Warning/Shutdown Indicators

Cummins/Onan — Reading Fault Codes Using Warning/Shutdown Indicators

Testing & diagnosis · Control panel status indicators

From a Cummins/Onan operator's manual — check it applies to your exact model before use.

Applies to: Cummins/Onan DFE, Cummins/Onan DFEJ, Cummins/Onan DFEK, Cummins/Onan QSX15 engine

Procedure

  1. If the Warning or Shutdown status indicator is lit, press and hold the Fault Acknowledge button and release after one second or more.
  2. The Warning lamp remains on for 2 seconds, then the Shutdown lamp blinks the fault code.
  3. A three-digit code is three sets of blinks separated by a two-second pause (hundreds, tens, ones).
  4. The sequence occurs three times per code; the fourth Warning flash indicates the next code.
  5. Codes are displayed in succession starting with the most recent (up to 32 stored).
  6. To return to the most recent fault code, press and release the Fault Acknowledge button (less than one second) and repeat.

Specs & values

  • Example Code No. 213: Shutdown LED blink-blink-pause-blink-pause-blink-blink-blink; Warning LED blink (2 seconds)

Full service-parts list: Cummins/Onan DFE →, Cummins/Onan DFEJ →, Cummins/Onan DFEK →

Source: Cummins/Onan operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.