Cummins/Onan PCC 2100 — Starting at the Control Panel (Manual Mode)
Operation · PowerCommand 2100 control
For the Cummins/Onan PCC 2100, from the Cummins/Onan operator's manual.
Applies to: Cummins/Onan GGHE, Cummins/Onan GGHF, Cummins/Onan WSG-1068 engine
Procedure
- Turn the O/Manual/Auto switch to the Manual position and press the Manual Run/Stop button.
- Starter begins cranking and, after a few seconds, the engine starts and the starter disconnects.
- Control completes warm-up at idle (if enabled) then ramps to rated speed and voltage.
Specs & values
- Warm-up at idle time delay 0-300 seconds
Full service-parts list: Cummins/Onan GGHE →, Cummins/Onan GGHF →
Source: Cummins/Onan operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.